Contents General Information ................6 Introduction ......................6 Purpose of User Manual ..................6 Warning and Safety instructions ................6 Components ......................7 Transport and Storage ....................8 Assembly .....................11 Assembly Area .....................11 Module Combination ....................12 Installation of Weather Protection Sheets ...............14 Ball Siphon Assembly ...................14 Removing of the Fan Fixing Parts..................
Page 3
Commissioning ...................25 Starting Device .....................26 Display Control ....................... 26 Parameter Change ......................27 Operating Mode ......................28 Temperature ........................30 Air Flow Control ......................31 Time Setting ........................32 Admin Settings ....................... 34 Service and Maintenance ..............35 Service Maintenance Information ..................35 Maintenance Plan ....................35 Component Maintenance ....................
Repairs and modifications to be made on the product can be made by AERA Technical service personnel or expert personnel approved by AERA, unless they are marked as the user in the maintenance plans. In case of need for spare parts, please contact the after-sales service department.
DANGER DANGER Death / serious irreversible injury Indicates an extremely dangerous situation that will result in death or serious irreversible injury if the safety instructions are not followed. WARNING WARNING Death / Serious injury Indicates an extremely dangerous situation that will result in death or serious irreversible injury if the safety instructions are not followed.
Transport and Storage DANGER Do not stand under/near suspended loads while transporting air handling unit modules. ATTENTION The unit must never be lifted, pulled or pushed using any protruding parts other than the main frame, such as coils, dampers. ATTENTION The unit must not be tilted during transport or lifting.
Page 7
ATTENTION If a forklift is used during transportation, make sure that the forklift blades pass through the bottom of the units. Otherwise, it may damage the panels at the bottom of the units. Forklift blades must be long enough to pass through the module completely! ATTENTION If the units are lifted with a forklift, the lifting operation should be carried out by considering the center of gravity of the module and making sure that the load is evenly distributed on the forklift forks.
Page 8
30mm (standard) or 60mm (optional part) diameter holes on both sides of the pedestal. In crane operations, the connection details shown below should be considered and applied completely. AERA is not responsible for any damage that may occur otherwise. Sample Application for Lifting from Pedestal...
Air handling units can wait for the time of assembly at construction sites or warehouses. In such storage situations, the warnings below should be taken into account. • In order to avoid pollution, all gaps in the air handling unit must be covered. If stored in a wet environment, sufficient ventilation should be provided.
In order to take out the components for reasons such as cleaning, maintenance and replacement, While locating the unit, gaps of appropriate sizes should be left around the unit. This space should be on the service side of the unit and at least 1.2 times the width of the unit.
Page 11
ATTENTION The pedestal under the modules must be used to bring the modules close enough to each other! Fix a suitable tensioning strap to the pedestal and tighten the tensioning strap for this task. Make sure the modules get close enough with the base. ATTENTION Assembling with the tensioning strap should be done using only pedestal.
ATTENTION Correct installation of the siphon is the responsibility of the client / contractor. AERA is not responsible for The side connected to the drain pan outlet. damages that may arise due to incorrect connection.
The sheets must be removed before the fans are operated. ATTENTION The units may be damaged if operated without the fixing sheet of fan Insulators removed. AERA is not responsible for any damages that may occur due to the failure to remove the sheets.
ATTENTION Duct connection supports should not be connected to the unit frame. Using the unit frame as support equipment may cause panel damage! AERA is not responsible for any damages that may occur in such cases. Air Duct...
Page 15
ATTENTION Care should be taken when connecting ducts to the dampers in the openings of the device to the outside. If the screws get stuck in the gear of the damper mechanism, the damper will not work. Therefore, the following points should be considered in the duct mounting to be made on dampers. •...
Connection of Run Around Heat Recovery System In air handling units with a coil heat recovery system, the connection between the coils should be made in the construction site and in accordance with the diagram below. Air Bleeding Valve Frost Protection Sensor Expansion tank Refill Set...
Page 17
Torsions that will occur if it is not tightened by making contra may make the coil unusable! AERA is not responsible for any damage that may occur as a result of non-contra connec- tions! All pipes of installation and coil connection must be insulated.
The refrigerant inlet and outlet lines of the direct expansion coil are labelled on the unit, it is important to pay attention to these labels during assembly. Connection of DX coil with AHUKIT and VRF outdoor unit should be made by AERA technical service or authorized personel.
