Download Print this page

Honeywell MultiPRO TB7100A1000/U Manual page 15

Multispeed and multipurpose thermostat for conventional, heat pump, fan coil and ptac systems

Advertisement

Installer
Setup
Installer Setup
Number
Name
0700
Temperature
Display Offset
0710
Restore Factory
Defaults
0720
Screen Display
INSTALLER TESTS
Test 1
Installer Test
Cool
Test 2
Installer Test
Fan
Test 3
Installer Test
Heat
Test 4
Installer Test EM
Heat
NOTE: Press the Done button to exit the Installer System Test.
MAIN SCREEN
LOWERS TEMPERATURE SETTING OR
MAKES SELECTIONS IN OTHER SCREENS
UP ARROW BUTTON
RAISES TEMPERATURE SETTING OR
MAKES SELECTIONS IN OTHER SCREENS
System
Cool
System & Fan
SCHEDULE BUTTON
SELECTS PROGRAMMING
MODE
SYSTEM & FAN BUTTON
SELECTS FAN AUTO OR ON
SELECTS HEAT, OFF, COOL
AND EM HEAT
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 6. Installer Setup Menu. (Continued)
Default
Setting
All Settings
0
-3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
0
0—No
1—Yes
2
0—Display Room Temperature
1—Display Setpoint
2—Display Both
0
0—Off
1—Cool Stage 1
0
0—Off
1—Fan Stage 1
2—Fan Stage 2
3—Fan Stage 3
0
0—Off
1—Heat Stage 1
0
0—EM Heat Off
1—EM Heat On
DOWN BUTTON
Set To
Fan Auto
Schedule
Clock & More
CLOCK &
MORE BUTTON
SELECTS TIME AND
FURNACE FILTER
INFORMATION
M22316
This offset applies to both the control temperature
and to the display temperature for indoor sensor (and
remote indoor sensor).
Resets all ISU parameters to default values and
resets the schedule to default Energy Star. Retains
only calendar settings and time.
Only shown if system has cool stages.
Only shown if system has fan.
Only shown if system has fan.
Only shown if multi-stage HP is selected (heat pump
with more heating than cooling stages).
Fig. 33. Main screen selections.
SHOWS CURRENT
DAY OF WEEK
CURRENT
SYSTEM SETTING
CURRENT
FAN SETTING
Fig. 34. Main screen display.
15
Notes
TEMPERATURE
SETTING
CURRENT
TIME
Mon
Aux
Heat On
System
Auto
Fan Auto
System & Fan
Schedule
Clock & More
INDICATES
THERMOSTAT IS
"CALLING FOR
COOL OR HEAT"
M22317
63-2675—01

Advertisement

loading

This manual is also suitable for:

Multipro tb7100a1000