HPE8884MR Network I/O Expansion, Modbus RTU 485
FW4.02
28 point network point expansion unit for Modbus 485 networks. The large I/O count enables remote
monitoring and control of numerous points over the Modbus network.
Universal inputs may be locally scaled and tagged according to engineering units, calibrated and/or
filtered to adjust for cabling or sensor characteristics. Digital inputs and UI's may be configured as pulse
counters. Digital outputs may have short-cycle timers set.
Typical Applications
Digital/analogue inputs such as alarms, operation statuses, high/low level, water & air flow
proving, environmental conditions such as temperature, humidity or pressure, and other
auxiliary contacts.
Digital/analogue outputs for switching of fans, pumps, lighting or remote status indication, and
modulating control of actuators, speed or load controllers and remote analogue gauges.
Universal inputs and digital inputs may be used as counting inputs for metering of energy and
volume and instantaneous load calculation at the Master controller
Feature Summary
8 Digital Inputs (DI n/o or n/c, flip/flop, pulse-counting up to 10Hz)
8 Digital Outputs (DO) with power-up presetting & short-cycle timers
8 Universal Inputs (UI - user configurable analogue [AI] or digital [DI n/o or n/c], flip/flop, pulse-
counting up to 10Hz)
4 Analogue Outputs (AO) with power up presetting
RJ11 socket connection of HSD0012 or HSD0011 room sensors to UI1 & UI2 (room sensor
with set point adjuster option, occupancy button & HPECOM port)
UI's user definable for non-standard sensors, active or passive from 1kΩ
Connected sensors may be calibrated and filtered by way of the UI configuration
Isolated, 256 node (1/8
Communication speeds from 2400 baud up to 76800 baud
LED indication of the On/Off status of DI and DO points for fast visual status verification
Dynamic LED indication of AO status
Sequential flashing of DI LED's as 'Watchdog'
Automatic communication resumption after a power loss
PC configuration by text file download using FUNCPROG or by direct parameter settings entry
Upload text file data for retrieving lost application settings, for re-use in other controllers
HRW Limited
load), RS485 network driver
th
Unit E, 11/F, Sun Ying Industrial Centre
9 Tin Wan Close, Tin Wan
Hong Kong
Ph +852 2546 7402
Fax +852 2546 7403
www.hrw.hk

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HPE8884MR and is the answer not in the manual?

Questions and answers

Summary of Contents for HRW HPE8884MR

  • Page 1 HPE8884MR Network I/O Expansion, Modbus RTU 485 FW4.02 28 point network point expansion unit for Modbus 485 networks. The large I/O count enables remote monitoring and control of numerous points over the Modbus network. Universal inputs may be locally scaled and tagged according to engineering units, calibrated and/or filtered to adjust for cabling or sensor characteristics.
  • Page 2: Table Of Contents

    HP_MR S ......................... 22   THER ERIES EVICES UI C ........................23   ONFIGURATION EQUEST DOCUMENT UPDATE HISTORY ........................24   HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 2 of 24...
  • Page 3: Operation Overview

    The user display may contain up to 32 lines of user text with or without dynamic points included. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 3 of 24...
  • Page 4: Register Address Ranges

    1044 AO 1 Holding Register 1050 AO 2 Holding Register 1052 AO 3 Holding Register 1054 AO 4 Holding Register 1056 HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 4 of 24...
  • Page 5: Priority Levels

    Write current value as a manual override 525=0  Lock current value 525=1  Release current value for future change 525=17 HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 5 of 24...
  • Page 6: Function Block Points & Sub-Parameters

    * Digital 1 = 1000 (100%) when applied to these analogue logic functions. Analogue values will act as a Output Minimum when applied to an Output OR and Output Maximum when applied to an Output AND. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 7: Terminal Mode

    The HPECOMU data cable with USB connection is used for terminal mode between the device and a PC running a terminal program. HyperTerminal is recommended. The driver for the HPECOMU cable may be downloaded from www.hrw.hk, Resources / Tools, section. HyperTerminal Settings For successful communication between HyperTerminal and the device, initial Properties setup of HyperTerminal should be as per the screen prints below.
  • Page 8: Additional Settings

    In either case, after the Write action, you will need to reconnect the terminal program at the new baud rate if you wish to continue the terminal session. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 9: Break In To Terminal Mode

    (TTTTTTT…). After five (5) T’s have been sent to the device it will switch to terminal mode. At this point the device will display the default user screen. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 10: Administration Commands

    Enable 10 sec live update Enable/Disable display of point numbers and SLLD Screen Line Logic Display screen line numbers in the summary display HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 10 of 24...
  • Page 11: Summary Screen Setting

    DI or UI with pulse accumulator Reset pulse 100…800=6 config. (UI or DI setting 6) is reset to Example: 800=6 accumulator 1700…2400=6 zero HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 11 of 24...
  • Page 12: Operational Displays

    You may use SLL settings for alarm or warning text that will only appear when the assigned point has a value >0. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 12 of 24...
  • Page 13: Download Text File

    Column 4 = The dynamic point value  Column 5 = Units related to the dynamic point value (as configured in the linearization table) HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 13 of 24...
  • Page 14: 'Main' Physical I/O Display

    Enter P to display the first 21 active points. The listing will include any active logic connections and, in the case of the UI’s the present calibration offset if used. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 15: Reset To Factory Default

    Notepad. Whatever the process, the 10000=nnn line must be added if the file is to be used for Down Load in future. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 16: Universal Inputs

    * Measurement with some lower impedance voltage-based sensors may top out before the full voltage range is reached, requiring omission of the 4k7 resistor. HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 16 of 24...
  • Page 17: Linearisation Table

    4 and change Units display characters 134=-2 14=V (row 1 column 4) 24=d (row 2 column 4) 34=c (row 3 column 4) HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 17 of 24...
  • Page 18: Passive Sensor Definition

    7. If an intercept other than zero (0) is applied then raw count measurements must be at reference values shifted an equivalent amount Reset to Factory Default The FD=1 reset command also resets changes to the linearization tables HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 18 of 24...
  • Page 19: Installation & Commissioning

    24Vac power supplies cannot be guaranteed, we recommend that a repeater be used to provide isolation of the sections of the network having differing earth potential HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 20: Connections

    Connections HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 20 of 24...
  • Page 21: Dimensions

    Operating Temperature Range 0…50ºC (32…122ºF) Storage Temperature Range -5…75ºC (-40…167ºF) Humidity Range 10…95%rH (non-condensing) Dimensions 115mm H x 226.5mm L x 34.5mm D HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 21 of 24...
  • Page 22: Ordering Information

    * The Modbus port of these devices operates as a Modbus Master for the purpose of integration of a network of Modbus slave devices in to BACnet MSTP networks HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice...
  • Page 23: Ui Configuration Request Form

    10k NTC / Dig 20k NTC / Dig 100k NTC / Dig Nickel 1000 PT1000 Other: Passive types must be 1kΩ or higher Comments: HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 23 of 24...
  • Page 24: Document Update History

    Document Update History V4.02 150622 HRW address updated V4.02 141030 Upload application text-file, download network settings in text-file, isolated RS485 HRW HPE8884MR V402 Manual 150622.docx E. & O. E. / Subject to change without notice Page 24 of 24...