Operating manual SCS-1002 TABLE OF CONTENTS DESCRIPTION AND OPERATION OF THE SYSTEM ........4 ’ 1.1 T ..................... 4 YSTEM S PURPOSE 1.2 T ..................4 ECHNICAL SPECIFICATIONS ’ 1.3 T ..................4 YSTEM S COMPOSITION 1.4 S ............10...
Page 3
SCS-1002 This operating manual describes Hospital and refrigerator alarm system SCS-1002 (hereinafter referred to as the System) and any options of its composition. This operating manual describes composition, structure, operation, specifications of the System and its components, instructions for the correct and safe operation of the System (intended use, technical service, current repair, storage and transportation), and disposal instructions for the System components.
Operating manual SCS-1002 DESCRIPTION AND OPERATION OF THE SYSTEM ’ 1.1 T YSTEM S PURPOSE The System provides call signaling to the watch station from the calling stations, located in the refrigerator chambers, ship’s hospital and other areas where restricted mobility or life threat occur.
Page 5
Hospital and refrigerator alarm system SCS-1002 Table 2 – The list of the SCs Name Description Reception and control device SCS-SPS-5 To ensure light and sound call signaling, display number Mounting type: SCS-SPS-5 and name of a controller. 5 controlled devices...
Page 6
Operating manual SCS-1002 Name Description SCS-KP-6 To split power network and line to 6 outputs Relay unit RB-139 To provide power supply to signaling units with control signal. Power supply RB-139-24 24 V DC To provide power supply to signaling units with control signal. Power supply...
Page 7
Hospital and refrigerator alarm system SCS-1002 Name Description Rotating flashing lamp RFL-24 Dome colour: RFL-24-G green Dome colour: RFL-24-B blue To repeat a call with light signaling, flashing. Power supply 24 V DC Dome colour: RFL-24-R Dome colour: RFL-24-О orange...
Page 8
Operating manual SCS-1002 Name Description Light signaling unit L-24 Dome colour: L-24-W white Dome colour: L-24-G green Dome colour: To repeat a call with light signaling. Power supply 24 V DC L-24-B blue Dome colour: L-24-R Dome colour: L-24-О orange...
Page 9
Hospital and refrigerator alarm system SCS-1002 Name Description Light signaling unit PGS-VSPYSHKA-220 Dome colours: white Dome colours: green To repeat a call with light signaling, explosion-proof. Dome colours: PGS-VSPYSHKA-220 Power supply 220 V AC, frequency 50 Hz blue Dome colours:...
Operating manual SCS-1002 1.4 S TRUCTURE AND OPERATION OF THE YSTEM The System is a hardware and software unit that includes the SCs described in 1.3. The System sends a call from controllers of call buttons to the central unit (main reception and control device) or repeater providing actuation of light and sound signaling and displaying the address of the controller.
Page 11
Hospital and refrigerator alarm system SCS-1002 The System operates in the following order: а) a user initiates a call on a call button, the call is received at the watch officer station and backup station (controllers or reception and control devices) where it actuates local alarm signaling;...
Page 12
Operating manual SCS-1002 Place of the System use To control rooms Code Ship hospital rooms and from watch As a call bell system refrigerated holds officer station PGS-VSPYSHKA-24, PGS-VSPYSHKA-220, Orbita MK S, Orbita MK Z, Orbita MK ZS, BExS110DFDC024AS1A1G, BExS110DFAC230AS1A1G SCS-КР-2...
Hospital and refrigerator alarm system SCS-1002 Figure 2 – The System’s structure used to call a watch officer Figure 3 – The System’s structure used as a call bell system 1.5 M EASUREMENT TOOLS INSTRUMENTS AND APPLIANCES Consumables and instruments required for the TS are represented in tables 4 and 5.
Operating manual SCS-1002 Table 5 – Consumables required for the TS Name and identifier Amount of Purpose of consumables consumables 1 To clean surfaces of the SC use clean cloth. 2 To remove severe contamination – use cloth soaked in Cleaning cloth 0.1 kg...
Hospital and refrigerator alarm system SCS-1002 2 DESCRIPTION AND OPERATION OF THE SYSTEM COMPONENTS 2.1 R ECEPTION AND CONTROL DEVICES 2.1.1 Reception and control devices SCS-SPS type Functionality of RCD of SCS-SPS type: a) controls signals from controllers of call buttons in RS-485 network or via four- wire communication line;...
