jablotron Ei208W Quick Start Manual page 2

Stand-alone carbon monoxide detector

Advertisement

Fig. 3: 1 - ON; 2 - OFF
5) If the detector is OK, all three LEDs will flash briefly in sequence
and all symbols on the display (Ei208DW) will light up.
6) In order to make the detector resistant to unauthorized removal
and tampering, break off the small pillar on the base as shown in
Fig. 4a. To remove the detector from the ceiling it is now
necessary to use a small screwdriver which has to be inserted
between the detector body and the catch in the base (fig. 4b). The
locked detector can further be secured against rotating with a self-
tapping screw as shown in Fig. 4c
Fig.4a
Alarm signalling
Pre-alarm: when the detector detects over 43 ppm CO, the red
ALARM indicator flashes in accordance with the table. This is usually
not a concern in a shorter time interval, unless the acoustic signal
sounds. Such a slightly increased concentration may come from
various sources, e.g. from cooking, barbecuing or starting a
combustion engine. The display shows the current carbon monoxide
level if it exceeds 10 ppm.
When the detector detects a potentially dangerous carbon monoxide
concentration, the red ALARM LED starts flashing. If the concentration
remains unchanged, the detector sounds the alarm with a built-in siren.
The table below shows the detector signalling depending on the
concentration and exposure time. The detector reacts sooner with
greater concentrations. The siren can be silenced for 4 minutes by
holding down the test button. If the dangerous concentration persists,
the siren is reactivated. The siren cannot be silenced when the
concentration exceeds 150 ppm.
NEVER IGNORE THE SIGNALLING
OF INCREASED CARBON
MONOXIDE CONCENTRATION IN
The CO detector may sound if cigarette smoke is blown into it,
Note:
or aerosols are released nearby
CO alarm response:
CO gas
Red LED
Ei208DW display
concentration
pre-alarm
icon before the
(ppm)
siren sounds
0 < 10
Off
Blank
10 < 30
Off
ppm value
Flashes
on – 4 sec
off – 12 sec
30 <43
Off
ppm level
43 < 80
1 flash/s
060
80 < 150
2 flashes/s
>150
4
flashes/
2s
The Ei208W/Ei208DW stand-alone carbon monoxide detector
Fig.4b
THE BUILDING
.
Ei208DW display
icon
after
the
siren sounds
Blank
ppm value
Flashes
on – 4 sec
off – 12 sec
ppm level
060
ppm
ppm
100
100
ppm
ppm
150
150
ppm
ppm
1) Open the doors and windows to ventilate the area
2) Turn off all fuel appliances where possible and stop using them
3) Leave the threatened area as soon as possible
4) Get medical help immediately for anyone showing the symptoms
of carbon monoxide poisoning (headache, nausea)
Do not re-enter the property until the Alarm has stopped signalling
5)
harmful concentration of carbon monoxide. If the Alarm has been
silenced by pressing the test button, wait at least 5 minutes so the
Alarm can check if the CO gas has cleared.
6) Do not use the fuel appliances again until they have been checked
by an expert.
Note: If the carbon monoxide concentration has been decreased
only by ventilation, this might only be a temporary solution. It is
necessary to find the carbon monoxide source.
Detector testing, maintenance, fault indication
The detector regularly checks its function to ensure problem-free
functioning. Any fault is immediately signalled with LEDs or with a
symbol on the display.
It is further recommended to test the detector using a test button in
the following cases:
1) After the system is installed.
2) Regularly once per week
3)
After prolonged absence from the building
4) After repair or servicing of any of the fossil fuel-burning appliances
Fig. 4c
5) Once per year using a CO gas testing kit
The following table displays the status signalling after pressing the
test button:
Status
Standby
Unit OK
Low
battery
Sensor
failure
End of
life
When a low battery, detector failure or end of life is signalled,
the detector has to be replaced.
The carbon monoxide detector has a limited usable life which
runs out even if the detector is not used. There is a label on every
detector showing its usable life. The detector has to be replaced
after this date even if it does not signal any faults.
The detector requires no special maintenance. Keep it clean by
wiping it with a wet cloth from time to time. Do not use any aggressive
or abrasive cleaning agents.
Usable life
Siren
Power
Typical battery lifetime
Off
Operating temperature range
Off
Humidity range
Dimensions, weight
Conformity
Off
on
within
60-90
mins
(typ
72
mins)
on
within
10 – 40
mins
(typ
18
mins)
on
within 2
mins
(typ. 40
sec)
2
What to do when the alarm sounds
Red LED
Yellow
Green
LED
LED
(ALARM)
(fault)
(power)
No optical or acoustic signalling
Off
Off
Flashes
when test
button is
pressed
Off
1 flash
Off
Off
2 flashes
Off
Off
3 flashes
Off
Technical specifications
7 years (the end of life date is stated on the label)
Integrated non-replaceable lithium battery
for the whole usable life of the detector
EN 50291-1; EN 50291-2, EN 50270
Ei ELECTRONICS hereby declares that the Ei208W/Ei208DW detector is in
compliance with the essential requirements and other relevant provisions of
Directives 2004/108/EC, 2011/65/EU. The original of the conformity assessment
can be found at www.jablotron.com - Technical Support section.
Note: Although this product does not contain any harmful materials we
suggest you return the product to the dealer or directly to the producer after
use. For more detailed information visit www.jablotron.com.
Display
Sound
LCD
signalling
Ei280DW
Pressing
confirmed
with a
chirp
1 chirp
2 chirp
3 chirp
-10 to +40ºC
15% to 95% (non-condensing)
120x 105x40 mm, 170 g
P/N B17947 Rev0
MZZ25004