MANUFACTURER'S STATEMENT
MANUFACTURER'S STATEMENT
Read this operation manual carefully before use to ensure proper operation of this product.
Failure to read this operation manual may cause improper operation and may result in serious injury or death of
a person.The meanings of the symbols are as follows.
Disregard of the warning symbol can cause improper operation which may cause death
WARNING
or serious injury.
Disregard of the caution symbol can cause improper operation which may cause injury of a
CAUTION
person or damage the object.
NOTE
Special attention is required to the section of this symbol.
It is required to check the operation manual if this symbol is shown on the product.
NOTE
1. This product is a non-contact switch intended for header mount or wall mount for use on an automatic sliding door.
Do not use for any other applications.
2. When setting the sensor's detection area, make sure that there is no traffic around the installation site.
3. Before turning the power ON, check the wiring to prevent damage or malfunction of equipment connected to
the product.
4. Only use the product as specified in the operation manual provided.
5. Be sure to install and adjust the sensor in accordance with the local laws and standards of the country in which
the product is installed.
6. Before leaving the installation site make sure that the product is operating properly and instruct the building
owner/operator on proper operation of the door and the product.
7.The product settings can only be changed by an installer or service engineer. When changed, the
changed settings and the date shall be registered in the maintenance logbook accompanying the door.
WARNING
Do not wash, disassemble, rebuild or repair the sensor, otherwise
it may cause electric shock or breakdown of the equipment.
Danger of electric shock
NOTE
The following conditions are not suitable for sensor installation.
-Fog or exhaust emission around the door
-Wet floor
-Vibrating header or mounting surface
-Moving objects, steel plate, emergency lights or illumination in the detection area or in vicinity
-Highly reflecting floor or highly reflecting objects around the door
SPECIFICATIONS
Model
: OAM-DUAL T / TV / TF / TT
Cover color
: Black
Mounting height
: 2.0 (6'6") to 3.5m (11'6")
Detection area
: See DETECTION AREA
Detection method
: Active infrared reflection *1
Microwave doppler effect
Depth angle
: AIR area -6 to +6°
adjustment
Microwave area +25 to +45°
Power supply *2
: 12 to 24VAC ±10% (50 / 60 Hz)
12 to 30VDC ±10%
Power consumption
: < 2.5W (< 4VA at AC)
Operation indicator
: See Operation indicator table
Test input
: Opto coupler
Voltage 5 to 30VDC
:
Current 6mA Max. (30VDC)
Activation output
: See INSTALLATION 2
Table 1
OAM-DUAL T OAM-DUAL TV OAM-DUAL TF OAM-DUAL TT
Cat.
2 (EN ISO13849-1 : 2008)
AIR
part
PL
d (EN ISO13849-1 : 2008)
Cat.
2 (EN ISO13849-1 : 2008)
Microwave
part
PL
d (EN ISO13849-1 : 2008)
Operation indicator table
Status
Operation indicator color
Set-up
Yellow blinking
Stand-by (installation mode)
Yellow
Green
Stand-by (operation mode)
Lookback (1st row) detection*4
Blue
2nd row detection
Red blinking
3rd row detection
Red
Orange
Microwave detection
Setting error
Red & green blinking
Signal saturation
Slow green blinking
Sensor failure
Fast green blinking
NOTE
The specifications herein are subject to change without prior notice due to improvements.
*1 : Active infrared reflection has a presence detection function.
*2 : The sensor has to be connected to a door system which has a SELV circuit.
*3 : Overcurrent protection with less than 2A.
OUTER DIMENSIONS AND PART NAMES
267(10 1/2")
125(4 15/16")
36(1 7/16")
43(1 11/16")
(2)
(1)
(3)
(4)
(5)
(6)
(7)
LOOKBACK AREA
When dipswitch 15 is set to ON, the lookback area, that provides extra safety over the threshold, is activated.
In case the lookback function is not required, set dipswitch 15 to OFF.
Do not set the 2nd row overlapping the threshold regardless of the setting of dipswitch 15.
2nd row
Lookback
(1st row)
3rd row
All manuals and user guides at all-guides.com
ENGLISH
ORIGINAL
Safety / test output
: Opto coupler (NPN)
Voltage 5 to 50VDC
Current 100mA Max.
Dark current 600nA Max.
