Transducer Troubleshooting Guide

Installation Guidelines

1. Do not route the transducer wire in the same conduit or parallel to the motor leads
2. Cut the transducer wire to length. We do not recommend splicing transducer wire. If a wire must be
spliced the additional wire should be shielded and the splice should be a soldered connection. DO NOT
USE WIRE NUTS
3. Do not roll or coil the transducer wire
4. Transducer wire must cross the motor leads at 90 degrees if they must cross
5. Use a 3" non-metallic "T" fitting to prevent noise from coupling to the transducer wire
1

Identifying Transducer Noise

1. Check the 4-20 mA input under Read Measured Values for unstable reading. Press Enter navigate to
Read Measured Values press enter and navigate to "4-20 ma I1 Input"
2. Does pressure change immediately when the VFD starts?
3. Is the drive acting erratically or displaying "Restart 3-2-1" without a fault being displayed? This indicates
the transducer is seeing an overpressure event. (Note: Check "Overpressure PSI" under Constant
Pressure Parameters if it is set too low it can also cause this problem)
222 Disk Drive
Rapid City, SD 57701
Intuitively Engineered
2
www.phasetechnologies.com
3
4
5
605-343-7934 - Main
866-290-7934 – Toll Free
605-343-7943 - Fax

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SD Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Phase Technology SD Series

  • Page 1 www.phasetechnologies.com Intuitively Engineered Transducer Troubleshooting Guide Installation Guidelines 1. Do not route the transducer wire in the same conduit or parallel to the motor leads 2. Cut the transducer wire to length. We do not recommend splicing transducer wire. If a wire must be spliced the additional wire should be shielded and the splice should be a soldered connection.
  • Page 2 www.phasetechnologies.com Intuitively Engineered 4. Is the drive not going to sleep after it appears to be maintaining pressure below “Shutoff Frequency” (Note: this could be a systemic issue if the drive cannot maintain pressure below Shutoff Frequency and Shutoff Frequency may need to be increased) Troubleshooting Transducer Noise 1.
  • Page 3 www.phasetechnologies.com Intuitively Engineered 222 Disk Drive 605-343-7934 - Main Rapid City, SD 57701 866-290-7934 – Toll Free 605-343-7943 - Fax...
  • Page 4 www.phasetechnologies.com Intuitively Engineered 222 Disk Drive 605-343-7934 - Main Rapid City, SD 57701 866-290-7934 – Toll Free 605-343-7943 - Fax...
  • Page 5 www.phasetechnologies.com Intuitively Engineered 7. Add snubber capacitor from I1+ to COM. If this does not work add a second snubber cap between I1+ and I1-. 8. Check to see if an Ashcroft low noise transducer is being used. If not replace with new S00150 low noise transducer.

This manual is also suitable for:

2xd seriesDx seriesSd202Sd205Sd207Sd210 ... Show all

Table of Contents