Troubleshooting - Venmar 6LC Installation, Operation And Service Instructions

Light commercial heat recovery ventilators and energy recovery ventilators
Table of Contents

Advertisement

Available languages

Available languages

6.1 Parts Replacement
M
B
R
OTOR AND
LOWER
EMOVAL AND
Disconnect power from the unit. To determine if the fan motor is burned out, disconnect the four-wire service connector between the motor
and cabinet. Connect the motor directly to a 120 volts power source with an electrical cable, as follows:
If the motor functions normally, there is a problem with the wiring connections or the main circuit board. Check all wiring and replace main
circuit board if necessary.
If the blower does not run, it must be replaced. To replace the motor, remove the recovery core from the unit. Disconnect the four-wire
service connector from the unit. Remove the fasteners holding the motor assembly in place. Lift the assembly up and out, using one hand
under the motor and one hand to steady it. Remove the assembly carefully from the unit to avoid damage to the insulation, shelf, etc. Install
the repaired motor assembly by following these instructions in reverse.
REMOVE THESE
TWO SCREWS
VD0004A
6LC, V6LC, 12LC and V12LC units

6.2 Troubleshooting

The wearing of safety glasses and gloves is recommended since a few diagnosis procedures may require the
unit to be in operation while proceeding. Be careful with moving and live parts to prevent injuries.
SYMPTOMS
Inside air is too dry.
Persistent condensation on windows,
walls, ceilings, etc.
Unit stops functioning.
Air from supply diffusers too cold.
Unit makes annoying noise.
Core freezing up.
(cont'd)
I
NSTALLATION
RED + WHITE
BLUE + WHITE
BLACK + WHITE
LOCKING PLATE
CAPACITOR
POSSIBLE CAUSES
Over ventilation - speed setting too high.
Dehumidistat setting is too low.
Improper adjustment of dehumidistat
control.
Improper ventilation rate.
Window frame is too cold or leaky.
Electrical supply interrupted.
Imbalance of supply and exhaust air.
Outdoor temperature very cold.
Blower wheel out of alignment.
Imbalance of supply and exhaust air.
Defrost damper not functioning.
For technical assistance and warranty information,
please call your local supplier.
6. Service
(cont'd)
Low speed
Medium speed
High speed
VD0001A
WARNING
!
9
7000 unit
SOLUTIONS
Adjust speed setting.
Set dehumidistat control in a higher position (if ap-
plicable).
Adjust dehumidistat control knob to a lower setting.
Install a dehumidistat (option).
Repair window frame.
Check the unit circuit breaker.
Check filters and cores for blockage.
Check balance of airflows.
Install electric duct heater if necessary.
Remove the motor/blower assembly
and adjust blower wheel.
Check filters and cores for blockage.
Check balance of airflows.
Check for operation of both defrost damper actuators.
THUMBSCREW
SERVICE CONNECTOR