  • Page 2 AVTRON MODEL LPV600 RESISTIVE LOAD BANK Part Number LPV600 994210 © 2013 Avtron Loadbank, Inc. November 19, 2013 Cleveland, Ohio...
  • Page 6: Table Of Contents

    Page SAFETY CONSIDERATIONS ................1-1 DESCRIPTION ....................2-1 INSTALLATION ....................3-1 OPERATION ....................... 4-1 MAINTENANCE ....................5-1 REPLACEMENT PARTS LIST ................6-1 APPENDIX - Avtron Load Bank Troubleshooting Guide DRAWINGS SB3396 Outline Drawing 995228 Schematic/Interconnection, Load Bank 995221 Resistor Assy...
  • Page 8: Safety Considerations

    Damage to the equipment and potentially hazardous conditions for personnel may occur if a CAUTION statement is ignored. Each Avtron unit is safety checked for opens and shorts, and the insulation is high potential tested to ensure safe operation. All fuses, safety interlocks and related safety equipment have been tested as part of the testing procedure of each unit.
  • Page 9 Avtron Resistive Load Bank - Part Number LPV600 994210 Safety Considerations Replace any burned out bulbs on the Control Panel. Each lamp is an indication that a system is active or has failed and is important to the operation of the Load Bank and safety of the operator.
  • Page 10 Avtron Resistive Load Bank - Part Number LPV600 994210 Safety Considerations The CONTROL POWER ON/OFF switch will disconnect both load steps and fan motor. A customer-supplied Generator Emergency OFF switch should be located near the Load Bank. An approved electrical fire extinguisher should be on hand at all times.
  • Page 12: Description

    SECTION II DESCRIPTION The Model LPV600 Load Bank is a portable, primarily indoor, self-contained unit for electrically loading and testing generators. The Load Bank is rated at 600 kW at 600 VDC and 300 kW at 300 VDC. The available load steps are 240 kW, 120 kW, 120 kW, 60 kW, 20 kW, 20 kW, l0 kW, 5 kW, 2 kW, 2 kW, and 1 kW at 600 VDC.
  • Page 13 Avtron Resistive Load Bank - Part Number LPV600 994210 Description overload relay, fuses and customer connection load bus. The cooling air is drawn in from the bottom and lower sections of side access panels, forced across the resistor elements and exhausted out the top of the unit.
  • Page 14: Installation

    Avtron Resistive Load Bank - Part Number LPV600 994210 Installation SECTION III INSTALLATION BEFORE INSTALLATION Inspect the Load Bank for obvious damage such as broken wires, broken or dented panels, cracked ceramic insulators, or any other component breakage that may have occurred in shipment.
  • Page 15 Load Banks mounted into a channel, trough, hollow, well, or pit, or exhausting into a full wall or corner, require special considerations even if above conditions are met. In these cases, provide a detailed sketch of site layout for Avtron to inspect and comment.
  • Page 16 Avtron Resistive Load Bank - Part Number LPV600 994210 Installation POWER REQUIREMENTS The Load Bank requires a 120V, single phase, 60 Hz, 20 amp source of power for operation of the control circuit. An integral 480/120V control power transformer is provided for powering the control circuit.
  • Page 17 Avtron Resistive Load Bank - Part Number LPV600 994210 Installation GROUNDING A permanent ground should be connected to the Load Bank enclosure either by a grounded conduit or with a separate ground wire to prevent a potential above ground on the enclosure. No internal ground connections are made to any terminal on the Load Bank.
  • Page 18: Operation

