Manual call point

Advertisement

Quick Links

Speci cation
Operating
Temperature
-10 to +70°C (ambient)
Storage
Temperature
0 to +35°C
Humidity
Up to 95% non-condensing
Supply
6x AA Alkaline (Panasonic LR6AD
Powerline / Varta 4006 Industrial)
IP Rating
IP24
Operating
Frequencies
868 MHz
Output Transmitter
Power
Variable 0-14 dBm
Dimensions
89mm (W) 92mm (H) 70mm (D)
Weight
0.40kg
Regulatory information
Manufacturer
EMS Ltd.
Technology House, Sea Street,
Herne Bay, Kent, CT6 8JZ,
United Kingdom
Year of
manufacture
See serial number on unit
12
Certi cation
0359
Certi cation body
CPD Certi cate
DOP
0359-CPR-0168
Approved to
EN54-11
EN54-25
Application
Intended for use in re detection
and re alarm systems in and
around buildings. Indoor use only.
www.acornfiresecurity.com
European Union
directives
EMS declares that the radio
equipment type Ziton Wireless
Manual Call Point is in compliance
with Directive 2014/53/EU. The full
text of the EU declaration of
conformity is available at the
following internet address:
www.utcfssecurityproducts.eu/dop/
2012/19/EU (WEEE directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European
Union. For proper recycling, return
this product to your local supplier
upon purchase of equivalent new
equipment, or dispose of it at
designated collection points.
For more information see
www.recyclethis.info
Dispose of your batteries in an
environmentally friendly manner
according to your local regulations.
Contact information
For contact information, see www.utcfireandsecurity.com
www.acornfiresecurity.com
Ziton Wireless Manual Call Point Installation Guide
General
The Ziton wireless manual call point is available under
the following part number:
PART NO
VARIANT TYPE
ZR485-3
Ziton wireless manual call point
The address of the unit is set when programming the
device to the system (see programming manual for
details). The installation must conform to BS5839:Part 1
(or applicable local codes).
Installation of Ziton wireless manual call point
Loosen the back plate xing screw. Insert at bladed
instrument into the removal slot and remove the back
plate from the transmitter/battery section. (See Figure 1).
Figure 1
Mount the back box 1.4m from the oor, using suitable
xings and fasteners. A minimum of two mounting holes
must be used. Countersunk head screws must be used to
avoid the possibility of damage to the internal
components. (See Figure 2).
Wall mounting positions
Figure 2
To ensure correct operation, connect the power jumper
across the PIN header on the battery PCB located on the
rear of the call point as shown in Figure 3.
Power jumper
Figure 3

Advertisement

loading

Summary of Contents for Ziton ZR485-3

  • Page 1 0 to +35°C following internet address: General www.utcfssecurityproducts.eu/dop/ Humidity Up to 95% non-condensing The Ziton wireless manual call point is available under the following part number: Supply 6x AA Alkaline (Panasonic LR6AD 2012/19/EU (WEEE directive): Powerline / Varta 4006 Industrial)
  • Page 2 www.acornfiresecurity.com Please see commissioning manual for log on procedure details. Locate the transmitter/battery section onto the back plate. This has a hinged connection and should be located on the top edge rst. Ensure that the tamper switch operates correctly. The switch should make contact with the back plate.