ESMI EB6500A Installation And Maintenance Instructions Manual

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
EB6500A AND EB6500SA REFLECTED TYPE PROJECTED
BEAM SMOKE DETECTOR

GENERAL

The model EB6500A is an addressable long range projected beam smoke
detector designed to provide open area protection.
combined transmitter/receiver unit and a reflector. Smoke entering the area
between the two components causes a reduction in the signal returned to
the receiver. When the obscuration reaches the alarm threshold, selected
at the transmitter/receiver unit, the detector generates an alarm signal.
Complete blockage of the beam causes a fault signal. Slow changes in
obscuration due to a build up of dirt or dust on the lens of the detector are
compensated for by a micro-controller that continuously monitors the signal
strength and periodically updates the alarm and fault thresholds. When the
self-compensation circuit reaches its limit, the detector generates a fault
signal, indicating the need for service. After local testing is complete, the
yellow LED will blink a pattern to indicate the level of drift compensation
employed during the test (see Blinks Output by Yellow LED table at back of
manual).
The model EB6500SA includes an integral servo controlled calibrated test
filter, which allows automatic remote alarm testing.

SPECIFICATIONS

General
Range:
Sensitivity:
Maximum angular misalignment
Environmental
Temperature:
Humidity:
Mechanical
Dimensions (Without Faceplate):
Dimensions (With Faceplate):
Adjustment Angle:
Electrical
Voltage:
Avg. Standby Current:
Advanced Protocol Mode:
Max. Alarm Current (LED on):
Max. Fault Current (LED on):
Max. Alignment Current:
External Supply (for EB6500SA
auto -alarm test only)
Remote Output (alarm):
PARTS LIST
Description
Transmitter/Receiver Unit
Paintable Trim Ring
Reflector (REFL6500)
Plug-in Terminal Blocks
Isolator Shunts
Orange Alignment Assistance Label
Instruction Manual
EB200-00-02
It consists of a
5 to 70m
70 to 100m using optional
accessory 6500-LRK/BEAMLRK
Level 1 = 25% (1.25dB)
Level 2 = 30% (1.55dB)
Level 3 = 40% (2.22dB)
Level 4 = 50% (3.01dB)
Level 5 = 30% to 50% Adjusting
(Acclimate)
Level 6 = 40% to 50% Adjusting
(Acclimate)
Detector ± 0.5°
Reflector ± 10°
-30°C to 55°C
10% to 95% Relative Humidity
(Non-condensing)
229mm x 178mm x 84mm
253mm x 193mm x 84mm
0.3 mm² to 3.2 mm²
±10° Horizontal and Vertical
15 to 32 VDC (15-28.5V when
using isolators)
2mA @ 24VDC; 1 comm. every
5sec, LED flashing.
Read 16 sec. LED blink 8 sec
8.5mA
4.5mA
20mA
Voltage:
15 to 32 VDC
Current:
0.5A Max.
Voltage:
15 to 32VDC
Current:
6mA to 15mA.
Limited by 2.2KΩ resistor
Quantity
1
1
1
3
2
1
1

APPROVED ACCESSORIES

6500-LRK/BEAMLRK
Long Range Kit comprising three additional 20cm x 20cm reflectors,
which may be mounted in a square with the supplied reflector, permitting
the detector to be used for ranges from 70m to 100m.
6500-MMK/BEAMMMK
Multi-Mounting Kit allowing the EB6500A to be mounted to ceilings, or to
walls where the detector and reflector cannot be mounted within 10° of
one another.
One kit mounts either the transmitter/receiver unit or
reflector. If the transmitter/receiver is mounted on the MMK, then the
6500-SMK/BEAMSMK must be used. Note that only a single 20cm x
20cm reflector can be mounted using the MMK:
BEAMLRK is not compatible with the MMK.
6500-SMK/BEAMSMK
Surface Mounting Kit for the transmitter receiver (also used in
combination with the 6500-MMK/BEAMMMK) to give an additional 43mm
depth to assist surface mounting and to permit side entry cabling.
RTS151KEY
Remote test and annunciator accessory that enables the detector to be
tested remotely, providing test and reset functions, it has a Red LED to
indicate alarm conditions (Note: Back-box, if required, needs to be ordered
separately - part number WM2348).