Page 16
Operating manual SCS-1002 Figure 4 – Exterior of SCS-SPS-5 Table 6 – Controls and LEDs of SCS-SPS-5 Pos. Name Description display status controllers (operation, fault, Controllers status LEDs communication line failure) Plastic slots To put inserts with a name of station...
Page 17
Hospital and refrigerator alarm system SCS-1002 Table 7 – Timer settings of signaling delay Position of DIP-switch Signaling delay, sec Position of DIP-switch Signaling delay, sec – – 2.1.2 Reception and control devices SCS-CU type Functionality of RCD, SCS-CU type: a) to control signals from controllers of call buttons in RS-485 network;...
Page 18
Operating manual SCS-1002 Figure 5 – Exterior of SCS-CU Table 8 – Controls and LEDs of SCS-CU Pos. Name Description To display names of controllers, to control and provide settings of RCD Navigation keys To navigate in the menu Power on (off) button...
Page 19
Hospital and refrigerator alarm system SCS-1002 Each area of the screen may operate in one of the following modes or their combination: – no call (normal); – call receipt; – no connection with a controller; – faulty call buttons or faulty communication channels with a call button.
Operating manual SCS-1002 Figure 7 – Exterior of SCS-WP Table 9 – Controls and LEDs of SCS-WP Pos. Name Description Brightness knob To adjust brightness of controls Reset button To provide temporary mute of sound signaling Speaker To provide sound call signaling...
Page 21
Hospital and refrigerator alarm system SCS-1002 There are two types of controllers: а) for internal ship rooms – SCS-CH; b) for refrigerating rooms – SCS-REF. Functionality of controllers: а) to initiate a call from a local call button (SCS-REF) or connected to a controller of call buttons (SCS-CH);...
Operating manual SCS-1002 2.2.2 Controllers of call buttons SCS-REF To make a call, press Call button located on the controller. For the exterior of the unit, see figure 9. For the description and assignment of controls and LEDs, see table 11.
Page 23
Hospital and refrigerator alarm system SCS-1002 Table 12 – Brief specifications of call buttons Call button Control of external Code Note Call Reset signaling unit code – – SCS-CH-PB IP22 – – SCS-BPT IP56 Heatproof – SCS-BPC IP56 Momentary push-button...
Operating manual SCS-1002 3 INTENDED USE 3.1 O PERATIONAL LIMITATIONS Connect the System components in compliance with connection diagrams in Appendix A, and table of connections issued for the order. All SCs must be grounded, insulation of cables must be intact, bare ends shall be absent.
Page 25
Hospital and refrigerator alarm system SCS-1002 All SCs start operation automatically once the power is supplied. To power the SCs, firstly, turn on a circuit breaker on the main switchboard, then, transfer a power button to ON position – on SCS-SPS, or press Power button – on SCS-CU, if it is not active.
Page 26
Operating manual SCS-1002 DIP-switch SW2 Address DIP:5 DIP:4 DIP:3 DIP:2 DIP:1 Notes 1 “0” means that corresponding DIP-switch is in OFF position, “1” – in ON position. 2 Switches DIP:6, DIP:7, DIP:8 are not used. Note – The System settings may be performed at the Manufacturer’s plant, if the System is delivered according to the technical design assignment of the customer or design company.
Hospital and refrigerator alarm system SCS-1002 powered up. Use power switch on the front panel of SCS-SPS-5, SCS-SPS-10 to start their operation. Table 14 – Specifications of the recommended cables Max. cable Max. frequency, Environment temperature of Cable purpose cable operation, °С...
Page 28
Operating manual SCS-1002 3 Call reset performed on a repeater SCS-CU-REP does not have an effect on signaling on RCD (see operation description of the SCs in mute mode in 2.1 and 2.1.4). To reset a call, act as follows: –...
Page 29
Hospital and refrigerator alarm system SCS-1002 3.3.3 Test of indication and alarm To test operation of indication and alarm, press and hold a brightness key for more than 5 sec. Once the test starts, backlight brightness of controls and display will change from the maximum level to minimum, and vice versa;...
Operating manual SCS-1002 4 TECHNICAL SERVICE 4.1 G ENERAL INSTRUCTIONS The System’s TS shall be performed by the staff familiarized with its composition, structure and operational features. In order to provide safe and reliable operation of the System, the staff shall maintain the following types of TS: ...
Page 31
Hospital and refrigerator alarm system SCS-1002 Table 16 – CL № 1. Exterior inspection of the SC Man-hours per To be done Routine 1 SC Check exterior of the SC, mechanical damage; paint defects must be absent; legends are to be read easily.
