AMC 1022M Series Instruction Manual

Hazardous gas monitoring system

Advertisement

Quick Links

1022M
AMC-1022M SERIES
HAZARDOUS GAS MONITORING
SYSTEM INSTRUCTION MANUAL
IMPORTANT:
PLEASE READ THESE INSTRUCTIONS
CAREFULLY BEFORE BEGINNING
INSTALLATION AND/OR OPERATION OF
THIS EQUIPMENT.
Revised 01/27/2000
Filename: Manual_amc 1022M
Copyright © September 1989
The Armstrong Monitoring Corporation
(613) 225-9531 —
(613) 225-6965 — Fax
(800) 465-5777 —
U.S. Toll Free
www.armstrongmonitoring.com

Advertisement

Table of Contents
loading

Summary of Contents for AMC 1022M Series

  • Page 1 1022M AMC-1022M SERIES HAZARDOUS GAS MONITORING SYSTEM INSTRUCTION MANUAL IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION AND/OR OPERATION OF THIS EQUIPMENT. Revised 01/27/2000 Filename: Manual_amc 1022M Copyright © September 1989 The Armstrong Monitoring Corporation (613) 225-9531 — (613) 225-6965 — Fax (800) 465-5777 —...
  • Page 3: Table Of Contents

    GENERAL DESCRIPTION......................... 1 Figure 1.1 Three circuit miniature switch................... 2 Figure 1.2 AMC-1022M series monitor, front panel................. 3 Figure 1.3 AMC-1022M series monitor, inside front panel.............. 4 Figure 1.4 AMC-1022M series monitor, inside power/relay panel........... 5 INSTALLATION......................6 LOCATION AND MOUNTING.........................
  • Page 4: Warranty

    1022M WARRANTY The AMC-1022M series monitor is warranteed against defects in material and workmanship for a period of two years from date of delivery. During the warranty period, we will repair or replace components that prove to be defective in the opinion of the Armstrong Monitoring Corporation. We are not liable for auxiliary interfaced equipment, nor consequential damage.
  • Page 5: Specifications

    AMC- - - - 1022M 1022M 1022M 1022M SPECIFICATIONS Monitor Serial Number......................_______________ Power Supply Requirement ....................120 VAC, 60 Hz Fuse Type and Rating......................3AG, ___ Amp Operating Temperature Range...................... 0°C to 40°C Sensors/Transmitters Alarm Trip Points Chan. Type of Gas Part No.
  • Page 6: Introduction

    FEATURES ARE NORMALLY IDENTICAL FOR ALL CHANNELS. The AMC-1022M is a multi-sensor gas monitoring system designed to continuously monitor for traces of hazardous gases (listed in Specifications, page v). It can be calibrated to detect a wide variety of gases, and each channel can monitor a different gas.
  • Page 7 AMC- - - - 1022M 1022M 1022M 1022M 14. THREE CIRCUIT MINIATURE SWITCH -Each actuator on the miniature switch controls a different circuit as shown in Figure 1-1. If the actuator is set in the UP position, its corresponding circuit is ON.
  • Page 8 AMC- - - - 1022M 1022M 1022M 1022M FIGURE 1.2 AMC-1022M SERIES MONITOR, FRONT PANEL.
  • Page 9 AMC- - - - 1022M 1022M 1022M 1022M FIGURE 1.3 AMC-1022M SERIES MONITOR, INSIDE FRONT PANEL.
  • Page 10 AMC- - - - 1022M 1022M 1022M 1022M FIGURE 1.4 AMC-1022M SERIES MONITOR, INSIDE POWER/RELAY PANEL.
  • Page 11: Installation

    AMC- - - - 1022M 1022M 1022M 1022M 2 INSTALLATION 2.1 LOCATION AND MOUNTING Care should be taken to securely fasten the monitor (via four mounting holes provided) to a solid, vertical, nonvibrating surface or structure. See Figure 2-2 for mounting dimensions.
  • Page 12: Schedule Of Cable Sizes

    AMC- - - - 1022M 1022M 1022M 1022M FIGURE 2.1 MONITOR POWER SUPPLY CONNECTIONS. 2.3 SCHEDULE OF CABLE SIZES For maximum noise rejection, each cable shield and metal conduit should be grounded at the monitor. The following is a listing of maximum distances the sensors or transmitters may be located from the monitor for various cable sizes.
  • Page 13 AMC- - - - 1022M 1022M 1022M 1022M FIGURE 2.2 MONITOR MOUNTING DIMENSIONS.
  • Page 14 AMC- - - - 1022M 1022M 1022M 1022M FIGURE 2.3 REMOTE SENSOR/TRANSMITTER WIRING LAYOUT (ONE CHANNEL)
  • Page 15 AMC- - - - 1022M 1022M 1022M 1022M FIGURE 2.4 RELAY CONTACT ARRANGEMENT...
  • Page 16: Operation And Calibration

    The AMC-l022M series monitor is factory calibrated at levels based on set standards. Calibration of the monitor should be performed every 6 months, unless the alarm trip point settings need to be changed.
  • Page 17 AMC- - - - 1022M 1022M 1022M 1022M NOTE THE FOLLOWING PROCEDURE IS FOR REMOTE SENSOR ONLY. IF A TRANSMITTER IS USED, REFER TO ADJUSTMENTS IN CALIBRATION SECTION 3.2 IN THE APPROPRIATE TRANSMITTER MANUAL. The low alarm adjust is used to establish the low alarm trip point. This is done by exposing the sensor being calibrated to the low alarm gas concentration and adjusting the LO trimmer clockwise until the yellow LED just lights.
  • Page 18 AMC- - - - 1022M 1022M 1022M 1022M FIGURE 3.1 TRIMMER ADJUSTMENTS AND TEST POINT LOCATIONS.
  • Page 19: Maintenance

    AMC- - - - 1022M 1022M 1022M 1022M 4 MAINTENANCE 4.1 GENERAL The monitor should be wiped clean with a damp cloth following a regular maintenance program. Avoid spraying, submersion and other conditions that could cause a liquid to enter the monitor and cause possible intrinsic damage to internal components.