DESCRIPTION
The BZ-150 power pack is the foundation for any low voltage lighting control
system. The BZ-150 supplies low voltage power to occupancy sensors and other
control devices, switching line voltage in response to signals from control devices.
The BZ-150 power pack is attached to existing junction boxes or mounted into
fi xture wiring trays.
Low voltage wiring should use at least 22-gauge wire. High voltage connections
should use at least 14-gauge. Always check local building codes. After initial
wiring is complete, check wiring diagrams to verify the power pack is wired
correctly. Improper wiring can cause damage to the power pack, lighting system,
occupancy sensor and other control devices.
INSTALLATION
TURN POWER OFF AT CIRCUIT
BREAKER BEFORE INSTALLING
WIRING
1. Make sure power has been turned off
at the circuit breaker.
2. Connect wires as shown in the wiring
diagram below, or as shown in the
BI-LEVEL CONTROL section.
White
Neut.
Black
120VAC
Hot
277VAC
Orange
+12-24VDC In
Hold ON
+12-24VDC In
Hold OFF
Brown
Call 800.879.8585 for Technical Support
WARNING
POWER PACKS.
High
Voltage
Power Pack
Red
Red
Low Voltage Wires
Control
Any 3-Wire
Common
24VDC
+24VDC
Sensor
Momentary Switch (optional)
Low
Voltage
Lighting
Load