  • Page 1 VoCALL CFVCCM9 Compact Master & VoCALL CFVCCS10 Compact Master Installation, Commissioning and Maintenance Manual www.acornfiresecurity.com...
  • Page 2: Product Overview

    www.acornfiresecurity.com Introduction An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters in an emergency in high rise buildings or large sites where radio communication may not work, and covers the operation of fire telephones, disabled refuge systems and the Disabled Toilet Alarm.
  • Page 3: Important Safety Information

    www.acornfiresecurity.com Important Safety Information This equipment must only be installed and maintained by suitably skilled and competent person. This equipment is defined as Class 1 in EN60065 (Low Voltage Directive) and must be earthed. Caution INDOOR USE ONLY SHOCK HAZARD- ARNING ISOLATE BEFORE OPENING TO REDUCE THE RISK OF FIRE OR...
  • Page 4 1 off 4 way network connector If there are any Items missing please contact your supplier or Cooper Safety Fire Systems, quoting the unit serial number, and the name on the packing list enclosed so we can rectify the situation.
  • Page 5 1 off 4 way network connector If there are any Items missing please contact your supplier or Cooper Safety Fire Systems, quoting the unit serial number, and the name on the packing list enclosed so we can rectify the situation.
  • Page 6 www.acornfiresecurity.com Preparation Remove the front door plate containing the circuit board by unscrewing the door hinge. This has a connection to the base PCB, which needs to be removed. Exercise static precautions to prevent damage to the electronics. Store the front panel assembly safely until the master handset is mounted and cables have been attached.
  • Page 7: Connecting Vocall Compact Unit

    www.acornfiresecurity.com Mounting VoCALL Compact unit The VoCALL Compact unit weighs 4Kgs with batteries, so care should be taken to securely mount the unit on stud walling. Connecting VoCALL Compact unit To comply with EMC (Electro Magnetic Compatibility) regulations and to reduce the risk of electrical interference in the system wiring, we recommend the use of fire-resistant screened cables throughout the installation.
  • Page 8 www.acornfiresecurity.com Batteries The compact requires one number 12V 5AH sealed lead acid batteries to provide backup power in the event of mains failure as defined in BS5839pt9 for 24 hours standby and 3 hours operation when powered by normal mains supply. For 72hour standby and 1 hour operation one number 12V 17AH battery is required, these will need to be fitted in an external battery enclosure.
  • Page 9 www.acornfiresecurity.com Outstation Wiring The VoCALL compact unit requires programming to determine the outstation configuration; Four types of handset are allowed on the system, type A (fixed phone) type B (hands-free refuge points), disabled toilet alarms and jack plates. For jack points a 10K EOL resistor is required at the OUT of the last plate on the line. Cable Guidance for VoCALL Compact Unit and Outstations Following the publication of BS5839pt9:2011, the guidance on cables for the VoCALL Compact unit has changed, following a relaxation in the requirements of the standard.
  • Page 10 www.acornfiresecurity.com Handsets (Type A): Hands Free Refuge Point (Type B) Disabled Toilet Alarm Master to Slave Connection www.acornfiresecurity.com...
  • Page 11: Auxiliary Connections

