Page 1
Check the software versions of the circuit boards Check the following points: • Circuit boards SCB-10 (DIEMATIC Evolution) must be in version 1.04 or higher. • All SCB-10 circuit boards must be at the same version. • Burner management circuit boards CU-GH06 must be in version 2.1 or higher.
Page 2
Check the parameters Set the cascade master boiler parameters (boiler with DIEMATIC Evolution control panel) as required. Access : Press menu key → Installation Setup → SCB-10 → Cascade management B → Parameters, counters, signals → Parameters Code / Text displayed...
Page 3
- Select and validate parameter Software Version to view the SCB-10 board version. On INICONTROL2 control panel : - Access the menus by pressing simultaneously the two keys on the right, - Select the Information Menu...
Page 4
7. Spare parts Reminder : in a cascade : All SCB-10 boards must be at the same version (at least 1.04 or higher) All CU-GH06 boards must be at the same version (at least 2.1 or higher). Appliance concerned...