Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB Installation & Operating Instructions Manual
Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB Installation & Operating Instructions Manual

Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB Installation & Operating Instructions Manual

Positive pressure storage system 50/60 hz

Advertisement

Quick Links

Installation, Operating, and Maintenance
Positive pressure storage systems are designed to pro-
vide safe and reliable service when operated within de-
sign specifications. When operating this equipment, use
good judgment and safety precautions to avoid damage
to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in ac-
cordance with the latest edition of ASHRAE 15 (American Society
of Heating, Refrigeration, and Air Conditioning Engineers). The
accumulation of refrigerant in an enclosed space can displace oxy-
gen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregulari-
ties, unconsciousness, or death. Misuse can be fatal. Vapor is heavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only tracer gases and dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel
until all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig machine sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali-
fied electrician.
DO NOT WORK ON electrical components, including control pan-
els, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-
state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized be-
fore resuming work.
DO NOT syphon refrigerant by mouth.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 211
Tab
5a
Instructions
For Use With Positive Pressure Chillers

SAFETY CONSIDERATIONS

Catalog No. 531-927
Printed in U.S.A.
Positive Pressure Storage System
with soap and water. If any enters the eyes, IMMEDIATELY FLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cyl-
inder. Dangerous overpressure can result. When necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before transferring refrig-
erant to the machine. The introduction of the wrong refrigerant can
cause damage or malfunction to this machine.
Operation of this equipment with refrigerants other than those
cited herein should comply with ASHRAE 15 (latest edition). Con-
tact Carrier for further information on use of this machine with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while ma-
chine is under pressure or while machine is running. Be sure pres-
sure is at 0 psig (0 kPa) before breaking any refrigerant
connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If machine operates in
a corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about
and cause personal injury and damage to the machine.
DO NOT climb over a machine. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if com-
ponents are light, use such equipment when there is a risk of slip-
ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN-
GAGE THE STARTER. Open the disconnect ahead of the starter
in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code require-
ments of the original equipment.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor-
rosion, rust, leaks, or damage.
DO NOT MIX REFRIGERANT from chillers that use different com-
pressor oils. Compressor damage can result.
Form 19XB-1SI
19XB
50/60 Hz
Pg 1
6-96
Replaces: New

Advertisement

Table of Contents
loading

Summary of Contents for Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB

  • Page 1: Safety Considerations

    Operation of this equipment with refrigerants other than those cited herein should comply with ASHRAE 15 (latest edition). Con- tact Carrier for further information on use of this machine with other refrigerants. DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while ma- chine is under pressure or while machine is running.
  • Page 2: Table Of Contents

    CONTENTS SAFETY CONSIDERATIONS ....1 INTRODUCTION ......2 INSTALLATION .
  • Page 3: Mount The Pumpout Unit

    Table 1 — Positive Pressure System Assembly Numbers POSITIVE PRESSURE PUMPOUT UNIT SYSTEM ASSEMBLY ASSEMBLY NO. NUMBER 19XB04280205 19EA42-748 19XB04280206 19EA44-748 19XB04280207 19EA46-748 19XB04280208 19EA47-748 19XB04280213 19EA48-748 19XB04280214 19EA49-748 19XB04280215 19EA51-748 19XB04280216 19EA52-748 19XB04280601 19EA42-748 19XB04280602 19EA44-748 19XB04280603 19EA46-748 19XB04280604 19EA47-748 19XB04280605 19EA48-658...
  • Page 4 VENT VALVE VALVES VALVES CONDENSER REFRIGERANT WATER INLET VALVE CONNECTIONS (FIELD PIPING) 19EA PUMPOUT UNIT Fig. 1 — 19XB Positive Pressure Storage System CONTROL BOX (WIRING BY CONTRACTOR) COMPRESSOR 19EA CONTROL BOX (INTERIOR) 19EA PUMPOUT UNITS...
  • Page 5 ⁄ -16 bolts × 1-in. lg; 4 required. Fig. 2 — 19EA Pumpout Unit: Typical Chiller Mount ELECTRICAL CONNECTION OPTION LIST TRADE SIZE LOCATION ⁄ ⁄ BOTTOM MIDDLE ⁄ MIDDLE Fig. 3 — Pumpout Unit Contact Surfaces and Dimensions...
  • Page 6 Pumpout Unit Weight* Pumpout Condenser Water Flow Rate Pumpout Condenser Water Pressure Drop Maximum Entering Condenser Water Temperature Maximum Leaving Condenser Water Temperature Condenser Relief Valve (Fusible Plug) Condenser Pressure Rating Refrigerant Side Waterside Compressor Rating 1750 rpm (29 r/s) Reciprocating Valves (4-Valve Manifold, Copper with Brass Turn Knob Valves) *The pumpout unit weight includes the compressor/condenser, control box, and the oil separator.
  • Page 7: Make Piping Connections

