QUICK START GUIDE
OSI-RI-FIK
Smoke Detection System
SPECIFICATIONS
Wire Gauge for Terminals:
Operating Voltage Range:
Maximum Standby Current:
Maximum Alarm Current (LED on): 22 mA @ 32 VDC, 15 mA @ 24 VDC, 22 mA @ 15 VDC
Operating Humidity Range:
Operating Temperature Range:
Adjustment Angle:
Sensitivity Levels:
Fault Condition (Trouble):
Alignment Aid:
Alarm Indicator:
This guide provides information on how to install the OSI-RI-FIK Smoke De-
tection System.
Extensive product and critical product security information can be found
in the OSI-RI-FIK Installation Guide (Document No. E56-6957) available at
http://www.fike.com/06-912.
The OSI-RI-FIK system consists of an Imager and a reflector. (See Figure 1.)
FIGURE 1. IMAGER AND REFLECTOR
DETERMINE THE POSITIONS OF THE IMAGER AND REFLECTOR
COMPONENTS
Make sure that the intended mounting locations meet the following criteria
(See Figure 2.):
• Detector spacing must comply with local codes and standards
• Reflector must be located within the Field of View (FOV) of the Imager
• Clear path between the reflector and Imager
• Mounted well above the head-height of people and obstructions
• Avoid direct sunlight onto the units
The Imager and reflector should be placed within a recommended distance
below the ceiling. (See Figure 3.) This value will vary according to regional
specifications, geometry, and specific requirements for the installation. The
distance for flat ceilings and basic spacing requirements (S) is shown in the
following table.
Standard
Distance from Ceiling
NFPA 72
12 in. (300 mm) minimum
AS1670.1
1 to 23.6 in. (25 to 600 mm)
BS5839.1
1 to 23.6 in. (25 to 600 mm)
GB50166
11.8 to 39.4 in. (300 to 1000 mm)
For full information on spacing requirements, please refer to your local codes
and standards.
14 AWG (1.6 mm), 14 AWG (2.08 mm
Without isolator: 15 to 32 VDC (12 or 24VDC nominal, non-polarized),
15-28.5V when using isolators
13 mA @ 32 VDC, 14 mA @ 24 VDC, 20 mA @ 15 VDC
0% to 95% Relative Humidity, Non-condensing
–4°F to 131°F (-20°C to +55°C).
UL-Listed for use from 32°F to 100°F (0°C to 37.8°C)
20 degrees vertical, 50 degrees horizontal
Level 1 25%, Level 2 30%, Level 3 40%, Level 4 50%
Long-term drift reference out of 20% range, beam blockage or detector out of alignment, imager saturated
LED directional arrows
Local red LED and remote output
C2051-00, C2052-00
Maximum Spacing (S)
60 ft (18.3 m)
45.9 ft (14 m)
49.2 ft (15 m)
45.9 ft (14 m)
2
)
FIGURE 2. MOUNTING LOCATIONS
12" minimum
(0.3m)
30' (9.1m) maximum
To First
Detectors
10' (3.0m)
minimum
Typical
FIGURE 3. MOUNTING LOCATIONS
Ex. Distances according to NFPA 72.
Tx/Rx
1/4 S
maximum
Tx/Rx
1
704 S. 10th Street
Blue Springs, MO 64015
Phone: 800.979.3453; Fax: 816.228.9277
For system/product documentation including
installation, operation, and maintenance,
scan QR code or enter URL provided.
http://www.fike.com/06-912
1/2 S
S
Wall
1/2 S maximum
Reflector
S
Reflector
16 ft. (5m) minimum
328 ft. (100m) maximum
R
www.fike.com
C2053-00
C2054-00
I56-6957-000
10/21/2020