OPERATING PROCEDURE
7. Removing the 4-way valve (21S4), LEV coil (LEV(A))
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
[Removing the 4-way valve]
(4) Remove the 4-way valve fixing screw (M4
(5) Remove the 4-way valve by sliding the coil toward you.
(6) Disconnect the connector 21S4 (green) on the controller
board in the electrical parts box.
[Removing the linear expansion valve coil]
(4) Remove the LEV coil by sliding the coil upward.
(5) Disconnect the connectors, LEV A (white), on the controller
circuit board in the electrical parts box.
8. Removing the 4-way valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 valve bed fixing screws (4
valve and stop valve fixing screws (5
remove the valve bed.
(5) Remove 3 right side panel fixing screws (5
rear of the unit and then remove the right side panel.
(6) Remove the 4-way valve. (See photo 7.)
(7) Recover refrigerant.
(8) Remove the welded part of 4-way valve.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by remov-
ing the right side panel.
Note 3: When installing the four-way valve, cover it with a wet
cloth to prevent it from heating (120°C or more), then
braze the pipes so that the inside of pipes are not oxi-
dized.
9. Removing the LEV
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 valve bed fixing screws (4
valve and stop valve fixing screws (5
remove the valve bed.
(5) Remove 3 right side panel fixing screws (5
rear of the unit and then remove the right side panel.
(6) Remove the LEV. (See photo 7.)
(7) Recover refrigerant.
(8) Remove the welded part of LEV.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by remov-
ing the right side panel.
Note 3: When installing the LEV, cover it with a wet cloth
to prevent it from heating (120°C or more), then
braze the pipes so that the inside of pipes are not
oxidized.
Photo 7
6).
Photo 8
10) and 4 ball
16) and then
10) in the
LEV
10) and 4 ball
16) and then
10) in the
92
PHOTOS
4-way valve
LEV coil (LEV A)
fixing screw
4-way valve
LEV coil (LEV A)
4-way valve
4-way valve
(21S4)