DETECTOR MOUNTING

Location

The EB6500A must be located in accordance with local standards and
guidelines, for example BS5839 part 1. For general information, refer to
the application guide for projected beam smoke detectors available on
request from your supplier.
Mounting Position
Beam detectors require a very stable mounting surface for proper
operation. A surface that moves, shifts, vibrates, or warps over time
may cause false alarm or fault conditions. Initial selection of a proper
mounting surface will eliminate nuisance alarms and fault signals. Mount
the detector on a stable mounting surface such as brick, concrete, a
sturdy load-bearing wall, support column, structural beam, or other
surface that is not expected to experience vibration or movement over
time. DO NOT MOUNT the beam detector on corrugated metal walls,
sheet metal walls, external building sheathing, external siding,
suspended ceilings, steel web trusses, rafters, non-structural beam,
joists, or other such surfaces.
tolerance to movement than the transmitter/receiver, hence in cases
where only one stable mounting surface as defined above can be used,
the transmitter/receiver unit should be mounted to the stable surface.
See specifications for maximum permissible angular misalignment;
movement outside these limits may cause nuisance alarms and faults.

Mounting Considerations

There must be a permanent clear line of vision between the detector
and the reflector.
Reflective objects should be a minimum of 380mm from the line of
sight between the detector and reflector to avoid compromise of the
protected area by reflected light.
Direct sunlight or strong lights into the transmitter/receiver unit
should be avoided. There should be a minimum of 10° between the
paths of the light source and the detector beam.
Operation of the detector through panes of glass should be avoided
if possible. If it is necessary to pass though glass, the angle between
the beam and glass should be set a minimum of 10° off perpendicular,
and operation through multiple panes should be avoided.
MOUNTING
The transmitter/receiver unit may be mounted directly to the wall, with
rear cable entry. The detector base has four primary mounting holes,
one in each corner of the base. All four holes must be used to provide
secure mounting. In order to mount the detector to the wall, the outer
cover must be removed after unscrewing it's four retaining screws.
1
The 6500-LRK/
The reflector has a much greater
I56-3880-000

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EB6500A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ESMI EB6500A

  • Page 1 Complete blockage of the beam causes a fault signal. Slow changes in Multi-Mounting Kit allowing the EB6500A to be mounted to ceilings, or to walls where the detector and reflector cannot be mounted within 10° of obscuration due to a build up of dirt or dust on the lens of the detector are one another.
  • Page 2 6500-MMK/BEAMMMK instructions for mounting details. 10° * CAN BE USED FOR TERMINATING CABLE SCREENS 10° Figure 3: Detector Terminal Connections EB6500A(S) ACCEPTABLE MOUNTING LOCATIONS FOR REFLECTOR REMOTE ALARM T2-1 RTS151/KEY OUTPUT Figure 2a: Reflector Mounting Guidelines AUX (-)
  • Page 3 2. Looking through the alignment mirror at both the alignment gun sight The alignment of the EB6500A is divided into four steps: Coarse and reflector simultaneously, locate the position of the reflector in the alignment, fine adjustment, final gain adjustment, and final verification.
  • Page 4 At this time it is sensible to set the sensitivity of the detector using the sensitivity switch and digital display. See SENSITIVITY SELECTION for further details. Step 3. Final Gain Adjustment See figure 9. In this step, the detector electronically adjusts its internal gain one final time.
  • Page 5 APPROPRIATE OBSCURATION LEVEL beam smoke detector. The wiring diagram to connect the EB6500A/S to the key is displayed on page 2 of this manual. The EB6500SA is equipped with an integral sensitivity test feature that consists of a calibrated test filter attached to a servomotor inside the detector optics.
  • Page 6 Blinks Output by Yellow LED once the Device has Passed a Local Test Percent the Number of detector has blinks drifted output <10% None <20% <30% <40% <50% <60% <70% <80% <90% <100% 0832-CPD-0327 12 EN54-12: 2002 EN54-17: 2005 EB200-00-02 I56-3880-000 Pelco Finland Oy, Kalkkipellontie 6, FI-02650 Espoo, Finland...

This manual is also suitable for:

Eb6500sa

Table of Contents