Bus model assembly (option) ........................13 Commissioning ................... 14 General information ..........................14 Requirements ............................14 Procedure for commissioning ........................14 Control-oriented integration of the HYDROOPT M in the customer's instrument and control facilities .. 15 ® Operation ....................16 Operating unit ............................16 Alarm message/Warning message ......................
AL-KO HYDROOPT ® Product description The hydraulic station is used for highly efficient heat and cold recovery in closed-cycle systems. In winter, heat is extracted from the exhaust air flow from an exhaust air unit and transferred to a heat exchanger in the central supply air unit.
Possible misuse HYDROOPT M may only be operated within the scope of the technical data specified by AL-KO. Any other use or use ® beyond that described in the "intended use" point is regarded as not in accordance with the designated use. The manu- facturer cannot be held liable for damage resulting from this.
20 A slow blow The maximum customer-side back-up fuse is specified on the enclosed circuit diagram. The exact dimensioning of the pump and the calculation of the necessary system pressure is carried out by AL-KO THERM after the order is placed.
Page 7
Product description Dimensions: Width Breite Length Länge Compact control units Type Dimension Flow rate m Length mm Width mm Height mm Weight kg DN 32 0.5–1.9 1330 1680 DN 40 2.0–4.9 1330 1680 DN 50 5.0–9.9 1330 1680 DN 65 10.0–14.9 1630 1880 DN 80 15.0–25.0 1630 1880...
The station must be stored in a dry location, protected against the weather. The functional units must be protected against debris (e.g swarf, stones, wires, etc.) and strong UV exposure. The HYDROOPT M station is delivered un- ®...
Installation Installation General information All hydraulic components are pre-mounted and piped on the supporting frame. All pipe parts and fittings at risk from condensation are insulated against cold and steam. Warning! Assembly, electrical connection, supply connection, maintenance, commissioning and repair, etc. must only be carried out by trained and authorised specialists.
AL-KO HYDROOPT ® Filling and venting The filling and venting equipment for the heat exchanger must be set up on-site. The pipe system must be resistant to ethylene glycol (N). The glycol content must be prepared according to the manufacturer's instructions.
Installation 2.4.2 Bus model assembly (option) As an option, the control system can be integrated in a superordinate network. The following bus modules are optionally available for this: Modbus BACnet, TCP/IP The figure shows the Climatix BACnet/POL908.00 IP module/STD. It is connected to the Climatix control system ...
Installation, commissioning, maintenance, and repair work may only be performed by trained and qualified specialist personnel. Requirements For commissioning the HYDROOPT M station, the following actions must already have been completed on site: ® The supply and exhaust air system must be operational.
The decision whether the heat recovery can take place must be made by the customer's control system by comparing the air temperature. y1 WRG y1 HRO y2 Heating y2 Heizen 100 % Heizen Heating Heating requirement Wärmebedarf Fig. Control strategy for controlling the HYDROOPT M closed-cycle system ® 3061955 Subject to changes in line with technical progress.
AL-KO HYDROOPT ® Operation Operating unit The operation is menu-driven and is carried out via the keys on the control unit or an optional remote control panel. Designation General function INFO button with integrated This button can be used to navigate from any menu item to the main menu.
Operation Reset alarms: Alarm list: The line is deleted. Alarm history: Display as an "outgoing" alarm Alarm types: The following table describes all of the alarms that can be displayed. Class B does not lead to a shut-down, but merely serves as a warning.
Page 18
AL-KO HYDROOPT ® In the main menu, the access level can be logged in, settings adjusted and system information retrieved. The displayed language can be changed with the service password in the main menu. System information, e.g. temperatures and brine/air volumes, can be viewed in the main menu under Information. These can vary depending on the expansion stage.
Operation Main menu (Info key) The selection of menu items changes depending on the access level: Password input Information Settings Versions The display of the screens depends on the system configuration. Only the screens required for the system configuration are displayed.
AL-KO HYDROOPT ® 4.4.2 Settings The setting options vary depending on the expansion stage. The date and time can be changed with the user password. All other settings fall under service applications. Under Settings, the service technician can adjust the system parameters in the service level.
System integrator Modbus (optional) The HYDROOPT M controller can be connected to a higher-level controller via a communication interface. The service password is required for this. The Modbus variant is explained below. To set the interface, navigate to the following menu item: Main menu (press the INFO key) >...
