Installation Instructions
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-
mation can result in death, serious personal injury,
property damage, or damage to the equipment.
Keep this Manual for future reference.
WARNING
!
FAILURE TO COMPLY WITH PROPER INSTALLATION
AND MAINTENANCE INSTRUCTIONS COULD
CONTRIBUTE TO THE VALVE FAILURE, RESULTING IN
INJURY AND/OR DEATH.
TO ENSURE THE ACCURATE AND RELIABLE OPERATION
OF THIS PRODUCT, IT IS ESSENTIAL TO:
• Properly design the system to minimize pressure and
temperature variations.
• This valve is not factory preset and can be adjusted
to deliver scalding temperatures. Check outlet tem-
perature to ensure it does not exceed 105°F (41°C).
Make sure temperature limit stop is properly re-set to
maximum 105°F (41°C) following valve maintenance or
repair. Tampering with limit stop in any way may result
in scalding temperature causing serious bodily harm
and/or death.
WARNING
!
Need for Periodic Inspection and Yearly Maintenance:
Periodic inspection and yearly maintenance by a licensed
contractor is required. Corrosive water conditions
and/or unauthorized adjustments or repair could render
the valve ineffective for service intended. Regular checking
and cleaning of the valve's internal components and check
stops helps assure maximum life and proper product func-
tion. Frequency of cleaning and inspection depends upon
local water conditions.
WARNING
!
You are required to consult the local building and plumbing
codes prior to installation. If the information in this manual is
not consistent with local building or plumbing codes, the local
codes should be followed. Inquire with governing authorities for
additional local requirements.
WARNING
!
Flush all pipes thoroughly before installation. Installation and
field adjustment are the responsibility of the installer.
HydroGuard
Thermostatic Tempering Valves
®
Installation
n
1. Locate suitable place for the tempering valve. Valves should
be accessible for service and adjustment, and be as close to
the point of use as possible.
2. Bleed pressure from the system.
3. Route copper tubing or piping to fit valve dimensions.
4. For valves with PEX tailpieces see instructions on the
next page.
5. Remove tailpieces from the valve and make sure union nuts
are over the tubing/piping before connecting to the tailpiece.
6. Flush piping again, install valve using filter gasket on
hot and cold water inlets and fiber gasket on mixed
water outlet.
7. Turn on the cold and hot water. If any leaks are observed,
tighten connections as necessary to stop leak
before proceeding.
LFLM495
Cold
Hot
Mixed
POWERS SERIES LM495 OR
LFLM495 WITH INTEGRAL
CHECKS AND SCREENS
HOT WATER SUPPLY
IS-P-LM495-PEX
LFLM495
LM495-4
Advanced
Thermal Activation
Figure 1.
Typical
ASSE 1069
Application
COLD WATER
SUPPLY
Figure 2.
Single/Two
Handle Faucet
Application

Advertisement

loading

Summary of Contents for Watts Industries Powers HydroGuard LFLM495

  • Page 1 CLICK ANYWHERE on THIS PAGE to RETURN to TEMPERING VALVES at InspectApedia.com IS-P-LM495-PEX HydroGuard Thermostatic Tempering Valves ® LFLM495 Installation Instructions WARNING Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use infor- mation can result in death, serious personal injury, property damage, or damage to the equipment.
  • Page 2 Illustration of a Good CrimpRing Connection ™ Making a Good CrimpRing Connection ™ 1.  Cut the pipe to length, making sure that you have a good square cut. A rough, jagged, or uneven cut will result in a weakened joint. 2. ...
  • Page 3 To Adjust Temperature (Figure 3) Repair Kit Model Part # Description Figure 3. Turn LFLM495 495 100 Plunger/Motor Assembly Hotter Troubleshooting Fluctuating or erratic hot water temperature at fixture: Colder Unbalanced pressure. Install balancing or throttling valve at the hot and cold water supplies and adjust accordingly for demand. Hex Wrench Hot water backing up into cold water line: Unscrew, Lift Cap...
  • Page 4 WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. Warranty For more information: www.watts.com/prop65 The Seller warrants that the equipment manufactured by it and covered by this order or contract is free from defects in material and workmanship and, without charge, equipment found to be defective in material or workmanship will be repaired, or at Seller’s option replaced F .O.B.