Heatsink Sensor Error/Heatsink Over Heat - Samsung AQN36VFUAGM/CV Service Manual

System air conditioner
Table of Contents

Advertisement

4-4-14 Heatsink sensor error/Heatsink over heat

1.Checklist :
1) Are there screws assembly in PBA-heatsink?
2) Is the gap PBA-heatsink
3) Is the fan operation normal?
4) Is the cover assembly in control-box normal?
2. Troubleshooting procedure
Restart after power off.
Are there screws in PBA-heatsink?
(4 screws)
Is the fan operation normal?
Exchange the Outdoor PBA
Samsung Electronics
Yes
Yes
Yes
No
Check the fan connection
No
Change the Fan motor
Fastening the screw
4-37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac100mntdeh/euAc100mntceh/eu

Table of Contents