Page 22
® Name Range Explanation MB type None No connection via Modbus Slave HYDROOPT M controller as slave for a higher-level controller Address 0…247 Address of the HYDROOPT M controller MB ComType RTU Int Modbus RTU (via serial RS485 interface) TCP/IP...
Page 23
Operation Access Address Description ENG Data Type Unit Value Input Status Read-Only for BMS 1x0004 Pump 2 0 = Off 1 = On Input Status Read-Only for BMS 1x0005 Optimizing 0 = Off 1 = On Input Status Read-Only for BMS 1x0006 Coil 1 0 = Off...
Page 24
AL-KO HYDROOPT ® Access Address Description ENG Data Type Unit Value Input Register Read-Only for BMS 3x0017 Demand Unsigned Word 0,1% Input Register Read-Only for BMS 3x0018 State Unsigned Word 0=Off; 1=On; 2=Optimizing; 3=Defrost; 4=Alarm; Holding Register Read-Write for 4x0001...
AL-KO HYDROOPT ® Further operating options 4.5.1 HMI Web With the HMI Web, the entire system can be fully configured and put into operation according to the logged-in password level. HMI Web is part of the standard controller equipment. It can be accessed via the network connection of the controller via a terminal device provided by the customer (PC, notebook, tablet) with a web browser.
Page 27
Operation Designation General function INFO button with integrated LED Press this button to return to the home page. The integrated LED indi- cates the system status. ALARM button with integrated LED Press this button to access the alarm pages. The integrated alarm LED indicates the alarm and acknowledgement status.
AL-KO HYDROOPT ® 4.5.2 System graphic (optional) Once this option has been enabled, the system can be visualised on the PC using a system graphic via a LAN connection. Symbol Description Display of the name and version of the controller software...
Error messages are shown on the controller in plain text. In case of emergency and in case of questions, please contact the manufacturer of your Air Technology system, one of our branch offices or us directly: AL-KO THERM GMBH Telephone: (+49) 8225/ 39-0 Hauptstraße 248-250...
The owner of an air conditioning system is obliged to have the system maintained regularly by trained specialist per- sonnel. AL-KO THERM recommends that maintenance of the overall AC system is carried out in accordance with German VDMA 24186 and VDI 6022.
Maintenance Maintenance schedule Excerpt from VDMA 24186-1 and -4 Item Implementation Assembly/ Periodically As required Component/ every Activity Activity Pipe network (VDMA 24186-1) Pumps 3 mon 8.1.1 Check exterior for dirt, damage, corrosion and a secure fit 8.1.2 Function-maintaining cleaning (exterior) 6 mon 8.1.3 Check functionality...
Page 32
AL-KO HYDROOPT ® Item Implementation Assembly/ Periodically As required Component/ every Activity Activity 6 mon 10.1.12 Check the function of the protection device Documentation and marking (according to VDMA 24186-1) 11.1 Maintenance-relevant documents 3 mon Overview sheet available in HVE 11.1.1...
Disposal Do not dispose of worn-out equipment, spent batteries or rechargeable batteries in domestic waste. When disposing of the HYDROOPT M , operating material or accessories, comply with the relevant local ® environmental and recycling regulations in your country and community that are applicable at the time when the activity is undertaken.
AL-KO HYDROOPT ® Appendix Commissioning list Attention of: Company: In order to ensure a smooth commissioning process, the following work is necessary in advance: Central ventilation unit: Central ventilation unit ready for operation Connection on air side available Air volume measurements carried out...
Page 35
Evidence of heat recovery Supply air volume Exhaust air volume Outdoor air temperature °C Temperature according to HRO SUPP °C Exhaust air temperature °C Temperature according to HRO EXH °C BCS power requirement in Outdoor air amount: Pump frequency Displayed HRO power in Place, date Name of commissioning person...
Page 36
AL-KO THERM GMBH l Jettingen-Scheppach l Germany All rights reserved for AL-KO THERM GMBH, as well as in the event of applications for industrial property rights. This documentation or excerpts thereof may not be copied or forwarded to third parties without the express consent of AL-KO THERM GMBH. We reserve the right to make technical changes that do not impair the function.