Refrigerant Piping
3. Refrigerant charging
Follow following procedure to charge the refrigerant.
1. Open all service valves
2. Run the unit with cooling mode
3. Charging the refrigerant to gas service valve during operation.
CAUTION
Never charge the refrigerant with service valves closed and unit stopped.
If charging is carried out with service valves closed and unit stopped, the compressor will be damaged.
When unit starts to run, and the unit will display ch26 error.
If trying to keep running under this condition, compressor will be broken.
36
Outdoor Unit
Refrigerant
cylinder
Open
Charging during
Open
cooling operation