Download Print this page
AAON PT-Link II LON-3 Installation Sheet

AAON PT-Link II LON-3 Installation Sheet

Advertisement

Quick Links

ASM01883
PT-Link II LON-3
Installation Sheet
Includes: PT-Link II LON-3
(3) Self-drilling 8 x 1" Hex Head Screws, PT-Link II Flash Drive
PT-Link II LON-3
®
The PT-Link II LON-3
, provides bi-directional communication between
®
ONE* of the following types of Orion controllers—VCCX2, VCC-X,
VCB-X, VCM-X, SA, VCM, MUA II, or VAV/CAV:
VCCX2 Controller (SS1088)
VCC-X Controller (SS1079)
VCB-X Controller (SS1051)
VCM-X Controller (SS1026, SS1030, SS1032, SS1033,
SS1034, Y200920)
SA Controller (Y200921)
VCM Controller (SS1016, Y200409, Y200616, Y200822)
VAV/CAV Controller (SS1003, Y200301) and
MUA II Controller (SS1004, Y200405)
To determine what controller you have, you must look at the software
label located on the controller.
EPROM on older devices. If the controller label does not match any of
the SS or Y numbers listed above, your controller will not work with
the PT-Link II LON
.
®
*NOTE: The PT-Link II LON
only one Orion controller. If more than one Orion control-
ler is present in a system, each one will require a PT-Link
II LON
device for integration with a LON
®
network.
Data Sharing and Scheduling
Provides values from points on the Orion side of the
gateway to LON
devices as if the values were
®
originating from LON
Allows LON
devices to modify point values on the
®
Orion controller side of the PT-Link II LON
standard LON
write services.
®
Controller, 10 Foot CAT5e Crossover Cable,
®
Overview
The label is located on the
NOTE:
device can be used to connect to
®
protocol
®
objects.
®
by using
®
®
System Requirements
Computer running Microsoft
operating system.
Ethernet Crossover Cable (supplied).
PT-Link LON
and RUINET software—
®
included on flash drive and also downloadable
from www.aaon.com/controlstechsupport
Prism 2 software—downloadable from
www.aaon.com/prism
Hardware Specifications
Technical Data
LON
Loop
TP/FT-10 (78 Kps)
®
Orion Controller Loop
RS-485, 9600 Baud Rate
Network Protocol
LONWorks
Orion Controls Protocol
HSI Open Protocol Token Passing
Communications
Power Input Voltage
18-30 VAC
Power Consumption
10 VA Maximum
Operating Temp
-30°F to 150°F
Operating Humidity
0-95% RH Non-Condensing
Weight
4.7 oz.
Table 1: PT-Link II LON-3
The PT-Link II LON-3 Technical Guide
is located on the included flash drive
and can also be downloaded from www.
aaon.com/PTLink
Windows
10
®
®
®
Technical Data
®

Advertisement

loading

Summary of Contents for AAON PT-Link II LON-3

  • Page 1 Technical Data ® Data Sharing and Scheduling • Provides values from points on the Orion side of the The PT-Link II LON-3 Technical Guide gateway to LON devices as if the values were ® is located on the included flash drive originating from LON objects.
  • Page 2 Power up the PT-Link II LON-3 with an appropriately sized ® The following steps are a quick means to get the PT-Link II LON-3 ® isolated 24 VAC power. (Note that the Unit Controller operational for many simple installations. This quick start depends on should already be powered up and running).
  • Page 3 Connections and Wiring Figure 2: PT-Link II LON-3 Interface Wiring to Unit Controller (VCCX2 Shown) ®...
  • Page 4 Windows is a registered trademark of Microsoft Corporation. ® 8500 NW River Park Drive • Parkville, MO • 64152 Ph: (816) 505-1100 • Fax: (816) 505-1101 ASM01883-INSTL-01A Printed in the USA • © April 2020 AAON • All Rights Reserved...

This manual is also suitable for: