CommandCenter Operator Panel
Introduction
This document describes the different features of the Operator Panel (local or remote)
that is used with the Seresco units.
Startup Screens
When the unit start up you will see the following menu screen. A 60 second timer is
started and if no selection is made before timer expires, Normal Mode will automatically
be selected.
1.
Normal Mode
2.
Service Mode
Selecting Normal Mode will take you to the main sensor screen. If the voltage monitor
fault signal is not active, blower will start right away. If voltage monitor fault signal is
active, 60 second timer will continue running. When timer expires, the voltage monitor
fault signal will be checked again. If signal now is cleared, the blower will start,
otherwise blower will remain off and there will be a voltage monitor fault alarm.
Navigation Mode and Edit Mode
The menu system implements two different modes where the keys have different
meanings. Navigation mode is used to navigate the menu system and Edit mode is used
when changing data.
The following keys are used in Navigation mode:
 Keys 1-3 (and 4-6) are used to select a menu item. If there are more than 6 menu
items, menu items will be listed 1-3 on every screen.
 Up and Down arrows are used to scroll up or down a page. Arrows at the top right
corner indicates which direction you can scroll. If no more than 6 items either down
or up arrow will be displayed (no scrolling "around corner"). If more than 6 menu
items, both arrows will be displayed and you can scroll "around the corner".
Obviously no arrows when 3 or less menu items.
 Back key takes you back to previous menu level.
OperatorPanel_OA_5.3.5
Page 1
3/31/2013

Advertisement

loading
Need help?

Need help?

Do you have a question about the CommandCenter and is the answer not in the manual?

Questions and answers

Summary of Contents for Seresco CommandCenter

  • Page 1 Introduction This document describes the different features of the Operator Panel (local or remote) that is used with the Seresco units. Startup Screens When the unit start up you will see the following menu screen. A 60 second timer is started and if no selection is made before timer expires, Normal Mode will automatically be selected.
  • Page 2: Data Types

     Enter key has a special meaning. From any menu screen it will take you directly back to the main screen (the sensor screen). If you now press the Back key it will take you back to the screen where you were before pressing Enter. On the sensor screen you can still use the Up and Down arrows to scroll up and down a page and the Back key will still take you back to where you were before pressing Enter.
  • Page 3: Information Messages

    A time value is entered in the same way as a date. An IP address is entered the same way as date and time except that you edit one digit at a time. Passwords are entered one digit at a time pressing Enter after each digit. Information Messages Certain actions and certain conditions will generate information messages.
  • Page 4 Menu Structure Quick Reference The root menu screen is where you see all the sensors and one menu option that takes you to the Main Menu. Some menu selections are dependent on current unit configuration and will not always be displayed. These menu selections are marked as Optional. For data menu items, the default value is displayed in the summary.
  • Page 5 Factory Settings 2.1. Ventilation 2.1.1. Options 2.1.1.1. Fire Reset 2.1.2. Blower 2.1.2.1. Normal Speed 2.1.2.2. Max Speed 2.1.3. Timers 2.1.3.1. Stabilize 2.1.3.2. Freezestat 1 2.1.3.3. Freezestat 2 2.1.3.4. No Airflow 2.1.3.5. Dirty Filter 2.2. Compressor 2.2.1. Configuration 2.2.1.1. Compressor 1 2.2.1.1.1.
  • Page 6 2.2.4. Pressures 2.2.4.1. LP Vacuum 2.2.4.2. LP Alarm 2.2.4.3. LP Start 2.2.4.4. LP Max 2.2.4.5. HP Min 2.2.4.6. HP OACC Min 2.2.4.7. HP OACC Max 2.2.4.8. OACC Deadband 2.3. Space Control 2.3.1. Room Temperature 2.3.1.1. Deg*Min On 2.3.1.2. Deg*Min Off 2.3.1.3.
  • Page 7 2.4. Network 2.4.1. TCP/IP 2.4.1.1. DHCP 2.4.1.2. 2.4.1.3. Mask 2.4.1.4. 2.4.1.5. 2.4.1.6. Time 2.4.1.7. Link Monitor 2.4.2. Serial Ports 2.4.2.1. Port B (RS-232) 2.4.2.1.1. User 2.4.2.1.2. Baud Rate 2.4.2.1.3. Databits 2.4.2.1.4. Parity 2.4.2.1.5. Flow Control 2.4.2.1.6. Reply Delay 2.4.2.2. Port C (RS-485) 2.4.2.2.1.
  • Page 8 2.4.4. BACnet [Optional] 2.4.4.1. Enabled 2.4.4.2. Interface 2.4.4.3. Device ID 2.4.4.4. Port 2.4.4.5. Heartbeat 2.4.5. Modbus [Optional] 2.4.5.1. Device ID 2.4.6. [Optional] 2.4.6.1. Enabled 2.4.6.2. Interface 2.4.6.3. Refresh Rate 2.5. Inputs/Outputs 2.5.1. Sensor Type 2.5.1.1. 2.5.1.2. 2.5.1.3. Superheat 2.5.1.4. HP 2 2.5.1.5.
  • Page 9 2.5.3. Sensor Calibration 2.5.3.1. 2.5.3.2. 2.5.3.3. Superheat 2.5.3.4. Suct Temp 2.5.3.5. Discharge 2.5.3.6. HP 2 2.5.3.7. LP 2 2.5.3.8. Superheat 2 2.5.3.9. Suct Temp 2 2.5.3.10. Discharge 2 2.5.3.11. Outdoor Air 2.5.3.12. OA Humidity 2.5.3.13. OA Dew Point 2.5.3.14. Supply Air 2.5.3.15.
  • Page 10 2.5.7. Assignments 2.5.7.1. Analog Inputs 2.5.7.1.1. Supply Air 2.5.7.1.2. Outdoor Air 2.5.7.1.3. OA Humidity 2.5.7.1.4. OA Dew Point 2.5.7.1.5. Evap Temp 2.5.7.1.6. 2.5.7.1.7. 2.5.7.1.8. Suct Temp 2.5.7.1.9. Discharge 2.5.7.1.10. HP 2 2.5.7.1.11. LP 2 2.5.7.1.12. Suct Temp 2 2.5.7.1.13. Discharge 2 2.5.7.1.14.
  • Page 11 2.5.7.4. Digital Outputs 2.5.7.4.1. Blower 2.5.7.4.2. More Reheat 2.5.7.4.3. Less Reheat 2.5.7.4.4. Compressor 1 2.5.7.4.5. Compr 1 PD 2.5.7.4.6. Compressor 2 2.5.7.4.7. Compr 2 PD 2.5.7.4.8. Cooler 2.5.7.4.9. Cooler PD 2.5.7.4.10. OACC 2.5.7.4.11. OACC 2 2.5.7.4.12. Heat Stage 1 2.5.7.4.13. Heat Stage 2 2.5.7.4.14.
  • Page 12 Service [Optional] 5.1. Force Contacts 5.1.1. Reset All 5.1.2. Ventilation 5.1.2.1. Blower 5.1.2.2. Blower Speed 5.1.2.3. OA Damper 5.1.3. Space Heating 5.1.3.1. Heat Stage 1 5.1.3.2. Heat Stage 2 5.1.3.3. Modulated Heat 5.1.4. Compressor 1 5.1.4.1. Contactor 5.1.4.2. Pump Down 5.1.4.3.
  • Page 13 Menu Structure Description This is a more detailed description of each menu item. User Settings 1.1. Setpoints If user password has been enabled, you will need to enter the password before you can change any setpoint. The Supply Temp setpoint is a floating setpoint that is controlled by the Room Temperature controller.
  • Page 14 1.4. Display Use Backlight to enable/disable the keypad backlight. Use Temp Unit property to set temperature unit to be used in the system (Celsius or Fahrenheit). Reset Display controls how long the operator panel will stay idle at a menu screen before being returned to the main sensor screen. 1.5.
  • Page 15 Factory Settings To access these settings you need to enter a service password. 2.1. Ventilation 2.1.1. Options Fire Reset property controls how the system will recover after a Fire Alarm. When set to auto, system will automatically go back to normal once the alarm is cleared.
  • Page 16 2.2.2. Options Use Enabled property to enable or disable usage of compressors. Compressors are disabled by default when unit is shipped and still in Commission mode. Refrigerant sets the type of Refrigerant used in the system. This will affect some of the pressure levels used to control the compressors. Reheat Time is the time it takes the reheat valve to move from fully closed to fully opened.
  • Page 17 Min Stop Time control the minimum time the compressor has to be stopped before being started again after a normal stop. Alarm Stop control the minimum time the compressor has to be stopped before being started again after an alarm. The Anti Block timer is used when deciding if the compressor should be started even if the low pressure has not reached minimum level.
  • Page 18 HP OACC Max pressure setting controls at what High Pressure level Outdoor Air Condenser will run at maximum capacity. OACC Deadband is used to determine when to turn off an OACC stage. OACC Min or Max pressure level minus deadband is when OACC stage will be turned off.
  • Page 19 Serial Ports Port properties are the same for all ports except where noted. User defines the user of the port. Default is Seresco which means the port is opened for inbound traffic using the Seresco protocol. Other users are other protocols like LON and Modbus as well as 3&4 compressor slave board communication.
  • Page 20 WebSentry server. Normally the WebSentry server should disconnect before this time. 2.4.4. BACnet These properties controls BACnet connections and are only available if the CommandCenter has been loaded with BACnet support. OperatorPanel_OA_5.3.5 Page 20 3/31/2013...
  • Page 21 Set Enabled to Yes to enabled BACnet. It is disabled by default. Set Interface to BACnet interface type. Currently only Ehernet and IP is supported. Use Device ID to set a unique device ID for unit on the BACnet network. Port can be used to change the default port setting.
  • Page 22  GSRH, Greystone RH sensor.  SG145, Saginomiya transducer, max 145 psi.  SG435, Saginomiya transducer, max 435 psi.  JCRH, Johnson Controls RH sensor.  JC100, Johnson Controls transducer, max 100 psi.  JC500, Johnson Controls transducer, max 500 psi. ...
  • Page 23 2.5.6. Sample Rates The AI Samples and AI Sample Rate properties are used to fine tune the way analog inputs are read and translated into sensor readings. A sensor reading is the average of all read samples. Refresh Sensor property sets how often sensors will be read. Sensor reading will also be generated when there is a change in the sensor reading.
  • Page 24 3.3. System Status The status screen shows the status for different internal system components. It’s main purpose is for troubleshooting a running system where the information here can be passed back to tech support. The status feature has been grouped into 4 areas. Environment shows status for the environment control (Space Temp, Humidity, Supply Air Control, Air Heater and Heat Recovery).
  • Page 25 Service To reach these settings you need to enter a service password. 5.1. Force Contacts Force Contacts is used to test all the Analog and Digital Outputs. This overrides any internal control of corresponding features and is just a way to physically test that a contact is working.
  • Page 26 before delivery to customer. When test completed, the Tested option is changed to Yes and can never be changed back again. When unit has been tested, the compressor Enabled property will be changed to No. When Commissioned option still is set to No, unit will start up in service mode.