GCAN-GT-410 user manual 1. Function introduction 1.1 Function overview GCAN-GT-410 is a programmable bus gateway (converter). It integrates 1 CAN bus interface, 1 Ethernet interface, 1 RS485 interface, and 1 RS232 interface, users can customize the data conversion format programmatically.
Page 4
Guangcheng Technology GCAN-GT-410 user manual ● Data conversion between industrial Ethernet and CAN bus ● Industrial Ethernet equipment and CAN network equipment interconnection ● Electrical communication network ● Industrial control ● High-speed, large data volume communication...
(height) 99.5mm, the schematic as shown in Figure 2.1. Figure 2.1 Dimensions of GCAN-GT-410 module 2.2 Device installation The installation method of GCAN-GT-410 module is shown in Figure 2.2. A flat-blade screwdriver can be used to assist in installing the module on the DIN rail.
RS485 serial interface, GCAN-GT-410 module wiring terminal block as shown in Figure 2.3. Figure 2.3 GCAN-GT-410 module wiring terminal block The power interface of the GCAN-GT-410 module is led out by a 4 Pin plug-in terminal. The interface definition is shown in Table 2.1. Port...
Page 7
Guangcheng Technology GCAN-GT-410 user manual RS485 device. The interface definition is shown in Table 2.3. Port Name Definition RS232 data receive RS232 data transmit NC Unused RS232 GND C-BUS NC Unused RS485 Signal B- RS485 Signal A+ NC Unused Table 2.3 CAN-BUS Port Definition...
RS485 interfaces. 3.2 CAN Connection When GCAN-GT-410 is connected to the CAN bus, it only needs to connect CAN_H to CAN_H and CAN_L to CAN_L to establish communication. The CAN-bus network adopts a linear topology, and the two farthest terminals of the bus need to be installed with 120Ω...
Page 9
Guangcheng Technology GCAN-GT-410 user manual 10 kbit/s 5.0km 5 kbit/s 13km Table 3.1 Baud rate and length...
Programming interface of OpenPCS mainly contains: 1)Menu Project window 3)Edit window 4)Output window 5)Catalog window 4.3 Create project and download program Note: GCAN series PLC uses the network port to download the program, and the factory IP address of the PLC: 192.168.1.30. 4.3.1 Create project...
Page 11
Guangcheng Technology GCAN-GT-410 user manual Figure 4.2 Create project 4.3.2 Add program page file Add files to the project (for example: add a program page ST, Program written in ST language), as shown in Figure 4.3. Please note that: the string entered in the name field cannot start with a number.
Page 12
Guangcheng Technology GCAN-GT-410 user manual Figure 4.3 Create a new file 4.3.3 Programming First define the variable in the variable area (VAR to END_VAR) VAR v1:INT:=0; v2:INT:=0; oled at%Q0.0:Byte; END_VAR After the variable is defined, start programming. The following is a simple...
Page 13
Guangcheng Technology GCAN-GT-410 user manual Figure 4.4 Debug connection Click 'New' to set up parameters, port number is the actual serial port number of the computer, shown in Figure 4.5.
Page 14
Guangcheng Technology GCAN-GT-410 user manual Figure 4.5 Connection Setup Enter 'TCP' in Name and click 'Select'. Figure 4.6 Click 'Select' Select 'TCP432' , then click 'OK'.
Page 15
Guangcheng Technology GCAN-GT-410 user manual Figure 4.7 Select TCP432 Click 'Settings'. Figure 4.8 Click 'Settings' Please enter 23042 for Port. IP address 192.168.1.30, set the back point OK...
Page 16
Guangcheng Technology GCAN-GT-410 user manual Figure 4.9 IP Address and Port Number Settings After completing the settings, click 'Close' Figure 4.10 Click 'Close' Set 'Resource Properties'...
Page 17
Guangcheng Technology GCAN-GT-410 user manual Figure 4.11 Set “Resource Properties” Select 'GCAN_PLC' and 'TCP', then click 'OK' to complete the setting Figure 4.12 Select 'GCAN_PLC' and 'TCP' 4.3.5 Download the program and debug After completing the program, click 'Build Active Resource'.
Page 18
Guangcheng Technology GCAN-GT-410 user manual Figure 4.13 Completing the program Please check if there is an error/warning after completing the program. Figure 4.14 Check error and warning Click 'PLC', then select 'Online'.
Page 19
Guangcheng Technology GCAN-GT-410 user manual Figure 4.15 Select Online Click 'PC->PLC(Download)' to download program Figure 4.16 Program download...
Guangcheng Technology GCAN-GT-410 user manual 4.4 Restore the default IP of the device Disassemble the casing of the device, and dial the No. 2 dial code to the 'ON' position when the device is powered on. The green light of the 'PWR' indicator is always on, and the green and red lights of the 'RUN' indicator flash alternately to restore the device's default settings, The factory setting IP address is: 192.168.1.30.
Guangcheng Technology GCAN-GT-410 user manual 5. Technical specifications PLC Parameters Programming environment OpenPCS Flash 32M byte SRAM 16M byte User data storage area 2k byte Run-Time System 1PLC mission PLC period time 3ms for 1000 instructions Programming language standards IEC 61131-3 Programming languages SFC、LD、FBD、ST、IL...
Guangcheng Technology GCAN-GT-410 user manual 6. Disclaimer Thank you for purchasing the GCAN series of software and hardware products from Guangcheng Technology. GCAN is a registered trademark of Shenyang Guangcheng Technology Co., Ltd. This product and manual are copyrighted by Guangcheng Technology.