Global Fire Equipment GFE-DHA Instruction Manual

Addressable magnetic door holder

Advertisement

Mechanical Specification

46.8 mm

Technical Specifications

Supply Voltage
Address Range
Loop Current - Quiescent
Loop Current - Charging
Isolator - Loop Line Resistance
Charge up time
Fail Safe Release Time
1)
Manual Release
Max. Cable Size
Max. Humidity
Operating Temperature
Magnet Holding Force
Dimensions (Magnet)
Weight (Magnet)
Dimensions (Keeper)
Weight (Keeper)
Weight - complete unit boxed
Order Code
GFE-DHA
1) Fail Safe Release Time is defined as the time taken to release door when removal
of loop power or loss of communication with control panel is detected.
Global Fire Equipment S. A.
MARF - Armazéns F3 e F4, Sítio do Guelhim, Estói, 8009-021 FARO, PORTUGAL
Tel: + 351 289 896 560 Fax: + 351 289 865 587
Sales sales@globalfire.pt Technical Support techs@globalfire.pt
112.5 mm
Loop Powered - 17V to 30 V DC
1-125
600 uA (450 uA module+150 uA isolator)
7 mA
60 mOhms
25 s
20 s
Push Button - Normally Open
2
2.5 mm
95% RH Non-Condensing
0
C to 40
C
º
º
200 N
112.5 (H) x 84.2 (W) x46.8 (D) mm
520 g - boxed inc. electronic module
55 (H) x 55 (W) x 50 (D) mm
139 g
700 g
Addressable Magnetic Door Holder
GFE-DHA
Addressable Magnetic Door Holder
The unit is a loop powered addressable
magnetic door release. It does not require
external supply as it is directly powered from
the loop.
Activation of the unit is achieved using cause
and effect programming as used for I/O units.
If power is removed or communication with
the panel is lost the unit will release
automatically after approximately 20
seconds.
A built in loop isolator is provided. When a
short condition exists in either side of the
loop connections, a YELLOW LED will be
turned ON. Its operation will be reset after
the fault condition is removed.
Module is fitted with 3 status leds. The GREEN
LED will flash every time the device is polled
by the addressable panel.
The RED LED, when ON, indicates that the
door release has been activated and it is OFF
after panel power up or reset. When flashing,
it indicates that the door holder is ready to
release. Finally the YELLOW LED will indicate a
fault in the module.
The activation of the module can be achieved
as part of the cause and effect programming
of the panel and it operates in the same way
as an I/O unit. This unit should normally be
added to an IO group and assigned to either a
specific device or zone.
Up to a maximum of 20 of these units can be
fitted on a particular loop.
Instruction Manual V1.0- 06/10
Addressable Unit
Loop Powered
4 Status Indicators:
Coms, Fault, Released, Isolator
Loop Powered
Max. 20 units per Loop
Built-in Loop Isolator
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GFE-DHA and is the answer not in the manual?

Questions and answers

Summary of Contents for Global Fire Equipment GFE-DHA

  • Page 1 Loop Powered Up to a maximum of 20 of these units can be fitted on a particular loop. Global Fire Equipment S. A. Max. 20 units per Loop MARF - Armazéns F3 e F4, Sítio do Guelhim, Estói, 8009-021 FARO, PORTUGAL...
  • Page 2 Maximum no. of devices between 2 Isolators: 32 (EN54 pt.2) - 20 (BS5839) Address Settings Short Circuit YELLOW LED indicators are ON Loop In Loop Out Short Circuit Loop Voltage = 0V Switches 1-7 used to configure the module’s address. Switch 8 Not used Address Switches binary weights...

Table of Contents