SPX Cooling Technologies 1000 Engineering Data & Specifications

Cooling tower
Hide thumbs Also See for 1000:

Advertisement

Quick Links

/
/
Marley Sigma 1000/1200
Cooling Tower
Engineering Data & Specifications

Advertisement

Table of Contents
loading

Summary of Contents for SPX Cooling Technologies 1000

  • Page 1 Marley Sigma 1000/1200 Cooling Tower Engineering Data & Specifications...
  • Page 2: Table Of Contents

    Sigma 1000/1200 Marley Engineering Data 1000 Schematic 1000 Piping 1000 Support 1200 Schematic 1200 Piping 1200 Support Energy Management Environmental Specifications / Base Base Thermal Performance Construction Fan Deck and Fan Cylinder Mechanical Equipment Fill, Louvers and Drift Eliminators Hot Water Distribution System...
  • Page 3 Space does not permit definition and explanation of all of the possible options that can be applied to the Sigma. SPX Cooling Technologies realizes that you, the purchaser, must be happy with the tower's characteristics, and we are prepared to provide—or provide for—any reasonable enhancement that you are willing to define and purchase.
  • Page 4: 1000 Schematic

    Marley Sigma 1000 PLAN Tower Width Model per cell 1011 380 - 2140 21'-5" 1021 580 - 3220 21'-5" 1031 580 - 3220 23'-9" 1041 790 - 4300 26'-0" NotE 1 Last number of model indicates number of cells. Change as appropriate for your selection.
  • Page 5: 1000 Piping

    GPM. Total pumping head will be furnished at time of proposal. 3 If your application requires a bypass system, recommended location is through tower endwall into plenum area. Review of the system by SPX Cooling Technologies engineering is required. Cooling Tower Engineering Data : Piping...
  • Page 6: 1000 Support

    Marley Sigma 1000 " " " Tower Model 1011 22'-1" 1021 22'-1" 1031 24'-5" 1041 26'-8" NotE 1 Use this bulletin for preliminary layouts only. All dimensions show anchor bolt locations. Obtain current drawings from your Marley sales representative before designing supports.
  • Page 7 Marley Sigma 1000 6" MIN. PLAN 6" MIN. 1'-0 RECOMMENDED 1’-6 OPERATING WATER LEVEL FLAt BAsiN sEctioN Tower Model 1011 21'-10" 1021 21'-10" 1031 24'-2" 1041 26'-5" NotE 1 Use this bulletin for preliminary layouts only. Do not use for construction.
  • Page 8: 1200 Schematic

    Marley Sigma 1200 PLAN Tower Width Model Per Cell 1211 1050 - 5750 31'-2" 1221 1050 - 5750 33'-2" 1231 1320 - 7200 33'-2" 1241 1500 - 8650 33'-2" 1251 1500 - 8650 37'-2" 1261 1850 - 10100 37'-2" NotE 1 Last number of model indicates number of cells.
  • Page 9: 1200 Piping

    GPM. Total pumping head will be furnished at time of proposal. 3 If your application requires a bypass system, recommended location is through tower endwall into plenum area. Review of the system by SPX Cooling Technologies engineering is required. Cooling Tower Engineering Data : Piping...
  • Page 10: 1200 Support

    Marley Sigma 1200 " " " Tower Model 1211 31'-10" 1221 33'-10" 1231 33'-10" 1241 33'-10" 1251 37'-10" 1261 37'-10" NotE 1 Use this bulletin for preliminary layouts only. All dimensions show anchor bolt locations. Obtain current drawings from your Marley sales representative before designing supports.
  • Page 11 Marley Sigma 1200 PLAN 1'-0 RECOMMENDED 1’-6 OPERATING WATER LEVEL FLAt BAsiN sEctioN Tower Model 1211 1221 1231 1241 1251 1261 NotE 1 Use this bulletin for preliminary layouts only. Do not use for construction. Obtain current drawings from your Marley sales representative.
  • Page 12: Engineering Data

    Marley Sigma 1000/1200 Cooling towers are usually selected to produce a specific cold water temperature at the higher summer-time wet-bulb temperatures. During the remainder of the year, the cooling tower is capable of producing much colder water. Unless your system will benefit from the coldest possible water tempera- ture, you should consider controlling cold water temperatures to higher levels.
  • Page 13: Environmental

    Marley Sigma 1000/1200 Enclosures Occasionally, cooling towers are located inside architectural enclosures for aesthetic reasons. Although Sigma towers adapt well to enclosures, a poorly designed enclosure can impair proper operation. An effective design includes gener- ous air inlet paths, with the tower’s fan cylinder discharge at or above the top of the enclosure.
  • Page 14: Specifications: Base

    Marley Sigma 1000/1200 Specifications Base: Furnish and install an induced-draft, crossflow-type, field-erected, wood- framed, PVC fill, industrial-duty cooling tower of _____ cell(s), as shown on Plans. The limiting overall dimensions of the tower shall be _____ wide, ___ __ long, and _____ high to the top of the fan cylinder.
  • Page 15: Thermal Performance

