ASM01883
PT-Link II LON-3
Installation Sheet
Includes: PT-Link II LON-3
(3) Self-drilling 8 x 1" Hex Head Screws, PT-Link II Flash Drive
PT-Link II LON-3
®
The PT-Link II LON-3
, provides bi-directional communication between
®
ONE* of the following types of Orion controllers—VCCX2, VCC-X,
VCB-X, VCM-X, SA, VCM, MUA II, or VAV/CAV:
VCCX2 Controller (SS1088)
VCC-X Controller (SS1079)
VCB-X Controller (SS1051)
VCM-X Controller (SS1026, SS1030, SS1032, SS1033,
SS1034, Y200920)
SA Controller (Y200921)
VCM Controller (SS1016, Y200409, Y200616, Y200822)
VAV/CAV Controller (SS1003, Y200301) and
MUA II Controller (SS1004, Y200405)
To determine what controller you have, you must look at the software
label located on the controller.
EPROM on older devices. If the controller label does not match any of
the SS or Y numbers listed above, your controller will not work with
the PT-Link II LON
.
®
*NOTE: The PT-Link II LON
only one Orion controller. If more than one Orion control-
ler is present in a system, each one will require a PT-Link
II LON
device for integration with a LON
®
network.
Data Sharing and Scheduling
•
Provides values from points on the Orion side of the
gateway to LON
devices as if the values were
®
originating from LON
•
Allows LON
devices to modify point values on the
®
Orion controller side of the PT-Link II LON
standard LON
write services.
®
Controller, 10 Foot CAT5e Crossover Cable,
®
Overview
The label is located on the
NOTE:
device can be used to connect to
®
protocol
®
objects.
®
by using
®
®
System Requirements
•
Computer running Microsoft
operating system.
•
Ethernet Crossover Cable (supplied).
•
PT-Link LON
and RUINET software—
®
included on flash drive and also downloadable
from www.aaon.com/controlstechsupport
•
Prism 2 software—downloadable from
www.aaon.com/prism
Hardware Specifications
Technical Data
LON
Loop
TP/FT-10 (78 Kps)
®
Orion Controller Loop
RS-485, 9600 Baud Rate
Network Protocol
LONWorks
Orion Controls Protocol
HSI Open Protocol Token Passing
Communications
Power Input Voltage
18-30 VAC
Power Consumption
10 VA Maximum
Operating Temp
-30°F to 150°F
Operating Humidity
0-95% RH Non-Condensing
Weight
4.7 oz.
Table 1: PT-Link II LON-3
The PT-Link II LON-3 Technical Guide
is located on the included flash drive
and can also be downloaded from www.
aaon.com/PTLink
Windows
10
®
®
®
Technical Data
®