Summary of Contents for Intellisystem IT-SDS-302-T-2D Series
Page 1
【Summarize】 IT-SDS-302-T-2D series is an high performance, industrial grade serial to Ethernet server, it can satisfy some kinds of customer requirements in consumption, temperature, volume and handle ability. It provides 2 port RS232 (RS-232 connector: RJ45) or RS485 (RS485 connector: terminal block) and 1 port 10/100Base-Tx Ethernet, can focus manage disperse serial device, master through network, easy, convenience.
【Packing list】 The first time use this product, please check the packaging is intact or not and the attachment is complete or not at first. 1. IT-SDS-302-T-2D series x1 2. Instruction x1 3. Warranty card x1 Please handle with care for there are precision components in the device, and it’s better to protect the device from excessive vibration to avoid affecting its performance.
1. Power input 5VDC±5% 10. Serial(COM1, COM2) 2. DIP switch 3. 10Base-T /100Base-TX Ethernet port 4. Company name, product series 5. Wall mounting installation nut 6. Ethernet port LED indicator 7. Power LED indicator 8. Serial transmit data indicator 9. Serial receive data indicator 【Dimensions(mm)】...
【Power input】 IT-SDS-302-T-2D series provide DC power input, voltage input is, DC power adapter specification is internal size 2.5mm, external size 5.5mm. 【DIP switch】 Top panel provide 4 bit DIP switch to set function(ON is effective), 1, 3, 4 is hold, 2 is factory default, if you change the DIP switch statue, please power off and power on.
Page 6
(RX+) (TX+) (RX-) (TX-) (TX+) (RX+) (TX-) (RX-) Serial port connection IT-SDS-302-T-2D series adopts RJ45 connector. The PIN define is as follows: RS-232 port: PIN define Description Transmit data Received Data Request to send Clear to send Data set ready...
RS-485/422 port: Serial port PIN define COM2 T-/D- T+/D+ COM1 T-/D- T+/D+ 【LED Indicator】 The LED indicator on the front panel of IT-SDS-302-T-2D can indicate the running system and the operation status, which makes it easy to find and solve problems, the specific meaning of indicator are shown in the table. System statue LED Indicate Description...
【Installation】 Before installation, confirm that the work environment meet the installation require, including the power needs and abundant space. Whether it is close to the connection equipment and other equipments are prepared or not. 1. Avoid in the sunshine, keep away from the heat fountainhead or the area where in intense EMI. 2.
Page 9
Parity bit: None, Even, Odd, Space, Mark Data bit; 5bit,6bit,7bit,8bit Stop bit: 1bit,1.5bit,2bit Band rate: 300bps~115200bps RS-232 Transfer distance: no more than 15m RS-232 connector: RJ45 RS-485 transfer distance: 1200m RS-485 connector: 5 bits terminal block Protection: class 3 static, RS-485/422 side, 1.5KV isolation LED Indicator Power (PWR) Ethernet port connect statue (Link)
Page 10
EN 61000-4-5 (Surge) Level 3, EN 61000-4-6 (CS) Level 3, EN 61000-4-8, EN 61000-4-11 Shock: IEC 60068-2-27 Free fall: IEC 60068-2-32 Vibration: IEC 60068-2-6 Warranty Warranty time: 5years Certificates CE, FCC, RoHS, UL508 (pending)
Need help?
Do you have a question about the IT-SDS-302-T-2D Series and is the answer not in the manual?
Questions and answers