    Table 3 — 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity TANK OD SIZE CODE (in.) 0428 24.00 0452 27.25 TANK OD SIZE CODE (mm) 0428 0452 LEGEND ANSI — American National Standards Institute ASHRAE — American Society of Heating, Refrigeration, and Air Conditioning Engineers —...
  • Page 8 TANK SIZE 0428 10- 5 9-10 ⁄ 0452 14-11 ⁄ 14- 4 ⁄ ⁄ ⁄ TANK SIZE 0428 3175 2997 1448 0452 4553 4382 1546 NOTES: Denotes center of gravity. 2. Dimensions in ( ) are in millimeters. 3. The weights and center of gravity values given are for an empty storage tank.
  • Page 9 CHILLERS WITHOUT ISOLATION VALVES GENERAL PIPING CONNECTION SIZES CONNECTION Refrigerant Transfer Connections Condenser Water Cooling Connectors Safety Relief Head Pumpdown Condenser ODS — Outside Diameter, Sweat NOTES: 1. The field-supplied tubing is to be ⁄ -in. OD tubing (min.) and must be arranged and supported to avoid stresses on the equipment, transmission of vibrations, and interference with routine access during the reading, adjusting, and servicing of the equipment.
  • Page 10 Table 4 — Relief Devices STORAGE RELIEF VALVE TANK SIZE OUTLET SIZE 1 in. NPT Female Connector 1 in. NPT Female Connector Fig. 7 — 19XB Pumpout System Wiring Schematic — Contactor — Fuse, 3 Amps — High-Pressure Cutout — Compressor Motor Voltage Line (3-phase) —...
  • Page 11: Controls And Components

    CONTROLS AND COMPONENTS Figure 1 shows the major components of the PPS system. Pumpout Unit — The pumpout unit consists of a spring- mounted direct motor-driven reciprocating compressor, a water- cooled refrigerant condenser, an oil separator, suction and discharge valves to control refrigerant flow, and prewired safety and control devices.
  • Page 12: Procedures

    NOTE: During this operation, maintain water circulation through the chiller cooler and condenser vessels to prevent tube freeze-up. DISTILLING THE REFRIGERANT — Refrigerant vapor is transferred from the chiller cooler vessel or pumpout stor- age tank through the pumpout condenser, condensed to a liq- uid, and pumped to the chiller condenser vessel.
  • Page 13: Tanks

    Fig. 10 — Valve Locations for 19XB Pumpout Unit With 19XB Storage Tank e. Open valve 5 fully after the chiller pressure rises above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. Open refrigerant charg- ing valve 7 and storage tank charging valve 10 to let liquid refrigerant drain into the chiller.
  • Page 14 3. Remove any remaining refrigerant. a. Turn on chiller water pumps. b. Turn on pumpout condenser water. c. Place valves in the following positions: VALVE CONDITION d. Run the pumpout compressor until the chiller pres- sure reaches 60 psig (414 kPa), [30 psig (207 kPa)]; then, shut off the pumpout compressor.
  • Page 15: Distilling The Refrigerant

    d. Close valve 1a. e. Turn off pumpout compressor. f. Close valves 1b, 3, and 4. VALVE CONDITION g. Turn off pumpout condenser water. h. Turn off chiller water pumps and lock out chiller compressor. Transfer All Refrigerant to Chiller Cooler Vessel: 1.
  • Page 16: Storage Tank

    Ordering Replacement Parts — formation must accompany an order for Carrier-specified parts: • machine model number and serial number • name, quantity, and part number of the part required •...

Table of Contents