Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
The HS-24 Appliance can be field set to provide either Continuous Horn or Code 3 Horn. It can provide a continuous horn tone
when connected directly to the Fire Alarm Control Panel (FACP), or synchronized Code 3 Horn when used in conjunction with
the Sync Module (SM), Dual Sync Module (DSM) or Wheelock's Power Supplies. Audible Horn Appliance can be field set to
provide either High (HI) dBA, Medium (MED) dBA or Low (LO) dBA sound output and can be used on coded systems in
which the applied voltage is cycled on and off. The HS-24 Appliance is UL Listed under Standard 464 for Audible Signal
Appliances and also ULC Listed under Standard CAN/ULC-S525-99 for Audible Signaling Appliances for Fire Alarm Systems.
It is listed for indoor use only and can be mounted to double-gang, 4" backbox, 100mm European backbox or SHBB surface
backbox (See Mounting Options).
The HS-24 is designed for use with either filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage. All inputs are
polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
WARNING:
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.
FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS
COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR OPERATION
OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE
AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE HS-24 APPLIANCE IS A "FIRE ALARM DEVICE – DO NOT PAINT."
SPECIFICATIONS:
Model
HS-24
Model
HS-24
Copyright 2005 Wheelock, Inc. All rights reserved.
Thank you for using our products.
INSTALLATION INSTRUCTIONS
HS-24 APPLIANCE
Table 1: UL Listed Models and Ratings
Regulated
Voltage Range Limit
Voltage
Per UL 464
(VDC/VRMS)
DC
24
FWR
Table 1A: ULC Current Ratings (AMPS)
ULC
Lo
Voltage
MEAN
20.0VDC
0.014
24.0VDC
0.017
31.0VDC
0.021
20.0VRMS
------
24.0VRMS
------
31.0VRMS
------
. All warnings are printed in bold capital letters.
Maximum RMS Current (AMPS)
Lo
16-33VDC
0.027
16-33VRMS
0.041
Med
RMS
MEAN
RMS
0.018
0.020
0.033
0.024
0.026
0.052
0.027
0.035
0.068
0.016
------
0.028
0.031
------
0.043
0.041
------
0.050
Med
Hi
0.068
0.110
0.050
0.094
Hi
MEAN
RMS
0.035
0.067
0.055
0.098
0.069
0.110
------
0.052
------
0.075
------
0.094
Sheet 1 of 6
P84432 G

Advertisement

loading

Summary of Contents for Wheelock HS-24

  • Page 1 GENERAL: The HS-24 Appliance can be field set to provide either Continuous Horn or Code 3 Horn. It can provide a continuous horn tone when connected directly to the Fire Alarm Control Panel (FACP), or synchronized Code 3 Horn when used in conjunction with the Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies.
  • Page 2 -6dB NOTES: 1. The HS-24 is UL Listed for indoor use with a temperature range of +32°F to +120°F (0°C to +49°C) and maximum humidity of 93% ± 2% RH. WARNING: FOR UL APPLICATIONS THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR).
  • Page 3 WARNING: THE HS-24 APPLIANCE MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE IT IS INSTALLED. THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS.
  • Page 4: Mounting Options

    NOTE: The HS-24 must be set for Code 3 horn when used with the sync module. Refer to Sync Module Installation Instruction sheets SM (P83123), DSM (P83177) and Wheelock’s Power Supplies for additional information. If the HS-24 is connected to a coded system the continuous horn setting must be used Figure 3: 1.
  • Page 5: Mounting Procedures

    The HS-24 and these instructions are copyrighted by Wheelock and the HS-24 contain proprietary, confidential and trade secrets of Wheelock. No part of the HS-24 product and these instructions may be photocopied, printed or reproduced in any form or modified, adapted, changed or enhanced, or converted to another programming language, or used to create updated, related or derivative works, without the prior written consent of Wheelock.
  • Page 6 (as determined by date code). Correction of defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty.

This manual is also suitable for:

Hs-24-rHs-24-wF.01u.001.812F.01u.001.813