Conduct Test - Retrotec DucTester DU200 Quick Manual

Advertisement

Step 2:
Connect to ducts cont'd
Connect Flex Duct to fan inlet for depressurization.
depressurize
Depressurization is easiest and permitted in all States
except CA & WA where it can still be used to
evaluate, but not for a final result.
To pressurize, connect the Flex Duct to fan exhaust.
All other connections remain the same
pressurize
Step 3:
Connect DM-2 gauge & fan
Connect power cord.
Switch to on: " l ". Green
light indicates that power
is connected.
Connect yellow and green
tubes to matching color
ports on fan. Ethernet
style Speed Control Cable
will disable the knob. It is
connected later in Step 4.
Speed Control Cable
Insert blue tube into the
supply register closest to
the air handler.
Total Duct Leakage Test: Depressurize
Ready to conduct the test by depressurizing the ducts:
Exhaust
airflow
Inlet
with Range Rings
inside Flex Duct
Depressurizing works best because the fan pulls the
Grill Mask tight on the registers during the test.
Inlet
Step 4:
airflow
Exhaust
* 50 Pa for Northwest ENERGY STAR.
Page 3 of 8
If Pressurizing, see tubing setup on page 7.

Conduct test

Press [On] twice to get to main
screen.
Adjust fan speed knob clockwise
until "PrA" reaches test pressure.
If not possible, go to Step
5 for advice on changing setup.
Connect Speed Control Cable to
fan.
Solid green Status light
indicates DM-2 is ready
to control speed.
For a test pressure of 25 Pa *, press
[Set Pressure] [25] [Enter].
Press [@ Pressure] to display what
the result would be at exactly 25 Pa.
Read results directly from the gauge.