5-1-3. F1 Group - Input terminals ........27 Contents 5-1-4. F2 Group - Output terminals........29 5-1-5. F3 Group - Start and stop control ......31 Chapter 1 Inspection and safety orecautions........1 5-1-6. F4 Group - V/F control..........31 1‐1. Inspection after unpacking ..........1 5-1-7.
After purchasing, please check if its package is damaged due to careless transportation, and if the specifications and model of the product are consistent with your order 6-3-1. Harmonic effect............90 requirements. For any problem, please contact your local authorized TPG dealer or 6-3-2. Electromagnetic Interference and Installation directly contact this company.
Chapter 1 Inspection and safety precautions Chapter 1 Inspection and safety precautions Process Type Explanation do not incorrectly connect wires! Otherwise which may 1-2.Safety precautions cause damage to the driver! Safety precautions in this manual are divided into the following two categories: ★...
Page 5
Chapter 1 Inspection and safety precautions Chapter 1 Inspection and safety precautions Process Type Explanation Type Explanation ★ When the inverter is operating, you should avoid that objects fall into this unit.Otherwise cause damage to this unit! Output side with The inverter output is PWM wave, if the piezoresistor for piezoresistor or lightning protection or the capacitor for improving power...
Chapter 1 Inspection and safety precautions Chapter 1 Inspection and safety precautions Type Explanation 1-4.Scope of applications when the motor works in overheating occasions,a strong This inverter only applies to typical industrial three-phase AC asynchronous motor. ※ exhaust fan should be retrofitted or replace non-inverter This inverter can only be used in those occasions recognized by this company, an ※...
Power (KW) Three-phase 220V, 50/60Hz levels Single phase 220V ±10% Three-phase 380V,50/60Hz Voltage: ± 10% ;Frequency: ± 5% CA-203A Allowable fluctuation The voltage unbalance rate is less than 3% and the distortion rate meets the IEC61800-2 standard. CA-204A 0.75 0.75...
Page 8
Chapter 2 Standard specifications Chapter 2 Standard specifications Items Specifications Items Specifications Automatic voltage Automatically maintain a constant output voltage frequency, speed and other physical parameters. regulation (AVR) when the voltage of electricity grid changes Support 0.1-10kHz square signal output. Overvoltage protection, undervoltage protection, Keyboard/terminal/communication Running method...
Chapter 2 Standard specifications Items Specifications Chapter 3 Keyboard Below 1000m Altitude 3-1.Keyboard description Pollution degree Keyboard is used to operate CA SERIES frequency inverters, read status data and Product adopts safety adjust parameters. IEC61800-5-1:2007 standards. Product adopts EMC IEC61800-3:2005 standards.
Chapter 3 Keyboard Chapter 3 Keyboard 3-3.Description of operation panel keys Sign Name Function * Enter top menu parameter change status Parameter * Exit from function option change Setting/Exit Key * Return to status display menu from sub-menu or function option menu * Select circularly parameters under run or stop Shift Key interface;...
Chapter 3 Keyboard Chapter 3 Keyboard Fl i cker of the motor's nameplate before inverter operation, CA SERIES frequency inverter will ▲ ENTER ▲ match the standard motor parameters according to the nameplate parameters; the vector control method is highly dependent on motor parameters, in order to get good control performance, the accurate parameters of the controlled motor must be required ENTER Motor parameter auto tunning steps are as follows (Take asynchronous motor as an...
Chapter 4 Installation and commissioning Braking resistor (optional) Chapter 4 Installation and commissioning Circuit Contactor breaker Main 4-1.Operating environment circuit (1) ambient temperature -10 ~ 50. After more than 40 degrees Celsius, in accordance with the proportion of 1 to 3% degrees down the amount of. Inverter is not recommended in the environment above 50.
Chapter 4 Installation and commissioning Chapter 4 Installation and commissioning supply Maximum output current: 200mA When external signal is used to drive, please External unplug JP1 jumpers,PLC must be connected to 4-4.Main circuit terminal power input external power supply. Factory default and +24V terminal 4-4-1.
Chapter 4 Installation and commissioning Chapter 4 Installation and commissioning motor ※ Do not let metal chips or wire ends into inside the inverter when wiring,otherwise 4-8.Commissioning which may cause malfunction to the inverter. ※ Disconnect motor or switch power-frequency power supply only when the inverter Commission- stops output ※...
Chapter 5 Function parameter F8 Fault and protection group To set fault and protection parameters Chapter 5 Function parameter Communication parameter 5-1.Menu grouping To set MODBUS communication function group CA SERIES inverter function parameters are grouped by function, there is d0 FA Torque control group To set parameters under torque control mode group, F0 group to Fb group, E0 group to E3 group, b0 group, y0 group to y1 group, L0...
