INSTALLATION AND MAINTENANCE INSTRUCTIONS
MP120KLA
120 VAC Adapter Mounting Plate

PRODUCT SPECIFICATIONS

Standard Operating Temperature:
Humidity Range:
Nominal Voltage:
Operating Voltage Range:
Current Draw From AC Line:
MP120KLA may be used with any standard L-Series indoor Horns, Strobes, or Horn Strobes, at all horn and strobe settings.
NOTICE: This manual shall be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The MP120KLA mounting plate is designed to allow the use of 120 VAC to
power L-Series indoor horn, strobes, horn strobes, chimes, and chime strobes.
The MP120KLA consists of a mounting plate that has been fitted with a power
supply that converts 120VAC to nominal 24V FWR.
The MP120KLA must be installed using a 120 VAC power source. This unit
can only be used for non-synchronous applications; it will NOT work with
System Sensor Sync•Circuit Modules.

WIRING

This module has pig-tail wires and is intended to be wired without rigid con-
nections inside a standard electrical box.
FIGURE 1. NON-SYNCHRONIZED DEVICES; ANY COMBINATION OF MODELS POWERED BY A 2-WIRE CIRCUIT
120 VAC
Power
FIGURE 2. WALL-MOUNTING (INDOOR ONLY)
4x4x2
–40°F to 151°F (–40°C to 66°C)
10 to 93% non-condensing (indoor products)
Regulated 120 VAC
96-132 VAC
150 mA max.
Horn
1
/
" BACKBOX
120V WIRES
8

MOUNTING (WALL)

1.
For indoor applications, attach the mounting plate as shown in Figure 2.
The mounting plate is compatible only with 4 × 4 electrical boxes.
2.
Connect field wiring. (For indoor models only)
3.
If the product is not to be installed at this point, use the protective dust
cover to prevent contamination of the mounting plate terminals.
4.
To attach product to mounting plate:
a. Remove the protective dust cover.
b. Hook the tabs on the top of the product housing into the grooves on
mounting plate.
c. Pivot the product into position to engage the terminals on the mount-
ing plate. Make sure that the tabs on the back of the product housing
fully engage with the mounting plate.
d. Hold product in place with one hand, and secure product by tighten-
ing the single mounting screw in the front of the product housing.
Horn Strobe
Strobe Only
120V MOUNTING PLATE
(Shipped mounted to MP120KL Module)
L-SERIES WALL-MOUNT
NOTIFICATION APPLIANCE
1
6335 Edwards Blvd. Mississauga, ON L5T 2W7
800/736-7672, FAX: 905-812-0771
www.systemsensor.ca
Two Wire System
Any Mix of Models
Wired for Tandem
Operation
A0526CDN-01
A0356-01
I56-9107-002
12/13/2018

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MP120KLA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for System Sensor MP120KLA

  • Page 1 Current Draw From AC Line: 150 mA max. MP120KLA may be used with any standard L-Series indoor Horns, Strobes, or Horn Strobes, at all horn and strobe settings. NOTICE: This manual shall be left with the owner/user of this equipment.
  • Page 2 Attach the round mating plate that ships with the notification appliance ing plate. Make sure that the tabs on the back of the product housing to the MP120KLA module. Attach with the 4 screws from Step 1 and fully engage with the mounting plate.

This manual is also suitable for:

Mp120ka

Table of Contents