EAST PENN Deka unigy I Battery 1 Assembly, Installation And Operation Instructions

Advertisement

Quick Links

STATIONARY BATTERY INSTALLATION
AND OPERATING INSTRUCTIONS
IN REFERENCE TO THIS MANUAL:
– "Battery" is defined as an individual 12-volt unit.
– "Battery string" is defined as a series connected
electrical system comprised of batteries
(individual 12-volt units).
SAFETY PRECAUTIONS
Although all valve regulated batteries have the
electrolyte immobilized within the battery, the
electrical hazard associated with batteries still exists.
Work performed on these batteries should be
done with the tools and the protective equipment
listed below. VRLA battery installations should be
supervised by personnel familiar with batteries and
battery safety precautions.
WARNING: Risk of fire, explosion or burns. Do not
disassemble, heat above 65°C, or incinerate .
®
Protective Equipment
Although VRLA batteries can vent or leak small
amounts of electrolyte, electrical safety is the principle
but not the only concern for safe handling. Per IEEE
1188 recommendations, the following minimum set
of equipment for safe handling of the battery and
protection of personnel shall be available:
1. Safety glasses with side shields, or goggles, or face
shields as appropriate. (Consult application specific
requirements)
2. Electrically insulated gloves, appropriate for
the installation.
3. Protective aprons and safety shoes.
4. Portable or stationary water facilities in the battery
vicinity for rinsing eyes and skin in case of contact
with acid electrolyte.
5. Class C fire extinguisher.
6. Acid neutralizing agent.
1

Advertisement

Table of Contents
loading

Summary of Contents for EAST PENN Deka unigy I Battery 1

  • Page 1 ® STATIONARY BATTERY INSTALLATION AND OPERATING INSTRUCTIONS IN REFERENCE TO THIS MANUAL: Protective Equipment Although VRLA batteries can vent or leak small – “Battery” is defined as an individual 12-volt unit. amounts of electrolyte, electrical safety is the principle – “Battery string” is defined as a series connected but not the only concern for safe handling.
  • Page 2: Receiving And Storage

    Report any missing parts or shipping a physician if splashed in the eyes. Consult SDS for damage to your East Penn agent or East Penn Mfg. additional precautions and first aid measures. Co. immediately.
  • Page 3: Installation

    Mishandling of batteries could result in equipment damage or human injury. East Penn will not be liable for damage or injury as a result of mishandling or misuse of the product.
  • Page 4: Battery Assembly

    Ventilation FLOAT / STANDBY (per battery) equipment is not designed or supplied by East Penn 13.50V +/- 0.06 @ 77°F (25°C) Mfg. Safe installation of any venting equipment is the responsibility of the installer.
  • Page 5: Record Keeping

    100 in lb +/- 5. Micro-ohm readings should be If operating temperatures are expected to be taken across every connection. Refer to meter in excess of 95°F (35°C), contact East Penn for manufacturer’s instructions for proper placement of recommendations.
  • Page 6: Maintenance

    Keep sparks and open flames away from only be cleaned with: clear water, a mixture of batteries at all times. Review “Safety Precautions” baking soda and water or East Penn Mfg battery (Pg. 1). cleaner (part # 00321). Annual Inspection...
  • Page 7 ALL FIELDS TO THE RIGHT OF THE CELL NUMBER ABOVE MUST BE COMPLETED EPM ORDER NUMBER WILL APPEAR ON THE SHIPPING LABEL ON THE CARTON COVERING EACH PALLET OF CELLS TO ENSURE CONTINUATION OF WARRANTY, SUBMIT FORMS TO: East Penn Mfg. Co, Inc., Reserve Power Division, Product Support & Warranty Dept. (reservepowerwarranty@dekabatteries.com)
  • Page 8 ® APPENDIX B VOLTAGE COMPENSATION CHART °C Float Equalize °F >35 13.38 14.28 >95 13.39 14.29 93.2 13.40 14.30 91.4 13.42 14.32 89.6 13.43 14.33 87.8 13.44 14.34 86.0 13.45 14.35 84.2 13.46 14.36 82.4 13.48 14.38 80.6 13.49 14.39 78.8 13.50 14.40...
  • Page 9 ® APPENDIX C UNIGY I CHARGE CURRENT LIMITS Max. Charge Max. Charge Battery Type Current (A) Current (A)** 12AVR30 12AVR40 12AVR75 13.4 12AVR90 15.5 12AVR100 17.9 12AVR130 23.6 12AVR100ET 17.6 12AVR145ET 26.3 12AVR150ET 27.1 12AVR170ET 30.8 12AVR200ET 38.3 11.5 ** = Using minimum charge current will extend recharge time and increase risk of battery being undercharged...
  • Page 10 ® APPENDIX D BATTERY MAINTENANCE REPORT Inspection Date _____________________________________________________________________ No. of Units/String __________________ Company ___________________________________________________________________________ Type _______________________________ Address ____________________________________________________________________________ Date New __________________________ Battery location and/or number ______________________________________________________ Date Installed _______________________ Individual Charger Output _____________________ Amp Air Temperature ______________________°F Battery Readings Total Battery String Voltage ________________ Panel Meter Volts ______________________ Unit...
  • Page 11 ®...
  • Page 12 East Penn Manufacturing Co. Lyon Station, PA 19536-0147 Phone: 610-682-3263 Fax: 610-682-4781 All data subject to change without notice. No part of this document may be copied or E.P.M. Form No. 0902 02/22 © 2022 by EPM Printed in U.S.A.

Table of Contents