Harrington Signal Network Plus 21 Manual page 28

Access terminal

Advertisement

Screen 21
Conventional Database
This screen lets the viewer see the display status of the conventional input circuits and
how they are setup in program. This screen will have the current status if these
convention circuits are in alarm or trouble. They will show if any circuits are set up for
verify or are in bypass or test mode. It will show if a reset is available or if it's an alarm
1 or alarm 2. With alarm 1 on a circuit is a detector and alarm 2 a pull station on a class
H programmed circuit. It will show if there is a trouble or a ground on the circuit.
Conventional circuits on an HS-3030 can be programmed in seven different configuration
types.
A = Class A contact
B = Class B contact
C = Normally closed
D = Normally open
E = Dual EOLR
G = Smoke detector
H = Smoke detector + contact
NP21 Access Terminal Guide
01-28-02
Technical Service
25