Page 1
HRC200 INDUSTRIAL REMOTE CONTROL USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
Page 2
Smartgen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. SmartGen Technology reserves the right to change the contents of this document without prior notice. Table 1 Software Version Date...
200m. Used with engine controller, it can realize remote start, stop, load, unload, emergency stop and other functions. HRC200 adopts fully sealed structure, IP65 protection level, which can effectively prevent dust, water or others from entering the controller, making the controller operate stably and reliably, suitable for field, mining, urban construction and other application sites with complex working conditions.
Modbus-RTU communication protocol, longest communication distance 1,000m. LINK SmartGen special interface for program upgrade. Case Dimension (LxWxH) 105mmx72.5mmx34mm Working Conditions Temperature: (-25~+70)°C Humidity: (20~95)%RH Storage Condition Temperature: (-30~+80)°C Weight 0.2kg HRC200 Industrial Remote Control User Manual Page 5 of 16...
Indicator flashes yellow during pairing process; Common Indicator keeps green on during normal running; Alarm/Running Status Indicator flashes red when common alarm occurs; It will extinguish when communication abnormal situation lasts over 5s. HRC200 Industrial Remote Control User Manual Page 6 of 16...
Page 7
Stop inactive, communication status indicator keeps flashing red.) If can’t receive the data and no key operation within 10 minutes, remote No Key Operation control power will automatically shut off. HRC200 Industrial Remote Control User Manual Page 7 of 16...
1 when the middle four positions are connected to the jumper cap, otherwise it is 0. The default jumper cap position is 1111 (515MHz). Fig.3 Communication Channel Configuration HRC200 Industrial Remote Control User Manual Page 8 of 16...
3. Turn on the receiver power, POWER indicator keeps on. Insert a slender needle less than 3.5mm in diameter into the PAIR hole vertically, then long press PAIR key 6s. HRC200 Industrial Remote Control User Manual Page 9 of 16...
Receiver connects to engine controller via RS485 interface, 120Ω terminal matching resistor is recommended to use (when RS485 A(+) and TR terminal is short connected), RS485 communication line must use twisted shielded pair line. Fig.4 RS485 Connection Diagram HRC200 Industrial Remote Control User Manual Page 10 of 16...
0.5mm terminal should be short connected. AUX. INPUT2 0.75mm B- connected is active. AUX. INPUT1 0.75mm B- connected is active. 0.75mm Externally connects power positive. 0.75mm Externally connects power negative. HRC200 Industrial Remote Control User Manual Page 11 of 16...
6 SYSTEM APPLICATION DIAGRAM Remote control communicates with receiver via LoRa, engine controller and receiver can be controlled by RS485 communication or digital input/output port. Fig.7 HRC200 System Application Diagram HRC200 Industrial Remote Control User Manual Page 13 of 16...
Fig.9 HRC200R Overall Dimension 7.2 RECEIVER OVERALL DIMENSION Installation method can be 35mm guide rail installation or screw (M4) installation. Overall dimension is as follows: Unit: mm Fig.10 HRC200M Overall Dimension HRC200 Industrial Remote Control User Manual Page 15 of 16...
Check whether the receiver dial switch is set to 0000 position. Connect Check whether the emergency stop key is pressed, when it is Remote Control Key Inactive pressed, other function keys are inactive. _________________________________ HRC200 Industrial Remote Control User Manual Page 16 of 16...