Rooster™ Sensor200 USER MANUAL Product Overview Congratulations on your purchase of the Rooster Sensor200, the first the BACnet® MS/TP capable air velocity and temperature sensor with color touch panel display for facility managers to achieve local and remote communications simultaneously. The Rooster™...
Rooster™ Sensor200 USER MANUAL Hard Button Overview MUTE Mutes the audible alarm, any time it is sounding. When the alarm has been muted, a mute icon [ ] will appear in the top center portion of the home screen. Just like a snooze button, the audible alarm will re-sound, when the configurable time-out is reached, and if ringback has been enabled.
Page 5
Rooster™ Sensor200 USER MANUAL CLOCK Users logged in as EH&S or Certifier can set time, date, and change clock to display in 12 or 24-hour format. Home>Settings>System>Date & Time>Date & Time Settings KEYPAD AND BUTTON SOUNDS Users may toggle keypad and button beep sounds on and off. Home>Settings>System>Alarms/Sound>Key Beep DEVICE VOLUME Users can toggle through low, medium, or high alarm volumes.
Page 6
Rooster™ Sensor200 USER MANUAL USB INTERFACE FOR UPGRADES AND DATA IMPORT/EXPORT Firmware upgrades can be installed on-site via USB flash drive. See the USB Field Upgrade section for more information. Users may also import/export Rooster™ settings and export the event log through the USB interface. CUSTOMIZABLE BOOT SCREEN Our engineers can configure your unit with a custom image or logo file (240x320) in portable network graphic (.png) format to display on boot up.
Rooster™ Sensor200 USER MANUAL AIRFLOW RESOLUTION EH&S or Certifier users can select the resolution of air velocity units. Home>Settings>System>Airflow Settings>Airflow Resolution Rear Panel Layout for Advanced Connections Figure 1 Connections Connection Connector Type Mating Connector Description 2-Pin, polarized, Phoenix Power Entry Included and attached to AC/DC power supply Contact Sensor Connection...
Rooster™ Sensor200 USER MANUAL Optional Sash Switch Kit, Degree Controls Part#: 62310AS004 includes 10-postion Phoenix Contact connector. This is for digital sash sensor mode. Optional Sash Position Sensor Kit, Degree Controls Part#: 62310AS008 includes 10-postion Phoenix Contact connector. This is for analog sash sensor mode.
Rooster™ Sensor200 USER MANUAL Connection and Wiring Information Degree Controls recommends 18-24 AWG wire for all wiring connections to the input and output connectors. The sensor and power entry connections have been prepared for you, and merely need to be pulled through the openings and connected to the display module. If the Sash Switch option (digital sash operation) is purchased, this is pre-connectorized for you as well.
See the sash height calibration section for additional calibration detail. See the I/O configuration section to configure a relay output for Sash Alarm. Note: For implementation support, or for users preferring to use a micro-switch for sash alarm activation, please contact Degree Controls. Night Setback Input The Rooster Sensor200 allows the user to connect to a digital input, dry contact, on positions 5 &...
Rooster™ Sensor200 USER MANUAL Muted: In this state, when the night setback signal is asserted, the Sensor200 will alarm (screen will display a red background, and the LED will flash) when airflow drops below the NSB trip threshold, but the alarm will be muted. Off (default): In this state, when the night setback signal is asserted, the Sensor200 will ignore it.
Page 12
Rooster™ Sensor200 USER MANUAL Once Control Output is enabled, the user needs to enter or select: 1. Setpoint, desired face velocity or volumetric flow (if volumetric flow is enabled) and 2. Output a. 0-20 mA b. 4-20 mA c. 0-5 V d.
Rooster™ Sensor200 USER MANUAL Mechanical Information Alarm Module Figure 2 Alarm Module with Wall-Mount Back Plate Installation Installation of the Rooster involves selecting and preparing appropriate locations for the alarm module and sensor, wiring, and connecting the unit, and then mounting both the alarm module and sensor securely.