DANGER The electrical connection of the unit should only be made by qualified electricians. DANGER Before all electrical assembly operations, the main supply panel must be de- energized and it must be ensured that it will not be energized accidentally. 3.11 External Sensors If sensors such as humidity, air quality, smoke etc.
CAUTION Documents containing electrical and automation details of the air handling unit are attached to the automation panel or the module with the accessories. All electrical connections must be made according to this document. 3.12.1.1 Control Panel and BMS Connection Air handling units that are requested with automation equipment can be integrated with the building automation system via Modbus TCP-IP / Bacnet protocols and can be monitored with these protocols.
Depending on the project variation, the air handling unit may have different component selections. In units where there is no automation panel, electrical connections have been moved to junction boxes placed outside the device. In order to reduce the starting current in motors above 4kW, “star-delta” motor connection is made. 3.12.2.1 Panel Assembly In air handling units ordered with automation, the panel may not be mounted on the device by special request.
For voltage unbalance; Voltage balance =100A/2Vort For example, if the measured voltages are 221.230 and 227, the average voltage will be 226V. A=(226-221)+(230-226)+(227-226) CAUTION The electrical connections of the air handling unit are carried out of the device with materials such as junction boxes, coupling, etc. Unless there is special instruction, holes, slots, etc. should not be drilled into the air handling unit.
If there is a problem with even one of the above items, the unit should not be operated ! If the error cannot be resolved by the user, AERA Technical Service should be contacted! If all the items in the list above are suitable, the device can be powered for the first time.
Do the power and current values drawn by the device match the unit label (+ - 5%)? If there is a problem in even one of the above items, the power plant should be stopped immediately and AERA Technical Service should be contacted! Starting Device 4.1.1 Display Control...
4.1.2 Change Parameters In some menus there are parameters that can be set. This is indicated by the yellow LED with flashing. A quick blinking (2 times/s) indicates that the parameter can be changed using the present user access. A slower blinking (1 time/s) indicates that a higher user access is required to change the parameter.
4.1.3 Running Mode Open Main Menu Click arrow down one time. → Ru nn i n g m o d e → R un ni ng m od e Au to T em pe ra tu re A ir c on tr ol T im e se tt in g s Click to right...
Page 27
Click arrow down three times and right arrow one time. Select AI and click Select DO and right arrow one time. click right arrow one time. AI1: 18.5 Outd temp DO1: Off SAF 1/1-speed AI2: 20.3 Supply temp DO2: Off EAF 1/1-speed AI3: 28.2 Frost prot DO3: Off SAF 1/2-speed AI4: 19.9 Room temp1...
4.1.4 Temperature Open Main Menu Click down arrow two times. R u n n i n g m o d e → T e m p e r a t u r e A i r c o n t r o l T i m e s e t t i n g s Click right arrow one time.
Supply air temp Setp: 22.0°C Click right arrow one time. Setpoint offset if reduced speed 0.0°C Submenus: Click arrow down one time. Setpoint Neutral zone 0.0°C 4.1.5 Air Control Flow control adjust point. The real points can be visible with the set points in the screen. This menu can not be changeable just for Open Main Menu observation...
4.1.6 Time Settings Open Main Menu Click arrow down four times. T em pe ra tu re A ir c on tr ol → T im e se tt in g s M an ua l/ Au to Click right arrow one time. →...
Page 31
T im e: 0 8: 18 D at e: 2 02 1- 0 9-01 Click right arrow one time. W ee kd ay : We dn esday Time is shown in 24-hour format. Date is shown in YY-MM-DD. H ol id ay s (m m :dd) Click down arrow five times 01 -0 1...
4.1.7 Access Rights In this menu it is possible to log on to any access level by entering the appropriate 4-digit code. The log on menu will also be displayed should you try to gain access to a menu or try to do an operation requiring Open Main Menu higher authority than you have.
Before contacting the technical service, make sure that you have the following information at hand so that any errors that may occur can be rectified as soon as possible: • Unit delivery date • AERA order number • Product name and label information • Brief description of the error •...
Cleaning If it is damaged, it should be re- Damage and Corrosion paired / replaced. Battary plumbing damage / If it is damaged, it should be re- corrosion paired / replaced. Cleaning Electric If it is damaged, it should be re- heater Damage and Corrosion paired / replaced.