(resistance load)
Noise level
: <70dBA
Output hold time
: <0.5 sec.
Response time
: <0.3 sec.
Operating temperature
: -20 to +55°C (-4 to 131°F)
Operating humidity
: <80%
IP rate
: IP54
Category
: See Table 1
Performance level
: See Table 1
Weight
: 320g (11.2oz )
Accessories
: 1 Operation manual
2 Mounting screws
1 Mounting template
1 Area adjustment tool
1 Cable 3m (9'10")
(8 × 0.22mm² AWG24 ) *3
1sec.
1sec.
*4 : See LOOKBACK AREA
[mm (inch)]
38(1 1/2")
(1) Connector
(2) Mounting holes
(3) Operation indicator
(4) Width adjustment screws
(5) Depth angle adjustment screw
(10)
(6) Function switch
(7) Microwave sensitivity potentiometer
(8) Dipswitches
(9) Detection window
(9)
(10) Area adjustment tool
(8)
Lookback
2nd row
(1st row)
3rd row
COMPLIANCE
EN16005:2012
EN12978+A1:2009
EMC Directive 2004/108/EC
EN ISO13849-1:2008
EN61496-3:2001 clause 4. 3. 5 and 5. 4. 7. 3
Notified Body: TÜV SÜD Product Service GmbH, Daimlerstraße 40 60314 Frankfurt Germany
DETECTION AREA
A
Lookback(1st row)
2nd row
3rd row
G
1000(3'3")
H
I
2000(6'6")
2000
1000
0
(6'6")
(3'3")
AIR emitting area
The chart shows the values at depth angle +6°
A
2.00 (6'6")
2.20 (7'2")
2.50 (8'2")
2.70 (8'10")
B
0.05(2")
0.06 (2")
0.07 (3")
0.074(3")
C
0.07(3")
0.08 (3")
0.09 (4")
0.10 (4")
D
0.23 (9")
0.25 (10")
0.28 (11")
0.31 (1')
E
0.35 (1'2")
0.39 (1'3")
0.44 (1'5")
0.48(1'7")
F
0.59 (1'11")
0.65 (2'2")
0.74 (2'5")
0.80 (2'8")
G
1.21 (3'12")
1.33 (4'4")
1.51(4'11")
1.63 (5'4")
H
1.86 (6'1")
2.05 (6'9")
2.32 (7'7")
2.51 (8'3")
I
2.52(8'3")
2.78 (9'1")
3.15 (10'4")
3.40 (11'2") 3.79 (12'5")
AIR detection area
To comply with EN16005, make sure that the detection area is within the values of the chart below.
A
2.00 (6'6")
2.20 (7'2")
3.00 (9'10")
X
0.23 (9")
0.25 (10")
0.34 (1'1")
G
1.02 (3'4")
1.12 (3'8")
1.53 (5')
I*
2.41 (7'11")
2.65 (8'8")
3.60 (11'10")
The values mentioned in "detection area" refer to the test conditions as described in the EN16005
(the emitting area is specified in "emitting area").
*: When installed at higher than 3.0m(9'10"), EN16005 requirements are fulfilled only within the area width "I"
of 3.6m(11'10").
NOTE
The actual detection area may become smaller depending on the ambient light, the color / material of
the object or the floor as well as the entry speed of the object.
The sensor may not be activated when the entering speed of the object or a person is slower than
50mm / sec. or faster than 1500mm / sec.
INSTALLATION
1
1. Affix the mounting template at the desired mounting position.
Refer to the chart in below.
2. Drill two mounting holes of ø3.4mm (ø1/8").
3. To pass the cable through the header, drill a wiring hole of ø8mm (ø5/16").
4. Remove the mounting template.
5. Remove the housing cover. Fix the sensor to the mounting surface with the two mounting screws.
H : Height from the floor to the bottom of the header
Header
Y : Distance between the bottom of the header and the sensor
Sensor
X : Distance between the door and the mounting surface
Maximum distance (Y)
H
Y
X
2.30 (7' 6")
2.00 (6' 6")
X
0
0.05 (2")
0.13 (5")
0.10 (4")
0.11 (4")
0.15 (6")
0.10 (4")
H
0.20 (8")
-
Door
-
0.25 (10")
0.30 (12")
-
Floor
NOTE
Make sure not to mount the sensor lower than the bottom of header.