Rooster™ Sensor200 USER MANUAL Figure 3 Wall Mount (left), Semi-Flush Mount (right) - for Alarm Module Installation Procedure 1. Determine mounting locations for the Rooster alarm module and sensor. 2. Choose alarm module mounting method: Wall Mount or Semi-Flush. 3. Mark the surface where the Rooster alarm module will be located, and make the necessary drills/cutout.
2. Drill a 17/32” (14mm) hole through the surface where you wish to install the sensor. 3. Drill two pilot holes for the °C Clamp fastening screws. (°C Clamp, Degree Controls P/N: 64500AS011) 4. Secure the °C Clamp with two screws (not provided).
Rooster™ Sensor200 USER MANUAL Step 2 Step 1 Step 5 Step 3 Step 4 Figure 7 °C Clamp Installation Figure 8 Airflow Direction Ensure that the sensor head is aligned correctly, by positioning the arrow in the direction of airflow. Boot Up Procedure The Rooster does not have a power-on switch and will become energized as...
Rooster™ Sensor200 USER MANUAL The Rooster can be rebooted at any time by pushing the hard “Home” and “Mute” buttons simultaneously until the boot screen reappears. Access Tier Privileges: USER, EH&S & CERTIFIER Users have the ability to customize their containment Manufacturer default passcodes: cabinets within a defined set of options for each authorization level.
Rooster™ Sensor200 USER MANUAL Set/Change Passwords To change or set a password, follow this GUI (graphical user interface) path to trigger the password change sequence: Home>Settings>System>Advanced>Change Passwords You will have to enter an EH&S or Certifier passcode to get access to the “Advanced” menu. To change either the EH&S or Certifier passcode, you must first re-enter the old passcode.
Rooster™ Sensor200 USER MANUAL If the sash reading is 1% of full scale greater than the normal position, the sash is ▪ considered to be in the open position. If sash readings are between the closed and open positions, the sash is considered to be ▪...
Rooster™ Sensor200 USER MANUAL The Rooster Sensor200 offers an array of customization options for alarm behaviors. The following section provides a detailed overview on how to customize alarm behavior to meet individual needs and preferences. Alarm Controls To provide our users with full customization of the alarm behaviors that are best suited for their facilities and unique conditions, the Rooster Sensor200 allows authorized users (Certifier &...
Rooster™ Sensor200 USER MANUAL Settings Definition Disables ringback. If an alarm is muted, the alarm remains muted for the entire duration of the alarm event. A muted alarm will ringback audibly after 10 seconds if the unit is still in an active alarm state. This is the default setting.
Rooster™ Sensor200 USER MANUAL Startup Delay Definition Alarm is paused for 30 seconds on power up. This is the default setting. 1 min Alarm is paused for 1 minute on power up. 2 min Alarm is paused for 2 minutes on power up. 5 min Alarm is paused for 5 minutes on power up.
Rooster™ Sensor200 USER MANUAL Examples: 1. If the sensor becomes disconnected, and Sensor Alarm is set to Tone 1, the audible alarm will play Tone 1, and the on-screen alert banner will indicate Sensor Fault. 2. If the sensor becomes disconnected, and Sensor Alarm is set to Off, there will be no audible alarm, and the on-screen alert banner will indicate Sensor Fault.
Rooster™ Sensor200 USER MANUAL Airflow Resolution Definition 1 fpm Displayed units in FPM are rounded to 1 fpm. This is the default setting. 2 fpm Displayed units in FPM are rounded to 2 fpm. 5 fpm Displayed units in FPM are rounded to 5 fpm. .01 m/s Displayed units in m/s are rounded to .01 m/s.
Rooster™ Sensor200 USER MANUAL 9. Enter the dimension(s) of the duct, diameter for circular shape, height and width for rectangular shape. A third units touch toggle of CFM is accessible on the main screen with volumetric flow enabled. Air Changes Per Hour The Sensor200 displays velocity flow by default.
Rooster™ Sensor200 USER MANUAL BACnet® MS/TP Objects The Rooster BACnet® MS/TP interface allows users to extensively configure and monitor the device. See the objects table below for details. Rooster™ Sensor200 USER MANUAL 62360MN000-A00 26 of 40...
