LeeLen ATSC702 Operation Manual

LeeLen ATSC702 Operation Manual

Atse controller

Advertisement

Quick Links

 
ATSC702 双电源自动转换控制器
ATSC702 ATSE Controller
操作手册
Operation Manual
 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ATSC702 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for LeeLen ATSC702

  • Page 1   ATSC702 双电源自动转换控制器 ATSC702 ATSE Controller 操作手册 Operation Manual  ...
  • Page 2: Table Of Contents

      目录  Table of Contents  一、产品简介 ......................  2   二、前面板触摸按键功能 ..................  3   三、前面板指示灯 ....................  3   四、工作模式 ......................  4   五、主菜单 ......................  4   六、接线图 ......................  1 3  七、机械尺寸与面板开孔 ...................  1 8  八、技术规格 .......................  1 8  附录 A.代码说明  ....................  1 9  1. Product introduction ..................  2 0  2. Front panel touch button function  ..............  2 1  3. Front panel LED .................... ...
  • Page 3: 一、产品简介

    产品介绍  一、 产品简介 ATSC702 系列双路电源自动切换控制器是一种具有可编程功能、自动化测量、LCD 菜单显示,数字通讯 为一体的智能化双电源切换产品,可自动实现电压、频率、相位、功率等电参量测量,并根据设置策略进 行自动化控制,可减少人为操作失误,是双电源切换的理想产品。 ATSC702 系列双路电源自动切换控制器由微处理器为核心构成, 可精确地检测两路三相电压, 对出现的 电压异常(过压、欠压、缺相、过频、欠频)做出准确的判断并输出无源控制开关量。该装置充分考虑了在 多种 ATS(负载自动转换系统)上的应用, 可直接用于专用型 ATS、 接触器组成的 ATS、 断路器组成的 ATS 等。 其结构紧凑、电路先进、接线简单、可靠性高,可广泛应用于电力、邮电、石油、煤炭、冶金、铁道、市 政、智能大厦等行业、部门的电气装置、自动控制以及两路电源供电系统。 功能参数  ●图形 LCD128x64 像素。 ●两路交流电源输入:单相两线、两相三线、三相三线、三相四线。 ●测量值、设置和消息文本支持中英文语言。 ●10~30VDC 直流电源。 ●具有过压、欠压、缺相、逆相序、过频、欠频检测功能。 ●8 路可编程数字输入(接地有效)。 ●10 路可编程数字输出。 ●集成 RS-485 隔离接口,MODBUS 通讯协议。...
  • Page 4: 二、前面板触摸按键功能

    界面介绍  二、 前面板触摸按键功能 图标  按键名称  功能描述  I 位置  手动模式下,按下此键,切换到 I 位置。    II 位置  手动模式下,按下此键,切换到 II 位置。    0 位置  手动模式下,按下此键,切换到 0 位置。    测试键  长按此键 3S 进入测试功能。    自动模式键  长按此键 3S 将控制器设置为自动模式。    手动模式键  长按此键 3S 将控制器设置为手模式。    编程模式键  长按此键...
  • Page 5: 四、工作模式