    www.acornfiresecurity.com Auxiliary Connections The VoCALL Compact unit has three auxiliary connections as shown below: Fault Is a normally closed volt free relay (30V DC 1A) which OPENS on any fault, including loss of power. In Use Is a normally open volt free relay (30V DC 1A) connection which closes when any outstation is operated. Enable Is a normally CLOSED input and is required to operate the system (if Jumper J1 is in place then no connection is required at the terminals.
  • Page 12 www.acornfiresecurity.com VoCALL CFVCCM9 Programming Cooper Fire Status Screen Menu Compact M9 -Healthy- Calls 10:24:01 07|01|11 On power up, or by pressing the * key, the Status Screen Menu can be accessed. The top line can be changed from the Set Site Name Menu. The second line can be changed from Set Panel Name Menu. The third line contains the status of the unit.
  • Page 13 www.acornfiresecurity.com >Log out Engineer Menu Accept faults View current faults View fault log View event log View call log View panel version Set time+date Change manager PIN Change engineer PIN Log settings Panel settings Set site name Set panel name Relay settings Set service date Panel test...
  • Page 14 www.acornfiresecurity.com Accept Fault This menu is only displayed when a new fault has occurred; entering this menu silences the fault buzzer and places an event in the event log, then returns the user to the main menu. The accept faults menu will now be hidden until a new fault occurs. View Current Fault Current faults: 1 This menu is an information only menu.
  • Page 15 www.acornfiresecurity.com View Panel Version The View panel version option will show the CFVCCM9 current software revision and the software version of any CFVCCS10 slave Panel Version:Master attached. Version:1.0 Build:1122 Build Date 02:03:11 Pressing up and down will switch from master to slave, pressing TICK will exit. Set time+date Scroll through the root menu using the navigation keys until Set time+date is selected.
  • Page 16 www.acornfiresecurity.com Change Manager PIN The default PIN to access the configuration menus is 3333, but this can be changed. Scroll through the root menu using the navigation keys until Change manager Pin is selected. Press TICK to show the Change manager PIN menu.
  • Page 17 www.acornfiresecurity.com Log Settings The CFVCCM9 has three independent Logs: Faults, Events and Calls. For each of these logs there is a menu to allow you to set the visibility to non-logged in users, or to clear the log (engineer only). Log settings Scroll through the root menu using the navigation keys until Log settings is selected.
  • Page 18 www.acornfiresecurity.com Set Site Name Set site name If the site name is to be changed, scroll through the menu options until Set site name is selected, then press the TICK button. >Cooper Fire < :Next The current site name will be displayed on screen, with the cursor on the first character. Use the navigation keys to scroll to the correct character then press TICK.
  • Page 19 www.acornfiresecurity.com Panel Test This menu option performs various tests on the panel in line with BS5839 pt 9 2011. Panel test There are four sub menus. Back >Battery test Define outstation Outstation ring Test indicators Battery Test This menu option performs a battery test when requested. The menu shows the current state of the PSU and the battery. Both the battery present test and the battery high impedance test are performed automatically (every 15 seconds, and every 3 hours respectively).
  • Page 20 www.acornfiresecurity.com Scroll to the Outstn settings menu and press TICK. This menu consists of a list of all 20 possible lines (M1 through M9 on the Outstation Settings CFVCCM9 master unit, and S1 through S10 on the CFVCCS10 slave unit, plus a back option. The outstation location is shown Select outstation with the outstation line number, along with a symbol: S10-outstation 10...
  • Page 21 www.acornfiresecurity.com Network Settings* The Network Settings for the VocALL CFVCCM9 Compact are only to be used for systems with the VOIP interface attached. These setting are not required for adding the CFVCCS10 slave unit. Press TICK Network Back >Settings Supervisor present Master present Outstations Pressing TICK again will show the settings menu, with the network option currently selected.
  • Page 22 www.acornfiresecurity.com Operation All conversations on the VoCALL Compact unit are under the command of the CFVCCM9 master handset. BS5289 Pt9 envisages the majority of calls to be made by lifting the handset of an outstation (Type A) or pressing the call button on a disabled refuge (Type B).
  • Page 23: Maintenance

    www.acornfiresecurity.com Maintenance It is a requirement of BS5839pt9 that a maintenance agreement be in place for the EVCS, the maintenance schedule should be as follows. Weekly: Lift a different handset each week and make a call to the Master. Repeat each week until all points are tested. Record results in the site log.
  • Page 24: Technical Specification

    www.acornfiresecurity.com Technical Specification www.acornfiresecurity.com...
  • Page 25 www.acornfiresecurity.com PR211-183-505-01 PINSTCFVCCM9 www.acornfiresecurity.com...