AMC-1044-T Monitor TABLE OF CONTENTS Section Title Page WARRANTY........................ii LIABILITY ........................ii MODIFICATIONS AND SUBSTITUTIONS..............ii PRODUCT RETURN ....................ii PRODUCT INFORMATION ....................iii PRODUCT DESCRIPTION....................1 INSTALLATION........................5 LOCATION AND MOUNTING..................5 WIRING OF THE MONITOR..................5 CABLE SIZES......................6 OPERATION AND CALIBRATION..................10...
AMC-1044-T Monitor 1 WARRANTY The AMC-1044-T monitor is warranted against defects in material and workmanship for a period of two years from date of delivery. During the warranty period, we will repair or replace components that prove to be defective in the opinion of The Armstrong Monitoring Corporation.
AMC-1044-T Monitor 2 PRODUCT INFORMATION Monitor Part Number …………………………………… Monitor Serial Number ………………..………………… Power Supply Requirements …………………………… 120 VAC, 60 Hz, 20 W max. Operating Temperature Range ………………………… 0° C to 50°C Relative Humidity ………………………………………... 0-99% RH, non condensing Contact Rating ……………………………………………...
AMC-1044-T Monitor 3 PRODUCT DESCRIPTION The AMC-1044-T is a gas monitoring system designed to be used with AMC broad selection of Sensor/Transmitter types. It serves to continuously monitor the target gas (listed in Product Information Section). The monitor comes with the following features (see Figures 1, 2 and 3).
Page 6
AMC-1044-T Monitor TIME DELAYS ACTUATORS AUDIO ALARM THREE CIRCUIT MINIATURE SWITCH Figure 1: Three-circuit miniature switch.
Page 7
1 ) Power On Indicator FAIL 2 ) Fail Indicator 3 ) Low Alarm Indicator HIGH 4 ) High Alarm Indicator 1044 215 Colonnade Road South Nepean, Ontario, K2E 7K3 U.S. & Canada toll free 1 (800) 4655777 Figure 2: AMC-1044-T monitor, front panel.
Page 8
FUSE 1 A OPTIONAL NEUT. HOT FAIL 120 VAC 5. POWER TERMINAL BLOCK 6. TEST SWITCH 7. LOW ALARM ADJUST 8. HIGH ALARM ADJUST 9. THREE CIRCUIT MINIATURE SWITCH 10. RELAYS 11. TRANSFORMER 12. AUDIO ALARM Figure 3: AMC-1044-T monitor, internal wiring.
4 INSTALLATION 4.1 LOCATION AND MOUNTING Care should be taken to securely fasten the AMC-1044-T monitor unit (via four mounting holes provided) to a solid, vertical, non-vibrating surface or structure. Mounting height is dependent on gas type. (See Figure 5 for mounting dimensions.) Note: All cable entry MUST be through the BOTTOM of the monitor enclosure only.
AMC-1044-T Monitor 4.3 CABLE SIZES For maximum noise rejection, each cable shield and metal conduit should be grounded at the monitor. The following is a listing of maximum distances the transmitter may be located from the monitor for various cable sizes.
Page 11
AMC-1044-T Monitor + SENS - POWER FAIL For 2 - wire Sensor/Transmitters + SENS - HIGH -HI+ -LO+ -FAIL+ + SIG – GND AC AC FUSE 1 A For 3 - wire Sensor/Transmitters OPTIONAL NEUT. HOT FAIL 120 VAC TRANSMITTER...
LED. 5.2 CALIBRATION The AMC-1044-T series monitor is factory calibrated at levels based on set standards. As the calibration procedure may cause the monitoring equipment to give a false alarm, appropriate precautions should be taken. Instructions on introducing the gas sample are included with the sensor/transmitter manual.
Page 15
AMC-1044-T Monitor Example: Full scale = 100 ppm Low alarm trip = 35 ppm (35/100 x 4 VDC)+1 = 2.4 VDC High alarm adjustment is done in the same manner as above, using the high alarm adjust and measuring between COM and HIGH TP.
AMC-1044-T Monitor 6 PREVENTIVE MAINTENANCE 6.1 GENERAL The monitor should be wiped clean with a damp cloth following a regular maintenance program. Avoid spraying, submersion and other conditions that could cause a liquid to enter the monitor and cause possible intrinsic damage to internal components.