    Avtron Resistive Load Bank - Part Number LPV600 994210 Operation SECTION IV OPERATION PURPOSE AND USE OF CONTROLS CONTROL POWER ON/OFF Switch. This switch turns on control power to the control circuit. Digital meters will illuminate. BLOWER VOLTAGE SELECT Switch. This switch selects the appropriate voltage for the fan motor.
  • Page 19 Avtron Resistive Load Bank - Part Number LPV600 994210 Operation NOTE Operator must ensure that MT1 terminal (2) is wired to either the Negative 300 VDC or 600 VDC Bus Bar to get correct voltage reading. Operator must move wire to correct Negative Bus Bar if needed before operation.
  • Page 20 Avtron Resistive Load Bank - Part Number LPV600 994210 Operation switches. If at any time, there is insufficient cooling air to the elements, this safety switch will drop out the load and the red BLOWER FAIL lamp will light. *************************************************************...
  • Page 21 Avtron Resistive Load Bank - Part Number LPV600 994210 Operation ************************************************************* W A R N I N G DO NOT touch the exhaust screen during operation. The screen will become hot from the exhaust heat and may cause a serious burn.
  • Page 22 Electric tools used during repair should be grounded. For example, use only anti-static type solder suckers and grounded tip soldering irons. Discharge non-electric tools before use. · Pack ESD items in static shielding containers before shipping them to Avtron for repair. * Styrofoam® is a registered trademark of Dow Chemical.
  • Page 24: Maintenance

    Avtron Resistive Load Bank - Part Number LPV600 994210 Maintenance SECTION V MAINTENANCE Good maintenance procedures must be followed to provide long equipment life and to reduce the chance of electric shock, fires, and personal injury. Before servicing, review Section I, SAFETY CONSIDERATIONS, of this manual.
  • Page 25 Avtron Resistive Load Bank - Part Number LPV600 994210 Maintenance THREE MONTHS OR 500 HOURS Remove access panels and screens. Inspect the load resistors for mechanical breakdown which is demonstrated by excessive sagging of the elements. Replace with new resistor elements, support rods, and insulators as required.
  • Page 26 PARTS REPLACEMENT Access to any component is easily made with the removal of the cover panels. All components in the unit that may need replacement are listed in the Replacement Parts List. Avtron maintains an inventory of normally used items.
  • Page 28: Replacement Parts List

    REPLACEMENT PARTS LIST INTRODUCTION The parts list in this section contains the description, quantity required, and Avtron part numbers for each listed part. The list also includes, where appropriate, the manufacturer's name and part number, as well as schematic reference designators to facilitate parts identification.
  • Page 29 Avtron Resistive Load Bank - Part Number LPV600 994210 REPLACEMENT PARTS LIST SCHEMATIC AVTRON QTY/ DESCRIPTION REFERENCE UNIT AVTRON MODEL LPV LOAD BANK, PORTABLE LPV600- 994210 .SCHEMATIC 995228 RA2-RA4 .RESISTOR ASSEMBLY 995221 K1-3 ..RELAY, DC 995215 K1A,2A ..RELAY 350748 XK1A,2A ..SOCKET, RELAY...
  • Page 30 Avtron Resistive Load Bank - Part Number LPV600 994210 SCHEMATIC AVTRON QTY/ DESCRIPTION REFERENCE UNIT .CONTROL BLOWER ASSEMBLY 995226 XF4-12 ..FUSE BLOCK 324997 F4-6 ..FUSE, 20A 324283 F7-12 ..FUSE, 10A 324282 K21,K22 ..RELAY 350980 K30,K31,K32 ..RELAY 351060 K23-27,K29 ..RELAY 351650 XK1A,30,31,32 ..SOCKET, RELAY...
  • Page 38 User, or fifteen months from the date of shipment, whichever expires first. The product shipment date will be determined only from the Avtron bill of lading. If any part or portion of the Avtron product fails to conform to the Warranty within the Warranty period, Avtron, at its option, will furnish new or factory remanufactured products for repair or replacement of that portion or part.
  • Page 39 User will be issued a credit in an amount equal to the parts prices previously invoiced. Warranty coverage will be provided only after Avtron's inspection discloses the claimed defect and shows no signs of treatment or use which would void the coverage of this Warranty.