C.A.P. PPM-4 Quick Start Manual page 2

Co2 controller

Advertisement

PPM-4
PPM-4
Indicators
The wall mount CO
sensor provides three LED lights that indicate
2
the CO
levels. The LED indicates the following settings:
2
• Left LED (green):
• Middle LED
• Right LED (red):
The plug in controller also
has two LED indicators:
• Left LED (red):
• Right LED (red):
Precautions
1. Do not expose the PPM-4 to water. It utilizes
a ventilated enclosure to properly "sample" the CO
2. Do not connect loads greater than 10 amps
@ 120 volts to this unit.
Calibration
The PPM-4 is factory calibrated and the sensor in the wall mount unit
is capable of remaining in calibration for a minimum of three years.
However extreme shock during shipping and other factors may
affect the calibration. The unit can easily be calibrated using
ambient air before use and periodically if desired.
Single-beam Non-Dispersive Infrared
Operating principle
(NDIR) with a 5" optical path length
Measurement range
0 – 5000 PPM CO
1 Minute
Warm-up time
Maximum drift per year
+/- 15 PPM
Accuracy @ 77˚F
+/- 50 PPM
R & M Supply, Inc., their retailers and distributors are not responsible for any damage or injuries, consequential or otherwise arising
from the use of this product. The purchaser assumes all responsibility for the use and proper installation of this device.
0-900 PPM
and power on
(yellow):
901 to 1450 PPM
1451+ PPM
Power is activated to
the CO
control device
2
/on control signal.
The plug-in controller
is plugged into an
active power source.
.
2
S p e c i f i c a t i o n S
2
Published by R & M Supply, Inc. Copyright 2010. All Rights Reserved
C O n T r O L L i n g Y O u r w O r L d
CO
CO
Controller
Controller
2
2
To calibrate, or re-calibrate the unit:
1. Bring the unit outside so that it will be exposed to an ambient
air source. Do not place the unit in direct sunlight.
2. Connect the plug-in controller to a 120 volt power supply and then
connect the wall mount sensor to the plug in controller. Allow the
sensor to warm up for 1 minute.
3. Locate the small calibration button that is on the back of the wall
mount controller. The calibration button is located in the one of
the slots going across the upper part of the back of the case.
The button is located in the second slot from the right. Use a
straightened paperclip or pin to press and hold the button.
4. To initiate calibration the button must be depressed for 8
seconds. When the calibration feature is activated, all LED lights
will begin flashing and will continue to flash until the calibration
is complete. The PPM-4 has a integrated calibration routine that
requires CO
levels to fully stabilize before finalizing the calibration.
2
5. Move away from the controller to allow the CO
stabilize for approximately 1-5 minutes. If the LED lights have
stopped flashing, the calibration is complete.
* Important: Do not breathe in the vicinity of the sensor while the calibration
routine is activated, this will just prolong the time necessary for the unit to
complete its calibration.
Warranty
The PPM-4 is warranted against defects in workmanship for
three years. Do not open or modify this unit. If the enclosure
on the wall mount sensor or plug-in controller is opened the
warranty is void. There are no user serviceable parts inside.
Always read and understand the operation manual in its
entirety before using this product and only use this item for its
intended purpose as described in the manual. Never exceed the
amperage specification. For technical questions, a copy of your
operation manual, safety concerns or warranty questions please
visit us at www.capcontrollers.com.
Recommended calibration interval
Operating voltages
Maximum amperage
Operating temperature range
Operating humidity range
Operating life expectancy
Warranty
concentration to
2
1 to 3 years
120 volts to plug in controller
10 amps @ 120 volts
0-50' C, 32 to 120˚F
0-99% RH (non-condensing)
15 years typical
Three years, parts and labor
through repair or exchange.