Phoenix Contact QUINT4-INV Manual

Phoenix Contact QUINT4-INV Manual

Dc/ac inverter

Advertisement

Quick Links

QUINT4-INV/24DC/1AC/600VA/
USB
DC/AC inverter
Data sheet
108987_en_00
1

Description

The QUINT-INV DC/AC inverter is used for generating AC
electricity in DC applications.
The output AC voltage RMS value can be configured via
software from a total of nine values in two ranges. The range
will be selected via the signal terminal during device startup.
The QUINT-INV can be connected in parallel to generate a
redundant system, to increase power, or to generate a 3-
phase grid.
Can be used worldwide thanks to manual selection of
AC output voltage via signal terminal
Pure sine curve at the output
Comprehensive signaling
Parallel connection possible (increased performance
and redundancy, 3 AC)
Integrated USB interface
High efficiency
All technical specifications are nominal and refer to a room temperature of 25 °C and 70% relative humidity at
2000 m above sea level.
© PHOENIX CONTACT
2020-09-28
Technical data (short form)
Nominal input voltage
Input voltage range
Current consumption
Apparent power
Real power
Nominal output voltage / Nominal
output current , 100% load 
Output voltage tolerance ( no soft
start )
Nominal output frequency
Output frequency tolerance
Form of output voltage
Efficiency ( Nominal load )
MTBF (IEC 61709, SN 29500)
Ambient temperature (operation)
Dimensions (W/H/D)
Weight
24 V DC
20 V DC ... 30 V DC
typ. 23 A / max. 28 A
600 VA
480 W
120 V AC / 5 A
( 100 V AC / 6 A...130 V AC / 4,6 A )
230 V AC / 2.6 A
( 200 V AC / 3 A...240 V / 2,5 A )
±2 %
60 Hz / 50 Hz
±0.5 %
Pure sine
> 86 % (120 V AC) /
> 87 % (230 V AC)
532525 h (40 °C)
-25 °C ... 60 °C
180 / 130 / 125 mm
2.5 kg

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUINT4-INV and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Phoenix Contact QUINT4-INV

  • Page 1: Description

    QUINT4-INV/24DC/1AC/600VA/ DC/AC inverter Data sheet 108987_en_00 © PHOENIX CONTACT 2020-09-28 Description The QUINT-INV DC/AC inverter is used for generating AC electricity in DC applications. Technical data (short form) The output AC voltage RMS value can be configured via Nominal input voltage 24 V DC...
  • Page 2: Table Of Contents

    QUINT4-INV/24DC/1AC/600VA/USB Table of contents Description ..........................Table of contents......................... Ordering data ..........................Technical data..........................Safety regulations and installation notes ................... Symbols used ...............................10 Important safety and warning instructions.....................10 Design ............................Function elements ............................12 Device dimensions and keep-out areas......................13 Block diagram...............................13 Mounting and removing......................
  • Page 3 QUINT4-INV/24DC/1AC/600VA/USB 14 Signaling ........................... 14.1 LED indicators and signal outputs ........................23 14.2 Signal outputs...............................24 14.3 Signal inputs ..............................24 15 Derating............................. 15.1 Ambient temperature ............................25 15.2 Installation height............................25 108987_en_00 PHOENIX CONTACT 3 / 25...
  • Page 4: Ordering Data

    Order No. Pcs./Pkt. Used for communication between an industrial PC and MINI-SCREW-USB- 2908217 Phoenix Contact devices with USB-Mini-B connection. DATACABLE 2-piece universal wall adapter for securely mounting the UWA 130 2901664 device in the event of strong vibrations. The profiles that are screwed onto the side of the device are screwed directly onto the mounting surface.
  • Page 5: Technical Data

    QUINT4-INV/24DC/1AC/600VA/USB Technical data Input data Nominal input voltage 24 V DC Input voltage range 20 V DC ... 30 V DC Current consumption typ. 23 A / max. 28 A Connection data, input Connection method Screw connection Conductor cross section, rigid 0.2 mm² ... 6 mm²...
  • Page 6 QUINT4-INV/24DC/1AC/600VA/USB Efficiency ( Nominal load ) 120 V AC 230 V AC > 86 % > 87 % 100 150 200 250 300 350 400 450 500 Power dissipation 120 V AC 230 V AC No load typ. 21 W typ. 21 W Nominal load typ.
  • Page 7 QUINT4-INV/24DC/1AC/600VA/USB Status and diagnostic indicator / signal output P>P Connection labeling Switching output Transistor output, active Continuous load current 20 mA LED status indicator green Status and diagnostic indicator / signal input Start 230V Connection labeling Low signal Connection to SGnd with < 2.7 kΩ...
  • Page 8 QUINT4-INV/24DC/1AC/600VA/USB Data interface USB (Modbus/RTU) Connection labeling Interface designation USB (Modbus/RTU) USB classification MINI-USB Type B Transmission physics USB 2.0 Locking Screw Electrical isolation Data interface Parallel Port Connection labeling Interface designation Parallel Port Connection method RJ45 Locking Locking clip Electrical isolation...
  • Page 9 QUINT4-INV/24DC/1AC/600VA/USB Electromagnetic compatibility / Conformance with EMC Directive 2014/30/EU Noise emission in accordance with EN 61000-6-4 Conducted noise emission EN 61000-6-4 Noise emission EN 61000-6-4 Immunity in accordance with EN 61000-6-2 CE basic standard EN 61000-6-2 requirement Tested Electrostatic discharge EN 61000-4-2 Housing contact discharge ±...
  • Page 10: Safety Regulations And Installation Notes

