TankScan TSM1000 Setup Instructions

TankScan TSM1000 Setup Instructions

Tank monitor with remote battery

Advertisement

Quick Links

TSM1000 Tank Monitor
Remote Battery Setup Instructions
Connect Battery and Test Connection
For tank farm systems with a gateway, set up gateway before connecting
1
battery. Select a spot near tank you are installing.
To power up TankScan Monitor, unscrew the screws on the cover of remote
battery pack housing and connect battery connector to remote battery pack
housing connector. Reinstall cover and tighten screws. Connect female
threaded connector of battery cable to connector on remote battery pack
housing. Connect male threaded connector of battery cable to connector on
monitor housing.
Monitor will wake up and sound 1 beep. Then a second single beep will
follow, with a third single beep for data transmission. 3 single beeps indicate
a good connection was made. If more than 3 single beeps were heard,
contact TankScan Technical Support. If 3 single beeps are confirmed, then
proceed as follows.
Disconnect battery cable from remote battery pack and mount remote
battery pack to the tank at a temporary location using magnetic back.
Explosion Hazard. Use only ATEK provided battery pack.
Take Tank Measurement
Remove any equipment from tank port to be used by monitor. TSM monitor
2
can be connected directly to tanks with a 1.5" or 2" NPT threaded opening.
Measure the total tank height from inside bottom of tank to top of tank port
3
and report this measurement to TankScan Technical Support.
Total Height:
Cut Probe Wire to Length
Determine probe wire length using Probe Length Calculation diagram
4
then measure probe wire length from wire exit point in housing base until
calculated length is reached. Make a mark at this point and trim excess wire.
Attach Accessories
Float Assembly - Slide onto probe wire if included with monitor.
5
Probe Wire Weight - Slide onto probe wire such that wire extends and is
6
flush with end of weight. Tighten weight clamp using provided hex wrench.
with
1
3
A
4
5
Probe Length
Calculation
Total
A
Height
4
Using 1.5" Thread:
Probe Length
= A - 2
Fluid
Level
Using 2" Thread:
Probe Length
= A - 2.50
= Total interior height of the tank
including any riser height.
Measure from
probe wire exit
point
6
Float Assembly
Probe Wire
Weight
www.tankscan.com