Flaring Work and Connection of Piping
Installation
• This unit may be installed suspended from the ceiling or mounted on the wall.
• This unit may only be installed horizontally , as shown in the diagram below.(Side B is facing up)
However, it may be freely installed in any direction forward or back, and to the sides.
• Be sure to leave a 600mm square opening for service and inspection as shown in the diagram
below, for both ceiling - suspended installation and wall-mounted installation.
• This unit "does not require drain treatment" as it uses internal foam treatment as low-pressure
piping insulation.
• Service direction is the side B and C
• The piping for the indoor unit may be led around in direction A
• The inclination of side B must be within ±5 degrees forward or back or to the sides.
A
Suspension bolt pitch.
(36)
50
(56)
50
Min 400
16 Multi Air Conditioner
50
50
Branch Pipe
50
50
Min 400
(Servicing space)
245
Main Pipe
72
300
Cover Control
Ø19.05
Ø9.52
30
50
60
Inspection opening
600
B
C