Appleton WSR Series Instruction Sheet

Interlocked receptacles

Advertisement

Quick Links

Instruction for Installation, Operation and Maintenance
11
11
of
WSR
Interlocked Receptacles: 30, 60 & 100 Ampere
"WSR" SERIES:
Heavy duty single throw safety switch with interlocked
Appleton Powertite
compatible receptacle .
®
COMPLIANCES:
UL. Listed, File No. 145917
UL498 - Attachment Plugs and Receptacles
UL98 - Enclosed and Dead-Front Switches
UL50 •· Enclosures for Electrical Equipment
NEC wire bending space, Table 373-6(b).
ELECTRICAL RATINGS:
Maximum Voltage: 600VAC at 60 Hz, 250 VDC 30, 60 or 100
Amperes, depending on current rating of product
( See product nameplate for details )
Read instructions carefully and with full understanding for
safe installation and operation..
S TANDARD FEATURES:
• Epoxy coated finish on receptacle and disconnect
switch housing.
• Current carrying parts in housing are all plated copper
• Lugs ·· front removable, standard mechanical lugs on
incoming line .. L. a y-•in ground lug.
• Screw cover assembly provided for 60 & 100 Ampere
units which can be used on receptacle housing,
instead of flip cover assembly to meet certain environ
mental conditions ..
OPTIONS:
• Electrical Interlocks -1 N.O., 1 N. C. or 2 NO, 2 N . . C.
MODIFICATION WARNING
Do not modify these devices in anyway . . Replace any missing
or broken parts with the proper replacement parts from
Appleton Electric. Modification of these devices or substitution
of parts with non-standard parts may result in serious/fatal
personal injury from electrocution.
TABLE A
HORSEPOWER RATING:
DC
AC
CA1ALOG
VOLTS VOLTS
AMP
NUMBERS
600
250
30
WSR3352
250
600
30
WSR33542
250
600
60
WSR6352
250
600
60
WSR63542
250
600
100
WSR10352
250
600
100
WSR103542
lli J ------
COMPANY
HORSEPOWER RATINGS
SWITCH
AC
TYPE
STAND. MAX. STAND. MAX.
FUSED
7.5
20
.... ..
NON-FUSED
20
FUSED
15
50
---
NON-FUSED
50
FUSED
75
30
-·--
NON-FUSED
75
FIGURE A
Except as expressly provided by Appleton Electric
Company (Appleton) in writing, Appleton products are
intended for ultimate purchase by industrial users and for
operation by persons trained and experienced in the use
and maintenance of this equipment and not for consumers
or consumer use .. Appleton warranties do not extend to, and
no reseller is authorized to extend Appleton's warranties to,
any consumer.
ELEC TRICAL WARNING
Electrical power must be turned
installation and maintenance.
I
in serious
fatal injuries due to electrocution.
DAMAGE WARNING
If any parts of the "WSR" unit or the mating plug appear to be
missing, broken or show signs of damage:
DISCON TINUE USE IMMEDIATELY
This condition could cause serious/fatal personal injury due to
electrocution and/or equipment damage. Repair replacement
part(s) before continuing service with the proper replace­
ment part(s) before continuing service
DC
The
"WSR"
---
tested for use with copper conductors only.
5
use aluminum wiring,as dangerous
---
DO NOT
5
overheating and fire may result.
-·--
10
--·-
10
---
20
... .. ..
Not suitable for use as service equipment.
20
330118
-I N _ s _r_R_u_ c _ r_ 1 o _ N _ S _ H _
before and during
OFF
Failure to do so m ay result
WARNING
receptacles are designed and
WARNING
Rev. A
3/29/95
E T
E
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WSR Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Appleton WSR Series

  • Page 1 • Lugs ·· front removable, standard mechanical lugs on or consumer use .. Appleton warranties do not extend to, and incoming line .. L. a y-•in ground lug. no reseller is authorized to extend Appleton's warranties to, any consumer.
  • Page 2: Electrica L Wa Rning

    • The receptacle face of the 60 & 100 Ampere units is threaded to 10-14 allow mating plugs to thread onto it for a weather-proof union . . • WSR Series Interlocked receptacles may be pole mounted or installed on flat vertical surfaces .. CONTACT PHASE IDENTIFICATION MARKINGS:...
  • Page 3 WSR INTERLOCKED RECEPTACLE - 30, 60, & 100 AMP FIGURE C ASSEMBLY VIEW WITH COVER REMOVED - UNIT SHOWN IS CATALOG NUMBER WSR6352 I • ,�2 .�:c hc,2 Z.lla ------� --------� ( 7,57 0,4 ) --�-----� CATALOG �ER DIMENSION •A• WSR3352 WSR33342 19.23...
  • Page 4: Installation

    C. Grease must be used on conduit and reducer bushing threads to completely seal out water. * Appleton Electric Company thread lubricant, part no. TLC-3, is recommended to be applied on threads in three generous lines running parallel to the thread axis and spaced equidistant around the thread . .
  • Page 5: Operation

    10. OPERATION: A. The receptacle can now be turned to the "ON" position by lifting the operating handle ( 1 1) to the upper-most position. Please note that the receptacle can be turned "ON" with or without a mating plug engaged. •...
  • Page 6: Electrical Testing

    receptacle (1) and either the disconnect switch load side lugs (9) or fuse block lugs (10). These wir· e markers 5. WIRING ( CONTINUED ): TABLE D: TERMINAL WJRE RANGE AND STRIPPING GUIDE I l l l i l l ill11 1 l i i i j : i l i i i i i i i i i i : : i : i [ l i f l ! l ! l ! ! f ill iliT�! : 1i ;�: r s : : : r I!�:;r.:.�r.,��"li�l i �...
  • Page 7: Ground Lug

    • Refening to "FIGURE C", replace the disconnect switch assembly into housing by reversing the steps taken to remove • Torque the mounting screws (17) to 15 - 20 lb.-in. torque. • Torque the line side lug screws (7) & the load side lug screws (9) to the appropriate values shown in "TABLE C". •...
  • Page 8 DISCONNECT SWITCH ASSEMBLY - CATALOG NUMBER WSRNT60F FIGURE D EXPLODED VIEW OF SWITCH AND INTERLOCK ROD ASSEMBLY B. DISCONNECT SWITCH AND HANDLE ASSEMBLY ( CONTINUED ): To assemble new disconnect switch component parts - • Replace disconnect switch and handle assembly with the same type as shown in "TABLE E" . . •...
  • Page 9 D. RECEPTACLE ASSEMBLY SCREW COVER INSTALLATION • Referring to "FIGURE C", loosen the three flip cover assembly mounting screws which fasten the flip cover assembly to the receptacle housing (1 ). Remove the flip cover assembly by carefully lifting it off of the receptacle housing. Retain for future use, if desired.
  • Page 10 . . The accuracy or completeness thereof are not guaranteed. In accordance with Appleton Electric Companies "Terms and Conditions of Sale", and since conditions of use are outside ou control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection herewith.