Page 16
Chapter 5 Function parameter Chapter 5 Function parameter Panel potentiometer Panel potentiometer setting 2: UP/DOWN setting is invalid 12. d0.11 0.01V ● voltage voltage value 3: Valid when running, invalid when stop 13. d0.12 Motor actual speed Motor actual running speed 1rpm ●...
Page 17
Chapter 5 Function parameter Chapter 5 Function parameter DI2 terminal 2: Reverse run setting 37. F1.01 ★ function selection 3: Three-wire operation control Filter time of AI1 4: Forward Jog 48. F1.12 0.00s to 10.00s 0.10s ☆ DI3 terminal input 5: Reverse Jog 38.
Chapter 5 Function parameter Chapter 5 Function parameter parameters BIT1: Set frequency 90. F4.03 V/F frequency point 1 0.00Hz to F4.05 0.00Hz ★ selection BIT2: Bus voltage 91. F4.04 V/F voltage point 1 0.0% to 100.0% 0.0% ★ BIT3: Output voltage BIT4: Output current 92.
Chapter 5 Function parameter Chapter 5 Function parameter Depends on action selection 1: Constant speed invalid 114. F7.04 Deceleration time 2 0.1 to 3600.0s ☆ models 0: OFF 0.00 to F0.08 (maximum 1: normal motor (with low Motor overload 115. F7.05 Jump frequency output 0.00Hz 127.
Page 21
Chapter 5 Function parameter Chapter 5 Function parameter 7: even parity (E, 7, 1) for ASCII setting 8: odd parity (O, 7, 1) for ASCII Note: Option 1 to 6, 100% 9: no parity (N, 7, 2) for ASCII relative to two times of the rated 10: even parity (E, 7, 2) for ASCII current of inverter 11: odd parity (O, 7, 2) for ASCII...
Chapter 5 Function parameter Chapter 5 Function parameter 5-1-14.E0 Group - Wobbulate control Factory No. Code Parameter name Setting range Change Factory default No. Code Parameter name Setting range Change default 0: Keyboard setting (E2.01) 0.0 to 100.0% (relative to 1: Analog channel AI1 setting 158.
Page 23
Chapter 5 Function parameter Chapter 5 Function parameter Units digit: VDO1 Factory Code Parameter name Setting range Change 0: positive logic default 1: negative logic 190. E3.00 VDI1 function selection 0 to 25 ★ Tens digit: VDO2 (same as units digit) 191.
Chapter 5 Function parameter Chapter 5 Function parameter Depends on Parameter 222. b0.10 Motor no-load current 0.01 to 655.35A ★ Parameter name Smallest unit models function code 0: no operation d0.00 Running frequency 0.01Hz 1: Motor parameters static Motor parameter auto 223.
Chapter 5 Function parameter Chapter 5 Function parameter 0: open-loop flux vector control: refers to that the open-loop flux vector control is Parameter Parameter name Smallest unit suitable for high-performance general-purpose applications where the encoder PG is function code not installed, an inverter can only drive one motor. Such as machine tools, centrifuges, wire drawing machines, injection molding machines and other loads.
Page 26
Chapter 5 Function parameter Chapter 5 Function parameter Keyboard command channel code by user. Panel potentiometer analog input voltage of 0V to 10V. Command source Terminal command channel F0.04 ★ 4: Analog AI1 + AI2 setting: refers to that the frequency is set by the analog input channel Communication command terminals.
Chapter 5 Function parameter Chapter 5 Function parameter The value should be less than or equal to the maximum output frequency. Carrier Electromagnetic Noise, leakage current Cooling degree Frequency noise Running frequency 0.00Hz to F0.10 (running F0.11 0.00Hz ☆ lower limit frequency upper limit) Large Small...
Page 28
Chapter 5 Function parameter Chapter 5 Function parameter 8: Free stop 8: Free stop: once command is enabled, the inverter immediately blocks output but 9: Fault reset can not control the process of motor stop, the mode is recommended for the application 10: External fault input of large inertia load and no requirement for stop time, the mode is same as the free stop 11: Frequency change...
Page 29
Chapter 5 Function parameter Chapter 5 Function parameter 25: Reserved Change rate of terminal 0.50Hz/ F1.07 0.01 to 50.00Hz/s ☆ UP/DOWN frequency increment Two-wire type control 1 When the terminal UP/DOWN is used to adjust the set frequency, the rate of frequency change, i.e.
Chapter 5 Function parameter Chapter 5 Function parameter Times of switching quantity F1.18 1 to 10 ☆ filtering Function Description value Set sampling filter time of DI1 to DI5 terminals. For the application that input No output The function of Output terminal is disabled. terminals are vulnerable to interference and cause the accidental operation, you can Inverter Run Forward: when the inverter Motor is running...
