Siting The Flue Terminal; Air Supply - Worcester 47 311 43 Installation And Service Instructions Manual

Table of Contents

Advertisement

5

Siting the Flue terminal

TERMINAL POSITION
A -
directly below an openable window or
other opening e.g. air brick.
B -
Below gutters, soils pipes or drain pipes.
C -
Below eaves.
D -
Below balconies or car port roof.
E -
From vertical drain pipes and soil pipes.
F -
From internal or external corners.
G -
Above ground, roof or balcony level.
H -
From a surface facing a terminal.
6

Air supply

Above the Turret
Above casing
Below casing
Right-hand side
Left-hand side
In front
MIN. DISTANCE
300 mm (12 in.)
75 mm (3 in.)
25 mm (1 in.)
25 mm (1 in.)
25 mm (1 in.)
25 mm (1 in.)
300 mm (12 in.)
600 mm (24 in.)
30 mm
235 mm
200 mm
75 mm
75 mm
250 mm
TERMINAL POSITION
I - From a terminal facing a terminal.
J - From an opening in a car port (e.g. door
window) into dwelling.
K - Vertically from a terminal on the same
wall.
L - Horizontally from a terminal on the same
wall.
M - From door, window or air vent (achieve
where possible.
POSITION OF
AIR FOM THE
AIR VENTS
ROOM
HIGH LEVEL
270 cm
LOW LEVEL
270 cm
Fig. 4
MIN. DISTANCE
1200 mm (47 in.)
1200 mm (47 in.)
150 mm (6 in.)
300 mm (12 in.)
150 mm (6 in.)
AIR DIRECT
FROM OUTSIDE
3
3
135 cm
3
3
135 cm