Incite Fire SYNCRO Product Manual

Analogue addressable syncro view serial lcd repeater panel

Advertisement

Quick Links

SYNCRO
Analogue
Addressable
Syncro View
Serial LCD Repeater Panel
Product Manual
Australia Version 2 – March 2016

Advertisement

Table of Contents
loading

Summary of Contents for Incite Fire SYNCRO

  • Page 1 SYNCRO Analogue Addressable Syncro View Serial LCD Repeater Panel Product Manual Australia Version 2 – March 2016...
  • Page 2: Table Of Contents

    The Syncro View repeater panel will be overridden and cannot take control of the panel to which it is connected if the main control panel is at access level 2.
  • Page 3: Mounting

    Mounting Surface mounting units should be mounted on a dry, flat surface, at eye height to the display and in a level position such that the enclosure is not distorted. Screws or bolts of a minimum of 4mm diameter must be used to mount the enclosure in all three mounting positions.
  • Page 4: Technical Specification

    2 core RS485 (Up to 1200 metres total cable length) Maximum terminal capacity 2.5mm² Max number of units on each Syncro panel serial bus Maximum number of units to be powered from Syncro Aux 24V output Syncro_View_AUS_v2.0.docx Page 4 of 12...
  • Page 5: Syncro View Fascia

    Syncro View fascia Models with enable controls keyswitch Models without enable controls keyswitch. Syncro_View_AUS_v2.0.docx Page 5 of 12...
  • Page 6: Connecting To The Circuit Board

    Data Termination Up to 15 units can be connected to a Syncro control panel. In and out terminals for data and 24V DC are provided on each unit.
  • Page 7: Addressing The Units

    Fault/Healthy Connection Switched -VE outputs are available for signalling of power fault and power healthy indication marked PO (power on) and PF (power fault). Under normal circumstances (mains and battery connected and fuses intact) the -VE appears at the PO terminal. Failure of the mains or battery supply will transfer the -VE to the PF terminal.
  • Page 8: Processor And Watchdog Reset Switches

    Processor and watchdog reset switches The Syncro VIEW is controlled by a microprocessor, which will re-start itself and continue to run if it stops for any reason due to severe electrical interference such as an electrical storm. To ensure that the unit is not being subjected to continual, undue interference which may affect its proper operation, a watchdog (W/DOG) LED indicator is latched on and a fault condition signalled to the control panel.
  • Page 9: Adding A Syncro View To The Syncro Panel

    10 Adding a Syncro View to the Syncro panel The Syncro View repeater must be added to the system by configuring the Syncro panel using the Loop Explorer configuration utility. Click on the site name in the left hand window pane to show the option to add panels or repeaters to the system.
  • Page 10 I/O boards that may exist on the serial bus. Once the configuration file has been loaded into the panel the panel will now expect to see a Syncro View at the address allocated to it and will show a fault condition if the Syncro View is not fitted or is removed.
  • Page 11: Revision Details

    11 Revision Details Revision Reason Date of issue Number v1.0 Initial Release V2.0 Change of Incite Sydney address. Add power supply details into section 6 29/03/2016 and corrected PO connection on section 9 drawing Syncro_View_AUS_v2.0.docx Page 11 of 12...
  • Page 12 Sydney Block Y, Unit 1, 391 Park Road, REGENTS PARK NSW 2143 Mail: PO Box 508 GYMEA NSW 2227 Phone: 1300 INCITE (1300 462 483) | 02 9644 7144 Fax: 02 9644 7255 Email: sales@incitefire.com.au Technical support: support@incitefire.com.au Melbourne Address: Unit 120, 45 Gilby Road, MT WAVERLEY VIC 3149 Phone: 03 9544 2211 Fax: 03 9544 2212 Email: salesvic@incitefire.com.au...