    工作模式  四、 工作模式 ●  编程模式:该模式下进行参数设置操作,长按编程模式键 3S 弹出密码输入界面,输入正确密码后进入 参数设置。  ●  手动模式:在 S1,S2 两路电源均可用时,可手动控制转换开关,长按手动模式键 3S 进入手动模式并锁 键防止误操作。需要手动切换时先长按 ESC 键解锁后操作,按下 I 位置键、II 位置键、O 位置键可将开关切 换至对应位置。  ●  自动模式:长按自动模式键 3S 进入自动模式。在自动模式下,设备自动切换开关位置。当优先电源电 参量超出设定范围, 且异常时间长于设定的延迟时间, 设备将断开优先电源的负载, 转而连接到备用电源。    五、 主菜单 ●主菜单由参数设置、电压参数、频率参数、延时参数、可编程控制、通信参数、语言/language 组成,方 便用户快速访问测量值及修改参数。  ●当有参数修改时,按 ESC 键退回到主界面提示是否“保存参数” 。选择“确认”保存当前修改参数,选择 “取消”则恢复为此次修改前的参数配置。 ...
  • Page 6 参数设置  5.1、参数设置 序号  选项  说明  默认值  范围  三相四线/三相三线/ 电网类型 被测电网的工作导线数目 三相四线 两相三线/单相两线 额定电压 电网线电压值 50-400V Ⅰ路市电Ⅱ路市电:市电到市电供电 Ⅰ路市电Ⅱ路市电/Ⅰ Ⅰ路市电 电源转换类型 Ⅰ路市电Ⅱ路发电: 市电到发电机供电 路市电Ⅱ路发电/Ⅰ路 Ⅱ路市电 Ⅰ路发电Ⅱ路市电: 发电机到市电供电 发电Ⅱ路市电 电源优先级 选择电网Ⅰ路或电网Ⅱ路为优先电源 Ⅰ路优先 Ⅰ路优先/Ⅱ路优先 自投自复/自投不自复/ 主电源返回方式  通过按键选择主电源返回方式  自投自复 1.5  互为备用  一分断位/二分断位/无 分断位设置  通过按键选择分断位  一分断位 1.6 ...
  • Page 7 参数设置  5.2、电压参数: 失电后或电源返回后开始检测限值 序号  选项  默认值  范围  电源Ⅰ过压值  2.1  115%  102‐130%  电源Ⅰ过压值返回值  2.2  110%  101‐129%  电源Ⅰ欠压值  2.3  85%  70‐98%%  电源Ⅰ欠压值返回值  2.4  95%  71‐99%  电源Ⅱ过压值  2.5  115%  102‐130%  电源Ⅱ过压值返回值  2.6  110%  101‐129%  电源Ⅱ欠压值  2.7  85%  70‐98%  电源Ⅱ欠压值返回值  2.8  95%  71‐99%  ATSC  702  6 ...
  • Page 8 参数设置  5.3、频率参数: 失电后或者电源返回后开始检测限值. 序号  选项  默认值  范围  电源Ⅰ过频值  3.1  105%  101‐120%  电源Ⅰ过频返回值  3.2  103%  100‐119%  电源Ⅰ欠频值  3.3  95%  80‐99%  电源Ⅰ欠频返回值  3.4  97%  88‐100%  电源Ⅱ过频值  3.5  105%  101‐120%  电源Ⅱ过频返回值  3.6  103%  100‐119%  电源Ⅱ欠频值  3.7  95%  80‐99%  电源Ⅱ欠频返回值  3.8  97%  88‐100%  ATSC  702  7 ...
  • Page 9 参数设置  5.4、延时参数: 序号  选项  说明  默认值  范围  Ⅰ路故障延时  一路电源故障检测延时  4.1  5S  0‐60S  返回一路电源前, 经过此设置延时 Ⅰ路可用延时  4.2  2.0Min  0‐60.0Min  后,确认其稳定可用  Ⅰ→Ⅱ零位置 一路电源转换至二路电源, 在零位 4.3  0S  0‐20S  延时  置上的停留时间  Ⅱ路故障延时  二路电源故障检测延时  4.4  5S  0‐60S  返回二路电源前, 经过此设置延时 Ⅱ路可用延时  4.5  2.0 Min  0‐60.0Min  后,确认其稳定可用  Ⅱ→Ⅰ零位置 二路电源转换至一路电源,...
  • Page 10 参数设置  5.2 自动同步转换启用:开启自动模式下同步转换功能。自动模式下同步转换将在返回“主电源”时进行。如同步转换操作等待时间超过 “最大同步时间, ”将提示“同步转换超时” 。  5.6、可编程控制: 序号  选项  默认值  范围  数字输入  6.1    1‐5  输入功能  6.1.x.1      触点类型  常开  常开/常闭  6.1.x.2  输入延时  6.1.x.3  0.05S  0.01‐600.00S          数字输出  6.2    1‐6  输出功能  6.2.x.1      触点类型  常开 ...
  • Page 11 参数设置  测试模式  控制器处于测试模式(空载以及带载测试) ,输出激活  Ⅰ位置信号  ATS 处于位置Ⅰ,输出激活  Ⅱ位置信号  ATS 处于位置Ⅱ,输出激活  0 位置信号  ATS 处于位置 0,输出激活  消防联动  消防联动输入信号有效,且开关动作,输出激活  负载脱扣  负载脱扣输入信号有效,且控制已做好判断,输出激活  ATS 电源 N  执行机构的辅助电源 N  ATS 电源 L  执行机构的辅助电源 L  启动发电机  在发电机模式下,市电异常时,输出激活  通用  设置为通用时,可通过通信协议激活输出  5.7、通信参数: 序号  选项  默认值  范围  通信地址  7.1  3 ...