Page 27
Rooster™ Sensor200 USER MANUAL BACnet® MS/TP Objects Table Feature Object Device Units Range Read/ Definition Default Notes Type Instance Write Value MAC Address Analog 1 - 127 MAC Address MAC Address must match Value alarm module to establish initial communication MAC ID Analog 1 - 254...
Page 28
Rooster™ Sensor200 USER MANUAL Feature Object Device Units Range Read/ Definition Default Notes Type Instance Write Value NSB High Analog 0 to 40.99 High air velocity value that will No value set Valid in Night Setback mode of Alarm Clear Value clear an alarm operation...
Page 29
Rooster™ Sensor200 USER MANUAL Feature Object Device Units Range Read/ Definition Default Notes Type Instance Write Value Calibration Binary 0: Uncalibrated 0, 1 Calibration status Calibrated Status Input 1: Calibrated Low Flow Alarm Binary 0: Inactive 0, 1 Low Flow Alarm becomes active Input 1: Active if low flow alarm setpoint is...
Page 30
Rooster™ Sensor200 USER MANUAL Feature Object Device Units Range Read/ Definition Default Notes Type Instance Write Value NSB Mode Binary 0: Disabled 0, 1 Enable or disable Night Setback Value 1: Enabled mode of operation Disabled NSB Mute Binary 0: Audible 0, 1 Configure the Night Setback Muted...
Page 31
Rooster™ Sensor200 USER MANUAL Feature Object Device Units Range Read/ Definition Default Notes Type Instance Write Value Device Volume Multi- 1: High 1, 2, 3 Device volume control High State 2: Medium Value 3: Low Relay1 Polarity Multi- 1: Normally 1, 2, 3 Relay out polarity status when Normally...
Page 32
Rooster™ Sensor200 USER MANUAL Feature Object Device Units Range Read/ Definition Default Notes Type Instance Write Value 4: 1 min 5: 5 min 6: 10 min Backlight Dim Multi- 1: 1 min 1, 2, 3, 4, 5 Time delay before screen Time State 2: 5 min...
Page 33
Rooster™ Sensor200 USER MANUAL Feature Object Device Units Range Read/ Definition Default Notes Type Instance Write Value SerialNumber Character Standard Serial number of Rooster Rooster information, ID Data String serial Value number format Rooster Caldate Character Standard Calibration date Rooster information, airflow String date format...
Rooster™ Sensor200 USER MANUAL I/O Configuration Relay Outputs Flow Alarm and Sash Alarm link to relay outputs 1 and 2 by default. Relay outputs are configurable, however, and can be linked to both alarms and on- screen accessory buttons. The output options are: 1.
Rooster™ Sensor200 USER MANUAL I/O Polarity For advanced users, it may be helpful to toggle relay and input nodes from normally open to normally closed. In the default state, a closed relay output denotes an alarm. If the alarm state is required to be an open relay, then toggle the output on the Sensor200.
Figure 10 Event Log Viewable On Screen USB Field Upgrade Procedure Degree Controls is continually improving Rooster™ products. The latest in Rooster™ technology offers users a convenient soft reboot procedure for upgrading the operating system while maintaining existing calibration data and user settings. This is available for a Rooster™ having firmware version 1.06 and later.
Rooster™ Sensor200 USER MANUAL Review the firmware update procedure carefully before you begin. The firmware update procedure must be allowed to complete without interruption. If the update procedure is interrupted by user interference, a power failure, or some other circumstance, the existing firmware may be corrupted, and the device may become nonfunctional.
Page 38
Rooster™ Sensor200 USER MANUAL 2. The “Enter Certify Password” screen will display. The factory default Certifier password is “6425”. This can be changed by accessing the Advanced menu. 3. The Factory Menu will display. Depress “Reset to Factory Defaults”. Rooster™ Sensor200 USER MANUAL 62360MN000-A00 38 of 40...
Rooster™ Sensor200 USER MANUAL Warranty For a period of one (1) year following the date of delivery, and subject to the other provisions of this Warranty Section, DegreeC warrants that all new products that are both (a) manufactured by DegreeC and (b) purchased directly from DegreeC (or an authorized distributor of DegreeC) shall be free of material defects in materials and workmanship.