Page 31
Chapter 5 Function parameter Chapter 5 Function parameter output terminal opens and then disconnects. Running frequency 0 to maximum output frequency F2.13 Reserved Set frequency 0 to maximum output frequency DO output terminal active Output current 0 to 2 times of rated inverter current F2.14 0x00 to 0x1F ☆...
Chapter 5 Function parameter Chapter 5 Function parameter 5-2-5.F3 Group - Start and stop control group Waiting time of stop F3.07 0.0 to 50.0s 0.0 s ☆ braking Factory Code Parameter name Setting range Change default Stop DC braking F3.08 0.0 to 150.0% 0.0% ☆...
Chapter 5 Function parameter Chapter 5 Function parameter F4.05 V/F frequency point 2 F4.03 to F4.07 0.00Hz ★ Output voltage (V) F4.06 V/F voltage point 2 0.0% to 100.0% 0.0% ★ 1.25th power down torque V/F curv Linear type F4.05 to b0.04 (rated motor ★...
Chapter 5 Function parameter Chapter 5 Function parameter Factory F5.02 Switching low point frequency 0.00Hz to F5.05 5.00Hz ☆ Code Parameter name Setting range Change default F5.03 Speed loop proportional gain 2 0 to 100 ☆ Valid only for panel control F5.04 Speed loop integral time 2 0.01 to 10.00s 1.00 s...
Chapter 5 Function parameter Chapter 5 Function parameter BIT1: Bus voltage CA SERIES provides two sets of acceleration and deceleration time. Their BIT2: Input terminal status meanings are the same, please refer to the instructions on F0.05 and F0.06. BIT3: Output terminal status Use multi-function digital input terminal DI to set, switch between ac/deceleration BIT4: PID setting value 1 and ac/deceleration time 2.
Chapter 5 Function parameter Chapter 5 Function parameter Forward/reverse Depends on Output F7.08 0.0 to 3600.0s ☆ rotation deadband models frequency(f In the transition process of setting forward and reverse running of inverter, output FDT Hysteresis transition time at zero frequency. Time(t) Output frequency(f)
Page 37
Chapter 5 Function parameter Chapter 5 Function parameter not overload protection to load motor. current limiting 1: Ordinary motor (with low speed compensation) As the cooling effect of During the operation of Inverter, due to the load is too large, the actual rising rate ordinary motor at low speed gets worse, the corresponding electronic thermal of motor speed is lower than the rising rate of output frequency.If no measures taken, it protection value should be adjusted as appropriate, as mentioned here with low...
Page 38
Chapter 5 Function parameter Chapter 5 Function parameter When the master is in the write-frame, the communication address of the slave is point of momentary voltage) set to 0, that is the broadcasting communication address, all slaves on MODBUS will power failure accept the frame, but the slave does not respond.
Chapter 5 Function parameter Chapter 5 Function parameter both write and read commands. compensation When units digit of the function code LED is 1, the host computer of inverter responds high speed torque read command only, this way can improve communication efficiency. FA.03 0.000-1.000 0.000...
Page 40
Chapter 5 Function parameter Chapter 5 Function parameter Oscillation E0.00, when E0.00 is set to 0, the wobbulate will not work. suppression valid Output Fb.07 Oscillation suppression ☆ frequency Oscillation suppression invalid Wobbulate upper Sudden jump amplitude The oscillation suppression is for VF control, the current oscillation phenomena limit frequency Wobbulate often occurs when the ordinary motor runs with light load or no load, which can cause...
Page 41
Chapter 5 Function parameter Chapter 5 Function parameter 0.0% instruction 0 not only can select E1.00, there are a variety of other options too. it is E1.12 Multi-speed 12 -100.0% to 100.0% ☆ convenience to change the multistage instruction and other given way. E1.13 Multi-speed 13 -100.0% to 100.0%...
Page 42
Chapter 5 Function parameter Chapter 5 Function parameter PID output as negative output adjustment amount continuously increases, if the deviation persists, the adjustment amounts will continue to increase until zero deviation. The integration PID output as positive, when the feedback signal is greater than PID setting, the regulator can effectively eliminate static difference.
Chapter 5 Function parameter Chapter 5 Function parameter detection time VDI depends on the state of virtual Feedback disconnection detection value: the detected value is relative to the full VDOx. scale (100%), the system has been detecting PID feedback, when the feedback value is less than or equal to the feedback disconnection detection value, the system starts to The availability of detect timing.
Chapter 5 Function parameter Chapter 5 Function parameter inverter receives one the forward run command, the inverter begins to run forward. E3.21 VDO5 delay time 0.0s to 3600.0s 0.0 s ☆ E3.07 AI1_DI function 0 to 25 ★ VDO is similar with DO output function, which can used with VDIx together to achieve some simple logic control.