Operating manual SCS-1002 4.4 I SPTA NSTRUCTIONS ON Portable SPTA kit is delivered together with the System. It is used to maintain operation of the System and replace faulty elements during operation. Composition of portable SPTA kit shall comply with the SPTA kit list.
Hospital and refrigerator alarm system SCS-1002 5 CURRENT REPAIR OF THE SYSTEM 5.1 G ENERAL INSTRUCTIONS To provide fault diagnostics of the System, use information in table 19. If you cannot diagnose the fault, please, contact the Manufacturer’s service center.
Operating manual SCS-1002 6 STORAGE The System must be stored in the packaging inside the areas complying with the required storage conditions (+ 5 °С to + 40 °С) with the concentration of dust, oil, moisture and aggressive impurities in the air within the required limits for the working areas of production facilities.
Hospital and refrigerator alarm system SCS-1002 7 TRANSPORTATION The System must be transported in the Manufacturer's transportation package in closed means of transport. Types of shipment: a) motor vehicle and railroad transportation in closed means of transport (covered cars, multipurpose containers) b) air transportation (in sealed and heated compartments);...
Operating manual SCS-1002 8 DISPOSAL Packaging material, SC damaged during operation of the System, and any overage equipment must not be disposed as standard household wastes, since they contain the materials suitable for re-use. Decommissioned and non-used components of the System must be delivered to a special waste disposal center licensed by local authorities.
OM. The Manufacturer will not consider damage claims in case of case violation of operating conditions. More information about warranty terms you can find on the official website of NPK MSA, LLC, section Support. Address and contacts of the Manufacturer's service centre: NPK MSA, LLC 26E, Kibalchicha str., 192174, St Petersburg, Russia...
Operating manual SCS-1002 APPENDIX A CONNECTION OF THE SYSTEM COMPONENTS Figure А.1 – Connection of SCS-SPS-5, SCS-KP-6, SCS-REF, FL-24 Note – The System may include junction boxes SCS-KP-2 or SCS-KP-6 from the System’s scope of delivery and third party junction boxes that split cables to several outputs.
Page 39
Hospital and refrigerator alarm system SCS-1002 Figure А.2 – Connection of SCS-CH-PB, SCS-CH-PB-Ех and SCS-BPT to controller SCS-WP, and signaling device with power supply 220 V to SCS-REF. Figure А.3 – Connection of SCS-WP, power supply unit PS-103 and call button SCS-SC-DC Figure А.4 –...
Page 40
Operating manual SCS-1002 Figure А.5 – Connection of several SCS-SPS-5 by means of SCS-KP-6 Version 0.2...
Page 41
Hospital and refrigerator alarm system SCS-1002 Figure А.6 – Connection of SCS-SPS-5, SCS-CU, SCS-CU-REP, controller SCS-WP, call buttons SCS-CH-PB, SCS-SH-DC, signaling device FL-24 Version 0.2...
Page 42
Operating manual SCS-1002 Figure А.7 – Connection of SCS-SPS-10, SCS-CU-REP, PS-103, call buttons SCS-CH- PB and controller SCS-WP by means of junction box SCS-KP-6 Version 0.2...
Page 43
Hospital and refrigerator alarm system SCS-1002 Figure А.8 – Connection of SCS-SPS-10, SCS-CU, PS-103, signaling devices with power supply 24 V, call buttons SCS-CH-PB and SCS-CH-EPB by means of junction box SCS-KP-2 Version 0.2...
Page 44
Operating manual SCS-1002 Figure А.9 – Connection of flashing lamp RL-24 and RL-220 types Figure А.10 – Connection of flashing lamp RFL-24 and RFL-220 types Figure А.11 – Connection of signaling devices L-24 and L-220 types Version 0.2...
Page 45
Hospital and refrigerator alarm system SCS-1002 Figure А.12 – Connection of light signaling unit Orbita MK S, Orbita MK Z and Orbita MK SZ Figure А.13 – Connection of sound signaling units BExS110DFDC024AS1A1G, BExS110DFAC230AS1A1G Version 0.2...
Page 46
Operating manual SCS-1002 Figure А.14 – Connection of light signaling units PGS-VSPYSHKA-24, PGS- VSPYSHKA-220 Version 0.2...