  • Page 12 参数设置  ●电源状态,参见图 1 页面  示例  说明  I 主:线路 I 为主电源,其后为实际电压值。  II 备: 线路 II 为备用电源, 其后为实际电压值。   图 1、 电源状态  Load:负载。  图中有开关标志。  ●数据显示,参见图 2—图 7 页面  示例  说明  图 2、 数据显示  线电压(380V)  图 3、 数据显示  相电压(220V)  实际相位  0°  图 4、 数据显示  120° ...
  • Page 13 参数设置  ●统计数据,参见图 8—图 12 页面  示例  说明  CNT AUT:自动模式下,线路的合闸次数。  图 8、 统计数据  CNT MAN:手动模式下,线路的合闸次数。  T‐LOAD:线路 1 或线路 2 为负载供电的时间。   T‐NOLOAD:线路没有为负载供电的时间。  POWER DOWN:掉电的次数。  图 9、 统计数据  A03:A03 的报警次数。  A04:A04 的报警次数。  图 10、  可编程输入,如检测 01 输入口有信号,则 01 可编程输入  会被选中。(1‐3 已固化)  图 11、  可编程输出,如 01 输出口有输出动作,则 01 可编程输出 ...
  • Page 14 参数设置  页面  示例  说明  启动空载试机,空载试机不判断电源状态即 图 14、空载试 进行转换开关动作测试,将执行负载依以下 机  顺序进行动作: 1 切换至双分, 2 切换至 2 路, 3 切换至双分,4 切换至 1 路。  启动带载试机,带载试机需要判断 S1,S2 电 源状态同时均可用时,才执行与空载试机相 图 15、带载试 同的开关动作测试。如电源转换类型为“市 机  电‐发电机” , 控制器启动发电机至电源可用时 执行测试。  ATSC  702  13                                                                                                                   ...
  • Page 15 端子布置    六、 端子布置图 6.1 端口定义及说明: 端子号  项目  功能描述  备注  若为单相,则只接入 S1 电压输入 L1、N。 L1、 N 为交流供电接口。 若为单相,则只接入 S2 电压输入 L1、N。 L1、 N 为交流供电接口。 模块接地 模块接地端 POSITION I INPUT I 位置开关闭合检测 POSITION Ⅱ INPUT Ⅱ位置开关闭合检测 接地有效 POSITION O INPUT O 位置开关闭合检测 INP1 用户自定义输入口功能...
  • Page 16 端子布置    INP2 INP3 用户自定义输入口功能 接地有效 INP4 INP5 RS485A+ RS485 通讯接口 RS485B- RS485 地 BATTERY+ 直流电源正极 BATTERY- 直流电源负极 继电器公共端 可编程输出口 10A(用 OUT1 继电器常开端 作 DPS 功能时,32、33 作为辅助电源输入) 继电器常闭端 继电器公共端 可编程输出口 10A(用 OUT2 继电器常开端 作 DPS 功能时,35、36 作为辅助电源输入) 继电器常闭端 发电机公共端 OUT3 发电机启动/停止信号常开端...
  • Page 17 接线示意图  6.2、接线示意图       ATSC  702  16                                                                                                                   ...
  • Page 18 接线示意图  6.3、同步转换逻辑图   手动模式下同步转换逻辑  Qs1:OFF Qs1:ON Qs2:ON Qs2:OFF 手动操作按键I 手动操作按键II 并联转换使能 并联转换使能 满足并联 满足并联 报警 转换条件 转换条件 Qs1:OFF Qs1:OFF Qs1:ON Qs1:ON Qs2:OFF Qs2:OFF Qs2:ON Qs2:ON 并行保持时间 并行保持时间 Qs1:ON Qs1:OFF Qs2:OFF Qs2:ON       ATSC  702  17                                                                                                                   ...
  • Page 19 接线示意图  自动模式下同步转换逻辑  Qs1:OFF S1恢复可用 Qs2:ON S2保持可用 电源返回方式 不动作 为自投自复 分断位为无分 分断位为两分 断位 断位 并联转换使能 满足并联 报警 转换条件 Qs1:OFF Qs1:ON Qs2:OFF Qs2:ON 并行保持时间 Qs1:ON Qs2:OFF   ATSC  702  18                                                                                                                   ...
  • Page 20: 七、机械尺寸与面板开孔