5.3.1 Filter maintenance DANGER Before any maintenance and installation work or opening the enclosure, the unit must be completely isolated from the mains power supply! Filter fixing systems in EVO-M series units are offered to users in 2 types. Replacement of Slide Filters: •...
CAUTION After the clamping wires are loosened, the filters may fall out of their casing. The last wire should be loosened by supporting the filters. ATTENTION After the filters are removed, the sealing elements on the filter fixing mechanism should be checked. If there are any damaged ones, they should be replaced with new ones. 5.3.2 Heat Exchanger Maintenance and Cleaning 5.3.2.1 Rotary Heat Recovery Systems...
5.3.2.2 Plate Heat Exchanger Heat Recovery Systems ATTENTION The spray machine to be used for heat exchanger cleaning should be at low pressure. Cleaning with high pressure machines can damage the fins and make the heat exchanger unusable. • Loosen wing fasteners and remove service panel. •...
If there is even the slightest movement on the fan, never open the fan door! DANGER Fans are components that cannot be taken out of the unit due to their nature (Except for units with sliding fan structure produced on special request). For this reason, no intervention should be made by the user, except for general controls about the service.
These units may cause the silencer lining to laceration and the silencer to become unusable! If there is a damaged silencer, AERA Technical Service should be contacted for spare parts. 5.3.8 Condensation Pan Maintenance and Cleaning Condensation pans are maintenance-free materials.
The interior and exterior surfaces of the switchboard should be checked within the period specified in the maintenance plan. Regarding the negativities detected because of the control, the “Problem Solving” section should be examined first, and if the problem cannot be solved, the AERA Technical Team should be contacted. Control points are as follows. •...
Page 41
ELECTRIC HEATER HIGH Electric heater high-temperature failure. Check if there is air TEMPERATURE flow. Check heater wiring connections. Cut off the power and check the heater. FREEZING RISK Freeze alert. LOW FREEZING The value from the freezing temperature sensor is below the TEMPERATURE specified limit.
Page 42
CO2 SENSOR ERROR Check the relevant sensor connections. ROOM HUMIDITY SENSOR Check the relevant sensor connections. ERROR MOISTURE PIPES SENSOR Check the relevant sensor connections. ERROR EXTRA UNIT TEMPERATURE Check the relevant sensor connections. SENSOR ERROR EXTERNAL CONTROL SAF Check the relevant sensor connections. SENSOR FAILURE EXTERNAL CONTROL EAF Check the relevant sensor connections.
Page 43
FILTER PROTECTION 2 Check if the filter on the return side is dirty. ERROR EXTRA SENSOR HIGH Check the place where the extra sensor is located. TEMPERATURE 1 EXTRA SENSOR LOW Check the place where the extra sensor is located. TEMPERATURE 1 EXTRA SENSOR HIGH Check the place where the extra sensor is located.
Duct sections, small for the Check the duct size and revise if application necessary. Fan too small for the applica- Contact the AERA Technical Team. High air velocity tion Serpentine with the insufficient Contact the AERA Technical Team. front surface...
Page 45
There is no power supply to Check terminals and contactors, the motor correct if necessary. Thermal burnout Contact the AERA Technical Team. In the air handling units, no airflow/mo- Control panel error System connections are checked. tor not running Main switch off Turn on the main switch.
Page 46
FAULT SYMPTOM POSSIBLE CAUSE SOLUTION Low fan k factor value (in auto- Correct the K-factor value (in auto- mation units) mation units) High Airflow External pressure loss less than Lower the fan speed. the design value Excessive Doors do not close properly/ Check the door gaskets and re- leakage on the fallen...
Page 47
POSSIBLE CAUSE SOLUTION No electricity Locate and repair the error. There is no Contactor is faulty Contact the AERA Technical Team. power in the The safety thermostat shut Check the safety thermostat, make controller. down the system. sure there is airflow. Reset the Electric heater - thermostat.
Page 48
There may be water leakage Turn off the water connections, in the water coils inside the air check the coil. Contact AERA handling unit. Technical Team in case of damage The drain pan is full.
After-Sales Services AIn the AERA EVO-M air handling units, there is no part replacement or repair work to be done by the user, except for cleaning and eye control. Users should contact the AERA company for any malfunctions detected during commission- ing or maintenance.
Need help?
Do you have a question about the EVO-MODULAR and is the answer not in the manual?
Questions and answers