Note: Dial switch status description: 1: OFF, 0: ON

6.2 Modbus function code description

6.2.1 Exception response format of the ARTU tetratele unit to an erroneous command received

Address
Corresponding error function
BYTE
BYTE
XX
XX (requested function code
+80H)
Exception codes are defined as follows:
01 Illegal function code (the received function code is not supported);
02 Illegal data location (the specified data location is out of the scope of the instrument);
03 Illegal data value (data values received to host are out of range of the corresponding address);
04 Slave station device failure (data values received to host sent are not currently allowed to be written).

6.2.2 Status of the used Modbus 01H/02H function

Reading required by the upper computer (MODBUS 01H/02H function)
Address
Function
BYTE
BYTE
XX
XX(01H/02H)
Address
Function
BYTE
BYTE
XX
XX(01H/02H)
Lower machine abnormal reply (MODBUS 81H/82H function)
Address
Corresponding
error function
BYTE
BYTE
XX
XX(81H/82H)

6.2.3 Read by using Modbus 03 or 04 function

Reading required by the upper computer (MODBUS 03H/04H function)
Address
Function
BYTE
BYTE
XX
XX(03H/04H)
Address
Function
BYTE
BYTE
XX
XX(03H/04H)
Exception response format of the ARTU tetratele unit
Exception error code data
BYTE
01H、02H、03H、04H
Address
WORD
XXXX
Lower machine reply (MODBUS 01/02 function)
Data length
BYTE
XX
Exception error code data
BYTE
XX (02H address error, 03H data error)
Start address
WORD
XXXX
Lower machine reply (MODBUS 03H/04H function)
Data length
BYTE
XX(2*N)
CRC check
WORD
XXXX (CRC check value)
Data
CRC check
WORD
WORD
XXXX
XXXX (CRC check value)
Data
CRC check
N BYTE
WORD
XXXX.......
XXXX (CRC check value)
CRC check
WORD
XXXX (CRC check value)
Data
CRC check
WORD
WORD
XXXX(N)
XXXX (CRC check value)
Data
CRC check
2*N BYTE
WORD
XXXX.......
XXXX (CRC check value)