    Marley Sigma 1000/1200 Specifications Thermal Performance: The tower shall be capable of cooling _____ GPM of water from ____ °F to _____ °F at a design entering air wet- bulb temperature of _____ °F . The cool- ing tower manufacturer shall guarantee...
  • Page 16: Construction

    Marley Sigma 1000/1200 Specifications Construction: The tower shall be capable of with- standing water having a pH of 6.5 to 8.0; a chloride content (NaCl) up to 750 ppm; a sulfate content (SO 4 ) up to 1200 ppm; a sodium bicarbonate con- tent (NaHCO 3 ) up to 200 ppm;...
  • Page 17: Fan Deck And Fan Cylinder

    Marley Sigma 1000/1200 Specifications Fan Deck and Fan Cylinder: The fan deck shall act as a working platform for maintenance personnel. It shall be fabricated of no less than 1" thick, 7 ply, exterior grade, treated Douglas Fir plywood, and shall be...
  • Page 18: Mechanical Equipment

    The value of a 5 year mechanical equipment warranty speaks for itself. Except for the motor, all of the mechanical equipment on a Marley tower is made by SPX Cooling Technologies. Cooling tower vendors who purchase commercial fans, gear boxes, driveshafts, etc.
  • Page 19: Fill, Louvers And Drift Eliminators

    Marley Sigma 1000/1200 Specifications Fill, Louvers and Drift Eliminators: Fill shall be film-type, 15 mil thick, thermoformed PVC, with louvers formed as part of each fill sheet. Fill shall be suspended from stainless steel structural tubing supported from the upper tower structure, and shall be elevated above the floor of the cold water basin to facilitate cleaning.
  • Page 20: Hot Water Distribution System

    Marley Sigma 1000/1200 Specifications Hot Water Distribution System: The mechanical equipment support/ crossover pipe shall deliver water to two open hot water basins per cell at the fan deck elevation. Water shall exit these basins to the fill by gravity...
  • Page 21: Cold Water Collection Basin

    Marley Sigma 1000/1200 Specifications Each endwall of the tower shall be equipped with a 20" wide aluminum vertical ladder, through-bolted to the endwall structure. Ladder shall rise from the cold water basin level to the top of the fan deck guardrail, and shall be designed and installed in confor- mance with OSHA standards.
  • Page 22: Specifications: Options

    Marley Sigma 1000/1200 Specifications Control Options Control System: Add the following paragraph in the Mechanical Equipment section: Each cell of the cooling tower shall be equipped with a UL listed control system in a NEMA 3R or 4X outdoor enclosure capable of controlling...
  • Page 23: Basin Heater

    Marley Sigma 1000/1200 Specifications Basin Heater: 10.2 Add the following paragraph in the Cold Water Basin section: Provide a system of electric immersion heat- ers and controls for each cell of the tower to prevent freezing of water in the collection basin during periods of shutdown.
  • Page 24: Marley Premium Vfd System

    Marley Sigma 1000/1200 Cooling Tower Specifications: Options Specifications Specification Value to modulate fan speed maintaining set point temperature. The drive's panel dis- play shall be able to display the set-point temperature and cold-fluid temperature on two separate lines. The bypass shall...
  • Page 25: Vibration Limit Switch

    Marley Sigma 1000/1200 Specifications set point shall be displayed on the door of the control panel. The bypass shall include a complete magnetic bypass circuit with capability to isolate the VFD when in the bypass mode. Transfer to the bypass mode shall be automatic in...
  • Page 26: Convenience And Safety Options Stairway

    Marley Sigma 1000/1200 Specifications Convenience and Safety Options Stairway: Replace paragraph 9.3 with the fol- lowing: A 30" wide, column supported, 45° stairway with 8" rise and run of treated Douglas Fir shall be provided at the tower endwall rising from grade (roof) to the fan deck elevation.
  • Page 27: Oil Level Sight Glass

    Marley Sigma 1000/1200 Specifications Oil Level Sight Glass: Replace paragraph 5.4 with the fol- lowing: A galvanized oil gauge and drain line shall extend from the gear reducer to the vicinity of the motor, and shall be equipped with a bronze- bodied oil level sight glass.
  • Page 28: Low Noise Tower

    Marley Sigma 1000/1200 Specifications Low Noise Tower: Add the following at the end of this paragraph: The cooling tower shall be quiet operating, and shall produce an overall level of sound no higher than ____ dBA at the critical location indicated on the Plans.
  • Page 29: Watertight Partitions Between Cells

    Marley Sigma 1000/1200 Specifications Watertight Partitions Between Cells: Replace the last sentence in this paragraph with the following: Partitions shall be 3/4" x 5-ply, factory- fabricated, grooved and splined treated Douglas Fir plywood sheets, installed and sealed watertight to permit inde- pendent cell operation.
  • Page 32 7401 WEST 129 STREET OVERLAND PARK, KANSAS 66213 UNITED STATES 913 664 7400 spxcooling@spx.com spxcooling.com In the interest of technological progress, all products are subject to design and/or material change without notice. ©2008 SPX Cooling Technologies, Inc. Printed in USA | SIG-TS-08A...