    QUINT4-INV/24DC/1AC/600VA/USB Safety regulations and installation Important safety and warning instructions notes WARNING: Danger to life by electric shock! Symbols used Instructions and dangers are labeled with the corresponding symbols in this installation note. – Only skilled persons may install, start up, and operate the device.
  • Page 11 QUINT4-INV/24DC/1AC/600VA/USB – Source connected to the inverter input must be SELV NOTE circuits that can be either battery circuits or secondary circuits derived from mains circuits of overvoltage category CAT II up to 300 V and have to be separated from mains circuits by double or reinforced insulation.
  • Page 12: Design

    QUINT4-INV/24DC/1AC/600VA/USB Design Function elements Figure 1 Position of the function elements 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 Link Parallel Port Power Single Redundancy Alarm L1 (Slave) (Master) (Master) Soft Start DC OK Output AC 120/230V Input DC 24V...
  • Page 13: Device Dimensions And Keep-Out Areas

    QUINT4-INV/24DC/1AC/600VA/USB Device dimensions and keep-out areas Figure 2 Device dimensions and keep-out areas 132,5 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 Link Parallel Port Power Single Redundancy Alarm L1 (Slave) (Master) (Master) Soft Start DC OK Output AC 120/230V...
  • Page 14: Mounting And Removing

    QUINT4-INV/24DC/1AC/600VA/USB Mounting and removing Normal mounting position The device can be snapped onto all DIN rails NOTE according to EN 60715 and should only be The device must be installed in a control cabinet mounted in the normal mounting position. that can be locked and only opened by specialist staff.
  • Page 15: Removing The Inverter

    QUINT4-INV/24DC/1AC/600VA/USB Removing the inverter 7.5.1 Mounting the UWA 182/52 universal wall adapter Proceed as follows to remove the device: Take a suitable screwdriver and insert this into the lock The UWA 182/52 universal wall adapter (Order hole on the universal DIN rail adapter (A).
  • Page 16 QUINT4-INV/24DC/1AC/600VA/USB 7.5.2 Mounting the UWA 130 2-piece universal wall adapter The UWA 130 universal wall adapter (Order No. 2901664) is attached to the device using the Torx screws provided. Proceed as follows to disassemble the universal DIN rail adapter that comes pre-mounted: Remove the screws for the universal DIN rail adapter using a suitable screwdriver (Torx 10).
  • Page 17: Device Connection

    QUINT4-INV/24DC/1AC/600VA/USB Device connection Connection parameters Figure 10 Connection parameters [mm] [Nm] [lb in] [mm²] [mm²] [mm²] [mm²] (Cu) Input DC 1.1...1.2 0.2-6 0.2-4 0.2-4 0.2-4 30-10 0.5-0,6 Output AC 2.1...2.3 0.2-6 0.2-4 0.2-4 0.2-4 30-10 0.5-0.6 N 2.4, PE 1.3 Screw 0.2-6...
  • Page 18: Ac Output

    QUINT4-INV/24DC/1AC/600VA/USB AC output The device also features the signal inputs: – Remote Buffered output voltage is connected via connection – Start 120 V: inverter startup in the 120 V range, digital terminal blocks: Output AC 120 / 230 V. input Figure 12 Output voltage connection terminal blocks: –...
  • Page 19: Device Operation

    QUINT4-INV/24DC/1AC/600VA/USB 10.1.1 MINI-SCREW-USB-DATACABLE – Master device in the mode power increase, redundancy, or 3AC (switch position: L1 (Master)) The uninterruptible power supply unit is connected to the – Slave device in the mode power increase or USB PC connection with data cable MINI-SCREW-USB- redundancy (switch position: L1 (Slave)) DATACABLE (Order No.
  • Page 20: Method Of Operation

    QUINT4-INV/24DC/1AC/600VA/USB Method of operation 12.3 Input voltage setting options You can set the following DC input voltage parameters via 12.1 Device start the POWER MANAGEMENT SUITE software: When a valid input voltage is applied and one of the Start –...
  • Page 21: Parallel Operation

    QUINT4-INV/24DC/1AC/600VA/USB 12.3.2 Application example: Operation on a battery Comply with the national safety regulations. In particular, comply with the regulations on grounding the The inverter DC input voltage is supplied via a battery with neutral conductor. In the delivery state, this is ensured 24 V nominal voltage.
  • Page 22: Signaling

    QUINT4-INV/24DC/1AC/600VA/USB Signaling Various LED indicators are available for visual function monitoring of the inverter. Active signal outputs can be used to forward this data to a higher-level control system. Figure 21 LED indicators 120V AC OK P>Pn / Remote 230V 3 .1...
  • Page 23: Led Indicators And Signal Outputs

    QUINT4-INV/24DC/1AC/600VA/USB 14.1 LED indicators and signal outputs For device signaling and the corresponding states, please refer to the table below. Figure 22 LED indicators and signal outputs Status LED Switching output Note Alarm DC OK AC OK P>Pn 120V / 230V...
  • Page 24: Signal Outputs

    QUINT4-INV/24DC/1AC/600VA/USB 14.2 Signal outputs P>Pn If the output power exceeds the maximum permitted output Alarm power, the signal output is active (high level). When an alarm is present, the signal output is active (low The signal status can be inverted via the POWER level).
  • Page 25: Derating

    A power derating of 0.6%/100 m should be observed for installation heights between 2000 and 3000 m. Figure 24 Altitude-dependent derating 1000 2000 3000 H [m] PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 108987_en_00 25 / 25 phoenixcontact.com...

This manual is also suitable for:

Quint24dcQuint1acQuint600vaQuintusb

Table of Contents