RAPID RESPONSE Series LFII Residential Sprinklers
4.9 K-factor Flat-Plate Concealed Pendent
Wet Pipe and Dry Pipe Systems
General
Description
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinklers (TY2524) are decora-
tive, fast response, fusible solder sprin-
klers designed for use in residential oc-
cupancies such as homes, apartments,
dormitories, and hotels.
The Cover Plate/Retainer Assembly con-
ceals the sprinkler operating compo-
nents above the ceiling. The flat profile
of the Cover Plate provides the optimum
aesthetically appealing sprinkler design.
Additionally, the concealed design of the
Series LFII Residential Flat-Plate Con-
cealed Pendent Sprinklers provides 1/2
inch (12,7 mm) vertical adjustment. This
adjustment provides a measure of flex-
ibility when cutting fixed sprinkler drops.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers are in-
tended for use in the following systems:
• wet and dry pipe residential sprin-
kler systems for one- and two-fam-
ily dwellings and mobile homes per
NFPA 13D
• wet and dry pipe residential sprin-
kler systems for residential occu-
pancies up to and including four sto-
ries in height per NFPA 13R
• wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13
The Series LFII Residential Sprinklers
have been designed with heat sensitiv-
ity and water distribution characteristics
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap protects the
sprinkler during ceiling installation or
finish. After ceiling installation is com-
plete, the Protective Cap is removed
and the Cover Plate/Retainer Assem-
bly is installed. Removing the Protec-
tive Cap is required for proper sprinkler
performance.
Dry Pipe System Application
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinkler offers a
laboratory approved option for design-
ing dry pipe residential sprinkler sys-
tems, whereas, most residential sprin-
klers are laboratory approved for wet
systems only.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for the
Series LFII Residential Flat-Plate Con-
cealed Sprinklers (TY2524) need not be
increased over the number of design
sprinklers (hydraulic design area) speci-
fied for wet pipe sprinkler systems, as
is customary for density/area sprinkler
systems designed per NFPA 13, 13D,
or 13R.
Consequently, the Series LFII Residen-
tial Flat-Plate Concealed Sprinklers
(TY2524) offer the features of non-wa-
ter filled pipe in addition to not having to
increase the number of design sprinklers
(hydraulic design area) for systems de-
signed to NFPA 13, 13D, or 13R.
NOTICE
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers (TY2524)
described herein must be installed and
maintained in compliance with this doc-
ument and the applicable standards of
the National Fire Protection Association,
in addition to the standards of any au-
thorities having jurisdiction. Failure to
do so may impair the performance of
these devices.
FEBRUARY 2014
The owner is responsible for maintaining
their fire protection system and devic-
es in proper operating condition. Con-
tact the installing contractor or sprinkler
manufacturer with any questions.
Sprinkler
Identification
Number (SIN)
TY2524
TFP443

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RAPID RESPONSE LFII Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Fire Protection Products RAPID RESPONSE LFII Series

  • Page 1 RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General proven to help in the control of residen- tial fires and to improve the chance for Description occupants to escape or be evacuated. The Series LFII Residential Flat-Plate The TYCO RAPID RESPONSE Series Concealed Pendent Sprinklers are...
  • Page 2 TFP443 Page 2 of 6 WRENCH BODY SEALING RECESS (1/2" NPT) ASSEMBLY SPRINKLER WRENCHING AREA SADDLE PUSH WRENCH COMPRESSION IN TO ENSURE SUPPORT SCREW ENGAGEMENT CUP WITH WITH SPRINKLER ROLL FORMED WRENCHING AREA THREADS FIGURE 2 LEVER W-TYPE 18 SPRINKLER WRENCH GUIDE SOLDER LINK ELEMENT...
  • Page 3 TFP443 Page 3 of 6 Technical Design Criteria Dry Pipe System Water Delivery When using the Series LFII Residential Data Flat-Plate Concealed Pendent Sprinklers The TYCO RAPID RESPONSE Series (TY2524) in dry pipe sprinkler systems, LFII Residential Flat-Plate Concealed the time for water delivery must not ex- Pendent Sprinklers (TY2524) are UL Approvals ceed 15 seconds for the most remote...
  • Page 4 TFP443 Page 4 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressure (b, c) Maximum Maximum Coverage Ordinary Temp Rating Spacing Area 160°F (71°C) Minimum Deflector to Installation Ft. x Ft. Spacing Ceiling Type (m x m) Flow Pressure (L/min) (bar) 12 x 12...
  • Page 5 TFP443 Page 5 of 6 Installation Step 6. Screw on the Cover Plate/Re- Automatic sprinklers must never be tainer Assembly until its flange contacts painted, plated, coated, or otherwise the ceiling. Do not continue to screw altered after leaving the factory. Modi- The TYCO RAPID RESPONSE Series on the Cover Plate/Retainer Assembly fied or overheated sprinklers must be...
  • Page 6 TFP443 Page 6 of 6 Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product description and Part Number (P/N). Sprinkler/Support Cup Assembly Specify: Series LFII (TY2524), K = 4.9 (70,6), Residential Flat-Plate Concealed Pendent Sprinkler without Cover Plate/ Retainer Assembly, P/N 51-114-1-160...