Temperature
Controller
TC-911, TC-711
Features
Factory Set Input
Economical Model
User Friendly & Easy to Program
4 Digit 0.8inch Bright LED Display with
RED and WHITE color option in TC-911
TECHNICAL SPECIFICATION
INPUT SPECIFICATION:
Input
Range
J / K
J : 0 to 850°C, K : 0 to 1200°C
Input Types
PT-100
PT-100: -50.0 to 400.0°C
2W/3W
Resolution
1°C
±1% of FSD ± 1°C
Indication
Accuracy
(FSD:- Full Scale Deflection)
DISPLAY AND KEYS:
4 Digit, 7 Segment LED,
Display
0.8 inch in TC-911, 0.56 inch in TC-711
Keys
SET, UP, DOWN
DIMENSION:
TC-911
Size (mm)
96 (H) x 96 (W) x 40 (D) mm
Panel Cutout
92 (H) x 92 (W) mm
TC-711
Size (mm)
72 (H) x 72 (W) x 50 (D) mm
Panel Cutout
68 (H) x 68 (W) mm
CONTROL ACTION
Control Mode
ON-OFF Control
OUTPUT SPECIFICATION:
Relay
1 Nos
Relay Type
1C/O (NO-C-NC)
Rating
10A (Resistive Load)
POWER SUPPLY:
Supply Voltage
230V AC, 50-60Hz
Power Consumption
4VA @ 230V AC MAX
(VA Rating
ENVIRONMENT CONDITION:
Operating Temp.
0°C to 55°C
UP to 95% RH
Relative Humidity
(non-condensing)
Protection Level
IP-65 (Front side)
(As per request)
As per IS/IEC 60529 : 2001
KEY OPERATION
Key
Funtion
SET Key
(Long Press to Enter Set Point Menu)
UP Key
(To increase the value/navigate in menu)
Down Key
(To decrease the value/navigate in menu)
SET+UP KEY
+
(Long press to enter parameter menu)
MECHANICAL DIMENSIONS
Dimensions for TC-911
92
96
92
96
-2
-2
Tolerance: 92
x
92
40
+0
+0
Front View
Panel Cutout
Side View
INSTALLATION
Dimensions for TC-711
68
72
68
72
-2
-2
Tolerance: 68
x
68
50
+0
+0
Front View
Panel Cutout
Side View
For installing the meter
1. Prepare the panel cutout with proper dimensions
as shown above.
2. Push the meter into the panel cutout.
Secure the meter in it's place by fitting the clamp
on the rear side. Fit the clamps on both the sides
in diagonally opposite location for optimum fitting.
3. For proper sealing, tighten the screws evenly with
required torque.
Terminal screw tightening torque:
0.68 Nm to 0.79 Nm (6.018ln-Lb to 6.992 ln-Lb)
Screw clamp tightening torque: 0.1N-m
(0.885 Lb-inch)
SAFETY PRECAUTIONS :
All safety related conditions, symbols and
instruction that appear in this operating manual
or on the equipment must be strictly followed to
ensure the safety of the operating personnel as
well as the instrument.
If the equipment is not used in a manner
specified by the manufacturer it might impair the
protection provided by the equipment.
Do not use the equipment if there is any
mechanical damage
Ensure that the equipment is supplied with
correct voltage
If there is physical damage to the unit then do not
use it.
Read complete instruction prior to installation
and operation of the unit.
Wiring Guidelines:
CAUTION :
1) To prevent the risk of electric shock power supply to
the equipment must be kept OFF while doing the
wiring arrangement.
2) Wiring shall be done strictly accordingly to the
terminal layout with the shortest connection.
Confirm that all connection are correct.
INSTRUMENT CONFIGURATION
ERROR CONDITIONS
If the display shows below message
S
e
c
Sensor Not Connected
It means Input
or any error with connected sensor.
In such case please check the sensor connections
If the display shows below message
S
e
E
This means Input
Sensor Reverse
;
In such case please check the sensor connections
SET POINT MENU
Long press
key
S E T
Set Point Menu
press SET key
Set Value
Using up & down key
2 2 5
to change SET point
Press the SET key
it will store the latest
SET Value
** Important Note:
Range for J Type Input : 0 to 850°C
Range for K Type Input : 0 to 1200°C
Range for PT 100 Input : -50.0 to 400.0°C
*Note: If the instruments stays in idle condition
while inside the Configuration Menu for more
than 30 seconds, then it will automatically exit
the configuration menu.
*Installation Note:
It is been advised that the settings should be
done by a professional, after going through
user operating manual and after having
understood the application.

Advertisement

loading

Summary of Contents for Sense TC-911

  • Page 1 MECHANICAL DIMENSIONS 4 Digit, 7 Segment LED, and operation of the unit. Display Range for PT 100 Input : -50.0 to 400.0°C 0.8 inch in TC-911, 0.56 inch in TC-711 Dimensions for TC-911 Keys SET, UP, DOWN Wiring Guidelines: *Note: If the instruments stays in idle condition...
  • Page 2 SET key PT 100 Input Range : -20 to 20 2W / 3W Sense Electric India Control Action : ON/OFF press SET key 4, Gajanand Industrial Estate, Nr. Hathijan Circle, Output: 1Relay / 1 C/O to SAVE and EXIT...

This manual is also suitable for:

Tc-711