    技术规格及尺寸  七、 机械尺寸与面板开孔   八、 技术规格 1、交流电源供电:端子 3、4 和 7、8 额定电压  400VAC(LL)  工作电压范围  90‐300VAC(LN)  频率  45‐65Hz  功耗  10W    2、直流电源:端子 29、30 额定电池电压  24VDC  工作电压范围  10‐30VDC  最大功耗  10W  3、数字输入:端子 17—25   输入类型  负  输入电流  ≤8mA  低输入信号  ≤2.2V  高输入信号  ≥3.4V      ATSC ...
  • Page 21 技术规格及尺寸    4、RS485 串行接口:端子 26、27、28 接口类型  隔离  波特率  2400‐38400bps  5、数字输出:端子 31—51   触点类型  4 组常开、常闭;6 组常开  容量  DC:10A、30V,AC:10A、250V  6、工作环境条件   工作温度  ‐25℃‐70℃  存储温度  ‐30℃‐80℃  相对湿度  20%‐93%  最大环境污染  3 级        附件.代码说明 代码  名称  报警说明  位置 1 动作超时  位置 1 在设定的时间内无断开或闭合操作。  A03 ...
  • Page 22: Product Introduction

    Product Introduction   1. Product Introduction ATSC 702 automatic transfer controller is an intelligent ATSE controller with programmable functions, automatic measuring, LCD menu display, and digital communication. It can automatically realize voltage, frequency, phase etc. electrical parameters measurement and automatic control according to setting strategy which can reduce human operation error.
  • Page 23: Front Panel Touch Button Function

    Product Introduction 2. Front panel touch button function Icon Button name Function description In Manual mode, press this button to transfer load to Position I position I In Manual mode, press this button to transfer load to Position II position II In Manual mode, press this button to transfer load to Position 0 position 0...
  • Page 24: Working Mode

    Product Introduction 4. Working mode  Programming mode: parameter setting operation under this mode, long pressing “programming mode” button for 3s to enter. All measuring values and status LED display keep activated. Set as programming mode before visiting programming menu. ...
  • Page 25 Parameter Setting 5.1、Parameter Setting Option Definition Default Adjustment Range NETWORK Network Type 4NBL 4NBL/3NBL/2NBL/1BL NOM.VOLT. P-P Voltage 50-400V M-M:Mains to Mains Supply M-G:Mains to Generator Supply M-M/M-G/G-M G-M:Generator to Mains Supply PRIO NET Choose S1 or S2 for Priority Net S1/S2 Automatic Automatic retransfer to retransfer...
  • Page 26 Parameter Setting 5.2、Voltage Levels Menu: Option Definition Adjustment Range OV.U I:Over-voltage 115% 102-130% threshold S1 OV.U HYS I: Over-voltage hysteresis 110% 101-129% UND.U I: Under-voltage 70-98%% threshold S1 UND.U HYS I: Under-voltage 71-99% hysteresis S1 OV.U II: Over-voltage 115% 102-130% threshold S2 OV.U HYS II: Over-voltage hysteresis 110% 101-129%...
  • Page 27 Parameter Setting 5.3、Frequency Levels Menu: Option Definition Adjustment Range OV.F I:Over-frequency 105% 101-120% threshold S1 OV.F HYS I: Over- frequency 103% 100-119% hysteresis S1 UND.F I: Under- frequency 80-99% threshold S1 UND.F HYS I: Under- frequency 88-100% hysteresis S1 OV.F II: Over- frequency 105% 101-120% threshold S2...
  • Page 28 Parameter Setting   5.4、Timer Menu: Option Definition Default Adjustment Range Source I Failure Timer 0-60S Source I Return Timer 2Min 0-60Min Source I to Source II dead time in 0 Ⅰ→Ⅱ 0DT 0-20S position Source II Failure Timer 0-60S Source II Return Timer 2.0 Min 0-60.0Min Source II to Source I dead time in 0...
  • Page 29 Parameter Setting 5.6、Programmable Control: Option Default Adjustment Range Digital Input 6.1.x.1 Input function 6.1.x.2 Contact Type NO/NC 6.1.x.3 Input delay 0.05S 0.01-600.00S Digital Output 6.2.x.1 Output function 6.2.x.2 Contact Type NO/NC INPUT MENU Input Menu Input code definition Inhibit Inhibit input function The transfer switch is immediately driven to 0 position,and the controller in manu Forced to pos.
  • Page 30 Parameter Setting Auto mode The output signal is activated when controller in auto mode Test mode The output signal is activated when controller in auto mode Position I The output signal is activated when ATS in position I Position II The output signal is activated when ATS in position II Position 0 The output signal is activated when ATS in position 0...
  • Page 31 Parameter Setting test with test off load.  ● Power supply status icon, refer to pic1: Page Example Note I Main: S1 is normal power supply, next to it is actual voltage Pic.1 value.II Backup:S2 is Power supply reserved power status supply, next to it is actual voltage value.
  • Page 32 Parameter Setting   Pic6. Alarm status, If there is A21 alarm, A21 in the Data display pic will be selected Pic7. Control threshold, The max/min value of Data display voltage and frequency of power supply ● Statistic data icon, refer to pic8-pic12 Page Example Note...
  • Page 33 Parameter Setting ●Event record Icon, refer to pic13 page example Note Pic13 Device Event record Event record ●Commissioning Icon, refer to pic14、15 page example Note Test off load will not judge power state and perform the transfer switch action test and Pic14 operate the load in the following order: Test off load...
  • Page 34: Wiring Diagram