Hospital and refrigerator alarm system SCS-1002 APPENDIX B DESCRIPTION AND PURPOSE OF THE SYSTEM COMPONENTS SCS-SPS-5 (wall mounting: w/casing) SCS-SPS-5 (panel mounting: w/o casing) SCS-SPS-5 (waterproof) Version 0.2...
Page 48
Operating manual SCS-1002 Reception and control device SCS-SPS-5 Description: Technical specifications: input voltage: 24 V DC; the unit ensures sound and light signaling of a power consumption: max. 15 W; call initiated by a controller. communication method: Features: ...
Page 49
Hospital and refrigerator alarm system SCS-1002 SCS-SPS-10 (wall mounting: w/casing) SCS-SPS-10 (panel mounting: w/o casing) Reception and control device SCS-SPS-10 Description: Technical specifications: input voltage: 24 V DC; the unit ensures sound and light signaling of power consumption: max. 15 W;...
Page 50
Operating manual SCS-1002 SCS-CU-PM SCS-CU-WM Version 0.2...
Page 51
Hospital and refrigerator alarm system SCS-1002 SCS-CU-WM (waterproof) Reception and control device SCS-CU Description: Technical specifications: input voltage: 24 V DC; the central unit ensures sound and light power consumption: max. 5 W; signaling of a call initiated by a controller of ...
Page 52
Operating manual SCS-1002 SCS-CU-REP-PM SCS-CU-REP-WM Version 0.2...
Page 53
Hospital and refrigerator alarm system SCS-1002 Central unit repeater SCS-CU-REP Description: Technical specifications: input voltage: 24 V DC; the unit repeats call signaling from a controller of max. power consumption: 5 W; call buttons. communication method: RS-485 network;...
Page 54
Operating manual SCS-1002 Reception and control device SCS-WP Description: Technical specifications: input voltage: 24 V DC; the unit ensures sound and light signaling of a max. power consumption: 1 W; call from a remote call button. controlled units: 1;...
Page 55
Hospital and refrigerator alarm system SCS-1002 Controller of call buttons SCS-REF Description: Technical specifications: input voltage: 24 V DC; the unit ensures call signaling. max. power consumption: 2 W; Features: communication method with RCD: RS-485 installation in refrigerated holds;...
Page 56
Operating manual SCS-1002 Controller of call buttons SCS-CH Description: Technical specifications: input voltage: 24 V DC; the unit ensures call signaling initiated by an max. power consumption: 2 W; external call button (SCS-CH-PB, SCS-BPT or communication method with RCD: network SCS-SC-DC).
Page 57
Hospital and refrigerator alarm system SCS-1002 Call button SCS-CH-PB Description: Technical specifications: operating temperature: −15 °С to +55 °С; The unit sends a call to a controller of call protection degree: IP22; buttons. weight: 0.38 kg. Features: ...
Page 58
Operating manual SCS-1002 Call button SCS-BPT Description: Technical specifications: operating temperature: −40 °С to +125 °С; the unit sends a call to a controller of call protection degree: IP56; buttons. weight: 0.4 kg. Features: connection of an external call button via Mounting type: ...
Page 59
Hospital and refrigerator alarm system SCS-1002 Call button SCS-SC-DC Description: Technical specifications: operating temperature: −40 °С to +55 °С; The unit initiates a call and resets it via four- protection degree: IP56; wire communication line. weight: 0.58 kg.
Page 61
Hospital and refrigerator alarm system SCS-1002 Call button SCS-BPC Description: Technical specifications: connected alarm units: 1; the unit temporarily switches on a signaling input voltage: device. 24 V DC; Features: 220 V AC frequency 50 Hz;...
Page 62
Operating manual SCS-1002 Call button SCS-SH-DC Description: Technical specifications: operating temperature: −15 °С to +55 °С; the unit repeats a call from an external call protection degree: IP22; button, and controls signaling units. weight: 0.65 kg. Features: ...
Page 63
Hospital and refrigerator alarm system SCS-1002 Call button SCS-CH-EPB Description: Technical specifications: operating temperature: −40 °С to +55 °С; unit sends call four-wire protection degree: IP56; communication line. weight (w/cable): 0.31 kg. Features: used with call button SCS-CH-PB;...
Page 64
Operating manual SCS-1002 Junction box SCS-KP-2 Description: Technical specifications: switching current: the unit connects two additional devices to RS- power circuits: 15 А; 485 network; outfitted with terminals to power the signaling circuits: 2 А; connected SCs.
