  • Page 2 UVR-HE Series THANK YOU FOR PURCHASING OUR APPLIANCE. BEFORE USING IT, READ THE USER MANUAL CAREFULLY AND STORE IT PROPERLY FOR FUTURE REFERENCE The products illustrated in this manual may differ from the actual product, depending on the various models. The equipment must not be used by persons (including children) with reduced mental, sensory or physical abilities, ie persons without experience or knowledge, unless they have been trained to use the equipment by a person responsible for their safety.
  • Page 3 UVR-HE Series 2. OPERATING DIAGRAM The machine consists of a heat exchanger and 2 fans that circulate two air flows: one from outside to inside the room (fresh air), one from inside to outside the room (exhaust air). These heat recovery units are suitable for the recovery of heat in public areas such as bars, meeting rooms, small and medium sized premises.
  • Page 4: Construction Features

    UVR-HE Series 4. CONSTRUCTION FEATURES • External galvanised steel sheet casing; • Condensate collection basin with condensate discharge; • Insulation with sound-absorbing mattress placed on the lower panel; • Air inlet and outlet circular connections; • Class F7 supply side flat or pleated filters;...
  • Page 5 UVR-HE Series 5. DIMENSIONS [MM] AND WEIGHT [KG] CODE MODEL ØE AP20071 UVR 500 MF HE 55.0 AP20073 UVR 700 MF HE 1000 1000 1060 64.0 AP20075 UVR 1200 MF HE 1000 1000 1060 80.0 AP20077 UVR 1600 MF HE...
  • Page 6: Optional Accessories

    6. OPTIONAL ACCESSORIES The UVR-HE series recovery units can be fitted with optional PRE or POST heating devices, such as water or electric heating coils. These accessories are equipped with male/female nipples for connection to the spiral duct and can be installed on the pressing and/or suction...
  • Page 7: Installation And Commissioning

    UVR-HE Series 7. INSTALLATION AND COMMISSIONING WARNINGS AND PRELIMINARY OPERATIONS • Check the perfect integrity of the various components of the unit. • Make sure to have the accessories for installation and the documentation. • Transport the packed section as close as possible to the installation area.
  • Page 8 UVR-HE Series HYDRAULIC CONNECTIONS The pipe installation and connection operations can compromise the good operation of the system or worse, cause irreversible damage to the machine. Therefore, these operations must only be carried out by specialised personnel. CONDENSATE DISCHARGE CONNECTION •...
  • Page 9 UVR-HE Series RCE-EC CONTROL UNIT • Suitable for wall installation in boxes with 3 type 503 modules. • Allows to switch the appliance on and off and to set 2 different operating modes: Manual operation Automatic operation For fan unit configuration and operation, refer to the instruction manual of the RCE-EC control unit included in the package.
  • Page 10 UVR-HE Series PLATE HEAT EXCHANGER MAINTENANCE Provided that the filter cleaning/replacement intervals specified above are respected, we recommend cleaning the heat exchanger once a year. Cleaning simply consists in the use of compressed air to remove anything that blocks the air passage channels of the exchanger.
  • Page 11: Operating Anomalies

    UVR-HE Series 10. OPERATING ANOMALIES SYMPTOMS CAUSES SOLUTIONS Difficult Reduced power supply voltage. Check the motor plate data. start-up Insufficient motor starting torque. Close the shutters until full speed is reached. If necessary, replace the motor. Insufficient Clogged pipes and/or obstructed intake points.