    Mechanical dimension and panel opening 6. Wiring diagram 6.1 Terminal definition and description: Terminal Item Function description Note If single-phase, only L1, N connected S1 AC 3-phase 4-wire voltage input L1,N are AC power supply terminal. If single-phase, only L1, N connected S2 AC 3-phase 4-wire voltage input L1,N are AC power supply terminal.
  • Page 35 Mechanical dimension and panel opening   RS485A+ RS485 communication interface RS485B- RS485 grounding BATTERY+ Positive electrode of DC power supply BATTERY- Negative electrode of DC power supply change-over switch L1 auxiliary power output port OUT1 SⅡ power supply L1 SⅠpower supply L1 change-over switch N auxiliary power output port OUT2...
  • Page 36 Mechanical dimension and panel opening 6.2、Typical application       ATSC  702  35                                                                                                                   ...
  • Page 37 Mechanical dimension and panel opening 6.3、Close transfer prototype   Close transfer prototype in Manu mode        ATSC  702  36                                                                                                                   ...
  • Page 38 Mechanical dimension and panel opening Close transfer prototype in Auto mode  S1 return Qs1:OFF available Qs2:ON S2 keep available RETURN=’ No Action Auto retransfer’ OFF POSITION OFF POSITION =’zero =’two position’ position’ Close transfer enable Close transfer Alarm condition available Qs1:OFF Qs1:ON Qs2:OFF Qs2:ON Max SYNC time Qs1:ON Qs2:OFF  ...
  • Page 39: Mechanical Dimension And Panel Opening

    Mechanical dimension and panel opening   7. Mechanical dimension and panel opening 8.Technical parameters 1、AC supply: terminal 3,4 and 7,8 Rated voltage 400VAC(LL) Operating limit value 90-300VAC(LN) Frequency 45-65Hz Power consumption 2、DC supply:terminal 29,30 Rated battery voltage 24VDC Operating limit value 10-30VDC Max power consumption 3、Digital input:terminal 17—25...
  • Page 40: Annex A: Code Description

    Mechanical dimension and panel opening Baud rate 2400-38400bps 5、Output 31-33(OUT1) 、34-36(OUT2) 、37-39(OUT3)、40-42(OUT4) Contact Type single-pole double throw Rated value DC:10A、30V,AC:10A、250V 6、Output 43(OUT5)、46(OUT6) 、48(POSITION O)、49(POSITION Ⅱ 、51(POSITION Ⅰ Contact Type single-pole single throw Rated value DC:10A、30V,AC:10A、250V 7、Working environment condition Working temperature -25℃-70℃...