7.5. IP Tunneling Address Assignment ............... 20 Legal Notice ..................21 FAQ ....................22 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany KNX TP to IP Router KNX CP IP • from application 1.0 Version: 29.09.2021 • Subject to technical changes. Errors excepted.
Page 4
The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to- date version of the manual is available.
240 bytes APDU length are supported. KNX CP IP can be used to connect a KNX TP line or area to KNX IP or an Ethernet net- work. In this way, several TP lines, TP areas or different KNX TP installation systems can be connected via an IP Backbone, Ethernet network or the Internet.
Page 6
KNX CP IP in a network and to update the firmware via IP is provided. It is easy to identify the KNX CP IP in a network by remotely switching on its Programming LED.
The Manual Function switch-off time is 120 min KNXnet/IP KNX CP IP is a KNX IP router. KNX IP routers are highly similar to TP line couplers. The only difference is that they use the IP communication medium as main line and the KNXnet/IP communication protocol.
In network installations KNX CP IP is used as KNX IP line/area coupler to couple KNX IP and KNX TP. After connecting to KNX TP, KNX CP IP operates with its default set- tings. Setting the correct physical address is necessary to include KNX CP IP in the present KNX bus system.
5.3. KNX Network Installation For line coupler functionality in a KNX network KNX CP IP has to use the correct phys- ical address of a coupler (x.y.0, 1≤ x & y ≤15). In ETS, up to 225 addresses can be de- fined from 1.1.0 to 15.15.0.
To configure the device an interface connection (IP, USB) to the KNX bus system is re- quired. The device is supplied with the individual physical address 15.15.0. The KNX KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • Technical changes and errors excepted.
KNX CP IP automatically switches back to normal operation. To config- ure the Manual Function and set the Switch-off time use the parameter tab General like KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • Technical changes and errors excepted.
Lights red if not con- nected Bus State KNX TP green Group Address green: filter Routing orange: route all red: block all Physical Address Routing KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • Technical changes and errors excepted.
Page 13
Number Colour Comment State IP green Bus State KNX TP blinking green Telegram Traffic blinking not the same tempo green as LED2 Programming KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • Technical changes and errors excepted.
Make sure that during commissioning all KNX IP devices intended to communicate with each other via IP use the same multicast KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
For Group Telegrams and Physical Telegrams the setting "transmit all" is intended only for testing purposes. Please do not use for normal operation. KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
Page 16
• block If blocked an ETS download to the KNX CP IP can occur only via main line KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
If KNX CP IP is not visible as an UPnP network device a manual restart is recommended. After that, the device becomes visible in the list of network devices. KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
Use the MAC address in the form of AA-BB-CC-XX-YY-ZZ and the pre-set HTTP port to be entered in the browser´s URL bar as described here (without brackets): KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
KNX CP IP restarts and continues with normal operation. Step 1: Open the Update tab of the Web front-end. Fig. 8: Update Tab KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
Page 21
Clicking on the "Abort" button cancels the firmware update procedure and the device exits Boot Mode. Fig. 12: Select Update File KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
Fig. 14: Additional Tunneling Address Assignment in the Web Front-end KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.
The Device Info tab of the Web front-end and the list of Discovered Interfaces in ETS both show the actual IP address. KNX TP to IP Router KNX CP IP • Version: 29.09.2021 • from application 1.0 • Technical changes and errors excepted.