CAUTION
Make sure to affix the mounting template as described in the above chart,
otherwise it can be dangerous since there may be no detection area around
Risk of getting caught
the threshold. Install the sensor as low as possible on the header.
2
Wire the cable to the door controller as shown below.
1.White
Power
1
supply
2.Brown
3.Green
Activation
2
output
4.Yellow
5.Pink (+)
Safety /
3
test output
6.Blue (-)
7.Red (+)
Test input
4
8.Black (-)
OAM-DUAL T
OAM-DUAL TV
1
12 to 24VAC±10% / 12 to 30VDC±10%
Form A relay
(+)
Voltage output 3.2V@10mA
2
50V 0.3A Max.
(-)
Min. 4.5V(no load)
3
Opto coupler(NPN) / Voltage: 5 to 50VDC
4
Opto coupler / Voltage: 5 to 30VDC
4
WARNING
Before starting the procedure, make sure that the power is turned OFF.
When passing the cable through the hole, do not tear the shield
Danger of electric shock
otherwise it may cause electric shock or breakdown of the sensor.
3
1.Plug the connector.
2.Supply power to the sensor. Adjust the detection area and set the dipswitches.
(See ADJUSTMENTS 4. Dipswitch settings)
NOTE
Make sure to connect the cable correctly to the door controller before turning the power ON.
When turning the power ON or after adjusting the settings, do not enter the detection area for more
than 10 seconds in order to enable the presence detection.
Do not touch the dipswitches before turning the power ON, otherwise an error occurs.
After changing the dipswitches and/or potentiometer, make sure to push the function switch for 2 seconds.
4
Place the housing cover.
If wiring is to be exposed, break the knockout.
Do not use the sensor without the cover.
WARNING
When using the cable knockout, install the sensor indoors or use the rain cover
(separately available) otherwise electric shock or breakdown of
Danger of electric shock
the sensor may occur.
Machinery Directive 2006/42/EC
EN ISO13849-2:2008
AutSchR (OAM-DUAL TV/TF/TT Only)
[mm(feet,inch)]
AIR
Mounting height : 2.2m(7'2")
Angle adjustment : +6°
Sensitivity : M
: Emitting spots
Mounting
surface
: Emitting spots
B
(can be eliminated)
D
C
E
: Detection area
X
F
Microwave
Mounting height : 2.2m(7'2")
Vertical adjustment : +35°
Sensitivity : H
Area width : wide
Speed of detection object
: 50mm / sec.
1000
2000
: Detection area
(3'3")
(6'6")
[m(feet,inch)]
3.00 (9'10")
3.50 (11'6")
0.08 (3")
0.09 (4")
0.11 (4")
0.12 (5")
0.34 (1'1")
0.39 (1'4")
0.53 (1'9")
0.61 (2')
0.89 (2'11")
1.03(3'5")
1.81 (5'11")
2.11 (5'11")
2.79 (9'2")
3.25 (10'8")
4.42 (14'6")
Test conditions required by EN16005
Floor :Grey paper
Detection object : EN 16005 CA reference body
Sensitivity : middle
Speed of detection object : 50mm / sec.
2.50 (8' 2")
2.80 (9' 2")
3.00 (9'10") 3.50 (11'6")
No limit
0.13 (5")
0.13 (5")
0.14 (6")
0.14 (6")
0.12 (5")
0.12 (5")
0.12 (5")
0.12 (5")
0.10 (4")
0.11 (4")
0.11 (4")
0.11 (4")
0.09 (4")
0.10 (4")
0.10 (4")
0.10 (4")
-
0.09 (4")
0.09 (4")
0.09 (4")
-
-
-
-
1.White
Power
1
supply
2.Brown
3.Green
Activation
2
output
4.Yellow
5.Pink (+)
Safety /
3
test output
6.Blue (-)
Test input
7.Red (+)
4
(Safety)
8.Black (-)
Test input
9.Gray/Pink (+)
(Activation) 5
10.Red/Blue (-)
OAM-DUAL TF
OAM-DUAL TT
Form A relay
Frequency output
100Hz±10%
50V 0.3A Max.
Opto coupler /
5
Voltage: 5 to 30VDC
[m (feet,inch)]
0
0
0
0
0
0