Page 65
Hospital and refrigerator alarm system SCS-1002 SCS-KP-6 (IP22 type) SCS-KP-6 (IP56 type) Version 0.2...
Page 66
Operating manual SCS-1002 Junction box SCS-KP-6 Description: Technical specifications: switching current: the unit connects six additional devices power circuits: 15 А; to RS-485 network; outfitted with signaling circuits: 2 А; terminals to power the connected SCs. max. switching voltage: 250 V;...
Page 67
Hospital and refrigerator alarm system SCS-1002 Relay unit RB-139-24, RB-139-220 Description: Technical specifications input voltage: the unit switches external power to the connected RB-139-220: 220 V AC frequency 50 Hz; devices with control signal. Light and sound RB-139-24: 24 V DC;...
Page 68
Operating manual SCS-1002 Rotating lamp RL-24, RL-220 Description: Technical specifications input voltage: the unit ensures light call signaling in noisy RL-24: 24 V DC; environment. RL-220: 220 V AC frequency 50 Hz; Features: power: delivered with a bracket and 3 m cable;...
Page 69
Hospital and refrigerator alarm system SCS-1002 Flashing lamp FL-24 Description: Technical specifications: input voltage: 18 to 36 V DC; the unit ensures light call signaling in noisy power consumption: 3 W; environment. flashing rate: 75 times per minute;...
Page 70
Operating manual SCS-1002 Rotating flashing lamp RFL-24, RFL-220 Description: Technical specifications: input voltage: the unit ensures light call signaling on open deck RFL-24: 24 V; and in noisy environment. RFL-220: 220 V; Features: power: dome colours: ...
Page 71
Hospital and refrigerator alarm system SCS-1002 Sound signaling unit A-24, A-220 Description: Technical specifications: casing material: plastic, impact-resistant; the unit ensures sound call signaling in noisy power consumption: environment. A-24: 0.6 W; Features: A-220: 3.0 W;...
Page 72
Operating manual SCS-1002 Sound and light signaling unit AL-24, AL-220 Description: Technical specifications: casing material: plastic, impact-resistant; the unit ensures sound and light call signaling in power: noisy environment. AL-24: 6.6 W; Features: AL-220: 11.0 W;...
Page 73
Hospital and refrigerator alarm system SCS-1002 Light signaling unit L-24, L-220 Description: Technical specifications: casing material: plastic, impact-resistant; the unit ensures light call signaling in noisy power: environment and on open deck. L-24: 7.5 W; Features: L-220: 8.5 W;...
Page 74
Operating manual SCS-1002 Light signaling unit PGS-VSPYSHKA Description: Technical specifications: power: 14 W; the unit ensures light call signaling in input voltage: explosion-hazardous areas. PGS-VSPYSHKA-24: 24 V DC; Features: PGS-VSPYSHKA-220: 220 V AC frequency connection through cable gland or conduit;...
Page 75
Hospital and refrigerator alarm system SCS-1002 Light signaling unit ORBITA MK S Description: Technical specifications: input voltage: 24 V DC; the unit ensures light call signaling in explosion- operating temperature: −40 °С to +55 °С; hazardous areas. protection degree: IP67;...
Page 76
Operating manual SCS-1002 Sound signaling unit ORBITA MK Z Description: Technical specifications: input voltage: 24 V DC; the unit ensures sound call signaling in operating temperature: −40 °С to +55 °С; explosion-hazardous areas. protection degree: IP67; Features: ...
Page 77
Hospital and refrigerator alarm system SCS-1002 Sound and light signaling unit ORBITA MK SZ Description: Technical specifications: input voltage: 24 V DC; the unit ensures sound and light call signaling in operating temperature: −40 °С … +55 °С;...
Page 78
Operating manual SCS-1002 Sound signaling unit BExS110 Description: Technical specifications: input voltage: the unit ensures sound call signaling in BExS110DFDC024AS1A1G: 24 V DC; explosion-hazardous areas. BExS110DFAC230AS1A1G: 220 V AC, 50 Hz; Features: operating temperature: −40 °С to +55 °С;...
Page 79
Hospital and refrigerator alarm system SCS-1002 Call button SCS-CH-PB-Ех Description: Technical specifications: input voltage: 24 V DC; the unit ensures a call in explosion-hazardous power consumption: max. 2 W; areas. operating temperature: −15 °С to +55 °С;...
Page 80
Operating manual SCS-1002 FOR NOTES Version 0.2...
Need help?
Do you have a question about the SCS-1002 and is the answer not in the manual?
Questions and answers