Chapter 5 Function parameter Chapter 5 Function parameter 0: no operation Motor stator and rotor Depends on b0.08 0.1 to 6553.5mH ★ 1: Restore factory settings, without inductance models motor parameters Function parameter 2: Clear fault history Motor stator and rotor Depends on y0.00 ★...
Chapter 5 Function parameter 9: Constant speed overvoltage Chapter 6 Fault message and troubleshooting (E.oU3) 10: Bus undervoltage fault (E.LU) 6-1.Fault message and troubleshooting 11: Motor Overload (E.oL1) No. Fault code Failure type Possible causes Solutions 12: Inverter overload (E.oL2) 14: output phase lose(E.oUT1) 1, excluding peripheral 16: Inverter module...
Page 47
Chapter 6 Fault message and troubleshooting Chapter 6 Fault message and troubleshooting No. Fault code Failure type Possible causes Solutions No. Fault code Failure type Possible causes Solutions decelerating 3. Input voltage is abnormal 2. Increasing braking External fault input terminal Check the external External fault 17 E.SET...
Page 48
Chapter 6 Fault message and troubleshooting Chapter 6 Fault message and troubleshooting 2004 (Adjustable speed electrical power drive systems part 3:EMC requirements and 1) Install surge suppressor on the devices generating interference; specific test methods),which is equivalent to the Chinese national standards 2) Install filter at the input end of the inverter,please refer to Section 6.3.6 for the GB/T12668.3.
Chapter 6 Fault message and troubleshooting There is the distributed capacitance between the output cables of the inverter. If the Chapter 7 Dimensions current passing lines has higher harmonic, it may cause resonance and thus result in leakage current. If the thermal relay is used, it may generate error action. 7-1.Dimensions The solution is to reduce the carrier frequency or install output reactor.
Chapter 7 Troubleshooting Chapter 8 Maintenance and repair Approxim Dimensions(mm) Installation Size( mm ) Base Power supply Power ate weight Type 8-1.Inspection and maintenance level (kW) (kg) During normal use of the inverter, in addition to routine inspections, the regular Single phase inspections are required (e.g.
Chapter 8 Maintenance and repair Chapter 8 Maintenance and repair The different instruments may come to different measurement results when -- 75% rated power 30minutes, --Last 100% rated power 30minutes, measuring. It is recommended that the pointer voltmeter shall be used for measuring Use adjustable power to charge the frequency inverter: input voltage, the rectifier voltmeter for output voltage, the clamp-on ammeter for input --25% rated power 2hours,...
Asynchronous series and half-duplex transmission mode. For master and 6. Dalian TPG Technology Co.,Ltd reserve the right to explain the terms of the slave,only one of them can send the data and the other only receives the data at the same event.
Page 53
Warranty Card Warranty Card unique. 1: + 5V Single application 2: GND T S R Figure I-3 single inverter and MODBUS set up the PC field wiring diagram. 3: RS+ 485 4: RS- 485 Because computers are generally not with RS485 interface, so must the computer comes 5: GND with RS232 interface or a USB interface through the converter conversion for RS485.
Page 54
Warranty Card Warranty Card Function Lo diverse character intervals under network baud rate,which is easiest implemented (as DATA (N-1) Data Content: nx8-bit data consists of 2n combinations of ASCII shown in Figure T1-T2-T3-T4) . The first field transmitted is the device address. The …...
Page 55
Warranty Card Warranty Card When F9.05 is set to 1: ‘8’ Data address 0004H low-order START T1-T2-T3-T4 ‘8’ ADDR ‘1’ Data address 0005H high-order ‘3’ Byte number ‘8’ Data address 0005H low- Data address 0001H high-order order ‘8’ Data address 0001H low-order LRC CHK Hi ‘C’...
Page 56
Warranty Card Warranty Card Besides, due to EEPROM is frequently stored, it will reduce the life of EEPROM, therefore under the communication mode some function code do not need unsigned int crc_value=0xFFFF; to be stored and you just change the RAM value. If F group parameters need to achieve the function, as long as change high int i;...
Page 57
Warranty Card Warranty Card 1016H Device code Inverter fault address: Fault code Inverter fault information: The set value is the percentage of the relative value, 10000 corresponds to 0000: No fault E.oUt1 0001: Output phase loss 100.00%, -10000 corresponds to -100.00%. E.oUt2 0002: Retain For frequency dimension data,it is the percentage of the maximum output...
Page 58
Warranty Card MODBUS exception code Code Name Explanations address is different from the password set by user (y0.01) . The request data address of host computer is disallowed; Illegal data particular, the combination of register address and number of address bytes transferred are invalid.